6.Operation data setting table
Digit
Meaning
Range
Default
Adjust(yes/no)
0
Tank set temperature hysteresis
0-30
℃
5
℃
yes
1
Water tank temperature setting
8-55
℃
55
℃
yes
2
Defrost Cycle
30-90Min
40Min
yes
3
The time point to enter defrosting in
heating
0-30
℃
-5
℃
yes
4
Exit defrost temperature
2-30
℃
15
℃
yes
5
Exit condition of defrost time
1-12Min
8Min
yes
6
Water tank temperature setting
range (55/65)
0-1
0
yes
7
Reserved
yes
8
Compensation(yes/no)
0-1
1
yes
9
Cyclic heating(yes/no)
0-1
1
no
A
Heater / pump selection
0-1
1
yes
B
Target superheat / 10
-F--F
0
no
C
Start temperature
10-55
47
no
D
Exhaust temperature
-9--99
℃
ajdusted by technicians
E
Pipe temperature
-9--99
℃
ajdusted by technicians
F
Reserved
-9--99
℃
ajdusted by technicians
10
Ambient temperature
-9--99
℃
ajdusted by technicians
11
The actual number of steps / 10
0-40
no
Running time
0-9999h
ajdusted by technicians
Fault indication / alarm code
Protection / Failure
Remote Controller
Water tank temp. sensor fault
F0
Coil temp.sensor fault
F1
Flow switch malfunction
F2
Ambient temperature sensor fault
F3
Protection of the exhaust temperature is too high
F4
High voltage protection of the system
F5
System voltage protection
F6
Exhaust temperature sensor fault
F7
The second time freezing protection in winter
F8
Wired remote communication failure
F9
Defrost
Defrost display
AIR SOURCE HEAT PUMP WATER HEATER