AFi MT-926C Instruction Manual Download Page 3

 

3

INSTALLATION AND OPERATION INSTRUCTIONS 

 

INTRODUCTION 

Thank you for purchasing your American Fibertek Series 926C multimode two channel video 
multiplexer with bi-directional multi-protocol data and contact closure. Please take a few minutes to 
read these installation instructions in order to obtain the maximum performance from this product. 
 

FUNCTIONAL DESCRIPTION 

The MT-926C operates as half of a transmitter / receiver pair for the digital transmission of two 
simultaneous NTSC or PAL video signals along with one channel of field configurable bi-directional 
data and one channel of bi-directional contact closure over one multimode fiber optic cable. The data 
channel may be configured as RS485 data, RS422 data, RS232 data, or Manchester data. The RS485 
channel may be configured for 2-wire (half duplex) or 4-wire (full duplex) with or without biasing. Switch 
selectable internal 120 ohm terminations are available for RS422 or RS485 data. 
 

NOTE: This unit is shipped with Data Channel 1 in the RS485 4-wire configuration. For other 
configurations, please refer to the DATA CONFIGURATION section for changes to the default 
switch settings. Data Channel 2 is set for contact closure and can not be reconfigured. 

 

NOTE: This unit is shipped with data terminations off and data bias off for Data Channel 1. For 
other configurations, please refer to the DATA TERMINATION / BIAS section for changes to the 
default switch settings.  

 
The MT-926C multiplexes two video input signals along with one data signal and one contact closure 
signal into a high speed serial data stream. This serial data stream modulates a laser at 1310nm 
wavelength. The MT-926C also detects and demultiplexes a return optical serial data stream containing 
one data signal and one contact closure signal at 1550nm wavelength.  
 
This unit is contained in a rugged aluminum housing with internal dc voltage regulation. The detachable 
terminal blocks and LED indicators provide for easy installation and monitoring of video, data, and 
optical power. 
 
The MT-926C is designed for mounting as a modular stand alone unit. For a rack mounted version 
please see the RT-926C. 
 

INSTALLATION 

THIS INSTALLATION SHOULD BE MADE BY A QUALIFIED SERVICE PERSON AND SHOULD 
CONFORM TO THE NATIONAL ELECTRICAL CODE, ANSI/NFPA 70 AND LOCAL CODES. 
  
Mount the unit to a secure surface using #8 (3mm) hardware in four places. See the drawing on the 
next page for mounting dimensions. Be sure to allow sufficient room for the required minimum bend 
radius of the fiber cable used. 
 

POWER SOURCE 

THIS PRODUCT SHALL BE POWERED BY A LISTED CLASS 2 POWER SUPPLY ONLY. 
 
This unit requires a +12VDC power source with a current rating of 1.25 amps for proper operation. The 
DC input is diode protected. In the USA and in Canada an American Fibertek PS-12D is supplied with 
this unit. The negative side of the power input is directly connected to ground. ANSI/NFPA 70 Class 2 
wiring is recommended. 

Summary of Contents for MT-926C

Page 1: ...10 02 2012 JPK Instruction Manual MT 926C Two Channel Video Transmitter With One Bi Directional Multi Protocol Data Channel And One Bi Directional Contact Closure Channel...

Page 2: ...deo Input Connections 4 Data Input Output Connections 4 Typical System Data Connections 5 Contact Closure Input Output Connections 5 Data Configuration Switches 5 Data Termination And Offset Bias Swit...

Page 3: ...RMINATION BIAS section for changes to the default switch settings The MT 926C multiplexes two video input signals along with one data signal and one contact closure signal into a high speed serial dat...

Page 4: ...appropriate 75 baseband video source such as a camera or a video recorder output For optimum performance the video cables should be the shortest length of coax practical DATA INPUT OUTPUT CONNECTIONS...

Page 5: ...res and which two wires are the receive data in wires Please note that Data In on the MT 926C becomes Data Out on the MR 926C or the RR 926C after going across the fiber The reverse flow follows the s...

Page 6: ...f the original RS422 protocol RS485 differs from RS422 in the ability of the transmitter devices to go into a high impedance Hi Z state This allows multiple transmitter devices to reside on the same w...

Page 7: ...he data contact closure coming in from the fiber through the MT 926C and out onto the electrical interface The intensity of this indicator will vary with input data patterns however in typical data ap...

Page 8: ...roducts have been tampered with This warranty shall be construed in accordance with New Jersey law and the courts of New Jersey shall have exclusive jurisdiction over this contract EXCEPT FOR THE FORE...