Table 14. Testing signals for AET100 transducer
Voltage, %
of the nominal value
Current, %
of the nominal value
Current phase
relative to the
voltage, degree
cos φ
5; 20; 50; 80; 100; 120
100
0
1
100
5; 20; 50; 80; 100; 120
0
1
Table 15. Testing signals for AET200 transducer
Voltage, %
of the nominal value
Current, %
of the nominal value
Current phase
relative to the
voltage, degree
cos φ
5; 20; 50; 80; 100; 120
100
0
1
100
5; 20; 50; 80; 100; 120
0
1
120
120
0
1
120
120
180
-1
100
100
60
0.5
90
0
150
-0.866
180
-1
-120
-0.5
-90
0
-30
0.866
Table 16. Testing signals for AET 300, AET 400 transducers
Voltage, %
of the nominal value
Current, %
of the nominal value
Current phase
relative to the
voltage, degree
cos φ
sin φ
5; 20; 50; 80; 100; 120
100
0
1
0
100
5; 20; 50; 80; 100; 120
0
1
0
120
120
0
1
0
120
120
180
-1
0
120
120
90
0
1
120
120
-90
0
-1
100
100
60
0.5
0.866
90
0
1
150
-0.866
0.5
180
-1
0
-120
-0.5
-0.866
-90
0
-1
-30
0.866
-0.5
Note
- Do not carry out measurements of the Q
FA
, Q
FB
, Q
FC
if phase angle is out-of-range
±
(30…150)
°