9- TROUBLESHOOTING 

Anomaly 

Possible failures 

Remedy 

The fan does not 

work 

There is no current 

Check the breaker / fuse 

The thermostat is damaged 

Check if there is power to the terminals of the fan (and / 

or 0-10V signal for EC) 

The cables are not 

connected 

Verify  all electrical connections within the wiring 

diagram suppled 

Condenser broken 

Replace capacitor (AC motor) 

Insufficient air flow 

 

Dirty filter 

Clean or replace the filter 

Battery dirty 

Clean the battery with lens cleaner 

Selected speed low 

Select a higher speed (max or med) 

Noisy fan 

 

Fan damaged 

Visually check that the fan is undamaged 

SOSTITUTION REQUIRED 

Fan loose 

Check that the fan is firmly secured to the machine 

frame 

Speed to much high 

Select a lower speed (min or med) 

In summer or 

winter hot air 

comes out cold air 

 

Water too hot / cold 

Check if temperature of  inlet water is less than 10 ° C 

in summer or more  40 ° C in winter. 

Water flow low 

Check if the dT between water input and output is at 

most 7K 

Valve closed 

Check that all manual valves are open to interception 

Valve Actuator broken 

Check that the actuator has opened the valve 

Air in the battery 

Purge the coil with the air valve 

Condensation on 

discharge grille 

 

Water too cool 

Raise the water inlet temperature 

Speed too low 

Increase the fan speed (med or max) 

Drip from the tank 

Condensate drain clogged 

Control the outflow of the exhaust pipe 

Pan counterslope 

Make sure the pan is level or tilted slightly towards the 

drain 

Water pipes are not 

insulated 

Insulate all pipes chilled water 

Faulty seals 

Check seals of hose connections 

Dirty pan 

Clean the pan to allow the normal flow of condensate 

10- DISPOSAL 

At  the  end  of  the  service,  the  unit  must  be  disposed  of  in  compliance  with  local  regulations  on  waste 

disposal. The main materials present are: copper, aluminum, steel, polystyrene, plastic. 

Summary of Contents for SOFFIO 101HP

Page 1: ...AERTESI srl SOFFIO INSTALLATION USE AND MANTEINANCE MANUAL Page 1 AER MIU GB SOFFIO 000 02 15 INSTALLATION USE AND MAINTENANCE MANUAL SOFFIO SOFFIO HP Ducted units...

Page 2: ...000 02 15 INDEX 1 INTRODUCTION 3 2 RECEPTION 3 3 POSITIONING 3 4 INSTALLATION 4 5 AERAULIC CONNECTIONS 6 6 IDRAULIC CONNECTIONS 7 7 ELECTRICAL CONNECTIONS 7 8 MANTENANCE 9 8 1 Filter 9 8 2 Fan motor...

Page 3: ...roperty resulting from the failure of requirements in this manual of regular maintenance or use of non original spare parts or change in the product status with respect to upon receipt Also in these c...

Page 4: ...lm and all guards before installation The machine must always be handled by two people and or with suitable lifting means for the larger sizes Apply four or six threaded rods M8 not provided to the ce...

Page 5: ...with fixing nut washer and nut M8 not supplied We recommend using a suitable system for not transferring to the structure some possible vibration vibration damping rubber or other material Antivibrat...

Page 6: ...the current standards and with attention for the safety of people 5 AERAULIC CONNECTIONS Connect the channels using the appropriate outlet flange It is advisable to interpose a flexible connection be...

Page 7: ...ecting pipe don t twist coils and valves it is recommended to use two wrench Valves can be supplied in the kit to be assembled by the installer or by delivered by the installer When the installation i...

Page 8: ...frequency of the power supply is 230V 50Hz Before attempting any operation on the unit check the main power supply is disconnected and can not be turned on unintentionally In the basic version the ele...

Page 9: ...accidentally inserted Make sure the engine is stopped before opening the panel of the box The motor the coil and the drainage pump do not require routine maintenance The filter instead requires period...

Page 10: ...n of the filter from below For vertical sizes is only possible extraction from the front In these cases you must remove the brackets that block the filter Removing the filter with engines with a high...

Page 11: ...move the bottom panel Then unscrew the M6 screws that secure the motor plate to the machine frame 2 screws for size 21 4 screws for size 31 38 5 screws for size 41 81 Fixing screw size 21 Fixing screw...

Page 12: ...operations in reverse order 8 3 Fan HP motor high pressure In versions High Prevalence after removing the bottom panel and disconnect the motor cables as described in the previous paragraph you must r...

Page 13: ...lower speed min or med In summer or winter hot air comes out cold air Water too hot cold Check if temperature of inlet water is less than 10 C in summer or more 40 C in winter Water flow low Check if...

Page 14: ...___________ ________________________________________________ ________________________________________________ ________________________________________________ _________________________________________...

Page 15: ...Aertesi srl Unipersonale viale della tecnica 6a 35026 Conselve PD ITALY t 39 049 9501109 f 39 049 9500823 www aertesi com info aertesi com AER MIU GB SOFFIO 000 02 15...

Reviews: