Aerovent IM-200 Installation, Operation And Maintenance Instructions Download Page 4

A Twin City Fan Company

5959 Trenton Lane  • Minneapolis, MN 55442-3238
Phone (612) 551-7500  • Fax (612) 551-7501 •  www.aerovent.com

Units ordered with the high-low fire option are supplied
with a 1" NPT SR600 two-stage valve mounted in the
pipe train.

The SR600 provides an economical means of flame

staging where infinite modulation is not required. Turn-
down on low-fire is from 25% to 75% of high-fire. This
valve is powered by a 24 volt AC transformer. When the
coil is energized, the valve is at low-fire. When the coil
is de-energized, it is at high-fire.

Adjustments

To check the minimum or low-fire and maximum or
high-fire pressures for the limits of modulation or stag-
ing, use the following procedures:

To set minimum or low-fire

1. Remove cover plate 

.

2. Remove high fire adjusting screw 

, spring 

, and

plunger 

. A small magnet is useful for this purpose.

Handle plunger carefully to avoid marring or collect-
ing dirt. Do not lubricate.

3. Modulation or Staging: Using low-fire adjusting

screw 

, set manifold pressure to manufacturer’s

specifications (50% to 75% of high-fire).

4. Modulation or Staging: Cycle solenoid gas valve to

check for proper ignition.

5. Modulation or Staging: Adjust air shutter or increase

low-fire adjustment if needed.

6. Replace plunger, spring and high-fire adjusting

screw.

To Set Maximum or High-Fire:

Note:

To avoid danger of over-firing, make certain that

inlet pressure is at 1.0" w.c. above the outlet pressure.

High-Low Fire Option

1

2

3

5

4

Make sure
plunger is
installed as
above.

1. Modulation and Staging: Using high-fire adjusting

screw 

, set manifold pressure to manufacturer’s

specifications. See page 1, Fig. 1.

2. Staging Only: Cycle burner to check performance.

3. Replace cover plate.

Summary of Contents for IM-200

Page 1: ...pressure and length of the run Required gas input can be determined by the chart Fig 1 Fig 1 NATURAL GAS INPUT NOMINAL GAS MODEL NO BTU TEMP RISE PRESS 24S728 325 000 73 F 1 oz NDH 440 000 99 F 2 oz 3 4 HP 580 000 131 F 3 oz 440 000 66 F 2 oz 580 000 85 F 3 oz 24S728 680 000 102 F 4 oz NDH 790 000 118 F 5 oz 2 HP 870 000 130 F 6 oz 990 000 148 F 7 oz PDH Propane units 4 Mount operating station in ...

Page 2: ...ly when door is completely open Installation 3 Overhead Location Switch is in free position when door is open Use switch terminals 1 and 2 Heater will fire when door starts to open FREE POSITION 360 location on actuator shaft ACTUATOR SHAFT OPERATING HEAD May be relocated four 90 positions LEVER LOCKING NUT Loosen to to relocate free position of adjustable roller lever TERMINAL CONNECTIONS 1 2 Nor...

Page 3: ...set at 200 F If spark is not occurring check spark plug Gap should be 072 and electrode should be clean no carbon If flame relay has power to it but flame cycle will not occur reset flame relay manual reset If flames comes on momentarily and goes out check flame rod There should not be any cracks in porcelain Flame rod senses current in flame To check if it is functioning plug voltmeter into ampli...

Page 4: ...ate 2 Remove high fire adjusting screw spring and plunger A small magnet is useful for this purpose Handle plunger carefully to avoid marring or collect ing dirt Do not lubricate 3 Modulation or Staging Using low fire adjusting screw set manifold pressure to manufacturer s specifications 50 to 75 of high fire 4 Modulation or Staging Cycle solenoid gas valve to check for proper ignition 5 Modulatio...

Reviews: