Aerotechnik Siegwart Multi-leaf dampers Installation Instructions Download Page 2

Installation instructions 

Operation and maintenance directions for multi-leaf dampers

 
 
 

1. Transport: 

The blades of the multi-leaf dampers must not be lifted up during transport. This 
could result in damage due to distortion. The multi-leaf dampers should not be used 
as a “ladder”. 

 

2. Operation:

 

The blades must be operated only by means of the drive shaft. Operation by rotating 
the blades is not permitted. The drive shafts have a diameter of 12 mm or a form-fit 
execution of SW 9 mm. 

 

3. Installation:

 

The installation of the dampers between ducts, on the wall or within devices (air 
conditioning equipments, ventilating devices) must be performed without warping, 
free of tensions, planely and in an exact angle of 90°. The multi-leaf dampers must 
be closed during installation. 

 

4. Maintenance:

 

Depending on the degree of soiling of the medium, dry cleaning should be performed 
periodically. Attention: do not clean the dampers with cleaning products, otherwise 
the seals will be damaged! Furthermore, the dampers are to be operated periodically 
according to the system-dependent conditions. This prevents adhesion of the blade 
seals, if the blades are closed. 

 

5. Accident risks:

 

Do not reach into the blades. 
Do not lift up or carry the dampers by the blades. 
A risk of injury exists on the gearwheels and the sharp edges. 

Aerotechnik E. Siegwart GmbH 

Untere Hofwiesen • D 66299 Friedrichsthal • Germany 

Tel.: + 49 6897 - 859 0 

Fax: + 49 6897 - 859 150 

[email protected] 