28
Chapter 2
www.aerotech.com
2.1.2. Motor Supply Connections (TB102)
N O T E :
This product requires two power supply connections. The Motor Supply and Control Supply
must both be connected for proper operation.
Motor power is applied to the Soloist HPe 10/20/30 Motor Supply connector (refer to
for locations).
Refer to local electrical safety requirements to correctly size external system wires and match wires to
fuses or circuit breakers.
The AC1 input is internally fused (5A HPe10, 10A HPe20/30). External fuses or a circuit breaker (15 A
maximum, time delay type) are required for the AC1 and AC2 inputs. The AC2 input can be connected
directly to Neutral without a fuse for single phase power systems.
W A R N I N G : Do not operate the Soloist HPe 10/20/30 without the safety ground connection in
place.
W A R N I N G : Do not operate the Soloist HPe 10/20/30 without proper branch protection.
An AC Line Filter may be required for CE compliance and should be located as close as possible to the drive.
For more information about the AC Line Filter, refer to
Wiring between the filter and drive can
be twisted and/or shielded to reduce radiated emissions.
Figure 2-2:
Motor Bus Input Connections
Table 2-3:
Motor Supply Input Connections (TB102)
Pin
Description
Recommended Wire Size
(1)
AC1
240 VAC Motor Power Input
1.3 mm
2
(#16 AWG)
AC2
240 VAC Motor Power Input
1.3 mm
2
(#16 AWG)
Protective Ground (required for safety)
1.3 mm
2
(#16 AWG)
(1) Refer to local electrical safety requirements to correctly size external system wires.
Table 2-4:
Mating Supply Part Numbers for the Motor Supply Connector (TB102)
Description
Aerotech P/N
Phoenix P/N
Tightening
Torque (Nm)
Wire Size:
mm
2
[AWG]
7-Pin Terminal Block
ECK01114
1754546
0.5 - 0.6
3.3 - 0.516 [12-30]
Soloist HPe 10/20/30
Installation and Configuration