CONNECTING TO AN EXTERNAL FUEL TANK
(BLAZE 600 D TURBO)
Beckett CF800 is fitted with 3/8” SAE male fittings and is set up for a 2 line system to eliminate
priming. Ensure fuel tank has a supply line and a return line and connect the supply line to the 3/8”
SAE fitting on the inlet side of the fuel filter and the return line to the return fitting located on the
Beckett Burner pump. For a 1 line system remove bypass plug located on inlet port of Beckett
Pump and just connect fuel line to inlet side of fuel filter.
ELECTRICAL
WARNING: ELECTRICAL GROUNDING INSTRUCTIONS
THIS APPLIANCE IS ABLE IS TO RECEIVE 1 PHASE
120V SUPPLY MUST BE AVAILABLE.
INSTALLATION
10/3 upto 100ft
NOTE: IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE MUST BE
REPLACED, IT MUST BE REPLACED WITH TYPE TEW 14GA WIRE OR ITS EQUIVALENT.
ELECTRICAL SYSTEM
BLAZE
600 D
Volts-Hertz-Phase
120-60-1
Full Load (Amps) (1PH)
11.5
Max fuse size (Amps) (1PH)
with time delay
15
The electrical grounding of the heater shall be in compliance with the National Electrical Code, ANSI/NFPA
70, or the CSA C22.1, Canadian Electrical Code, Part I
CAMPO EQUIPMENT CO. LTD. (ECOBLAZE)
6 Carson Court, Brampton, ON, CANADA, L6T 4P8
Tel: (905) 793-2525 | Fax: (905) 793-8768 |
www.campoequipment.com