27
STANDARD RATINGS
Size
ver.
0300
0330
0350
0500
0550
0600
0650
0700
System side heat exchanger
Min. flow rate
°
gpm
-
-
-
29.94
36.10
36.10
48.21
48.21
L
gpm
17.61
25.98
29.94
29.94
36.10
36.10
48.21
48.21
Max. flow rate
°
gpm
-
-
-
248.76
248.76
248.76
248.76
248.76
L
gpm
248.76
248.76
248.76
248.76
248.76
248.76
248.76
248.76
Source side heat exchanger
Min. flow rate
°
gpm
-
-
-
29.94
36.10
36.10
48.21
48.21
L
gpm
17.61
25.98
29.94
29.94
36.10
36.10
48.21
48.21
Max. flow rate
°
gpm
-
-
-
248.76
248.76
248.76
248.76
248.76
L
gpm
248.76
248.76
248.76
248.76
248.76
248.76
248.76
248.76
Minimum water operating pressure (PN)
psi
7,3
7,3
7,3
7,3
7,3
7,3
7,3
7,3
Maximun water operating pressure (PN)
psi
116,0
116,0
116,0
145,0
145,0
145,0
145,0
145,0
Cooling
System side water (in/out)
54.00 °F / 44.01 °F
Source side water (in/out)
84.99 °F / 94.30 °F
Heating
System side water (in/out)
104 °F / 113 °F
Source side water (in/out)
50.00 °F / 44.60 °F
OPERATING RANGE
The units, in standard configuration, are not suitable for installation in salty environment.
The values indicated in the table refer to the min. and max. limits of the unit.
If the unit operates beyond the operational limits, we recommend you first contact our technical-sales service.
OPERATING COOLING MODE RANGE
Key
A
Processed water temperature (source side) (°F)
B
Water produced (system side) (°F)
1
Cooling mode
0.0
20.0
40.0
60.0
68.0
80.0
100.0
120.0
140.0
160.0
°F
10.0
20.0 24.8 30.0
40.0
50.0
60.0
68.0
80.0
°F
B
140.0
95.0
1
A