If economy mode has been set in the system, the work setting
will be varied dynamically based on the actual system demand;
this variation is performed every given amount of time, modifying
the setting by increasing it or decreasing it by a certain value
(while remaining within the limits described by the bands set
for Economy mode in heating and cooling); this parameter
determines by how much the work setting is increased if the
control on the system requires it (value between 0.1 and 2.0°C);
to set this value it is necessary to:
(1) Enter modifi cation mode by pressing the
C
key; after
this key has been pressed, the current band value will be
highlighted.
(2) Press the
A
or
B
key to modify the band value to be
applied to the heating work setting during Economy mode.
(3) Press the
C
key to confi rm the value entered; once this
key has been pressed, the current setting will be highlighted
normally, thus indicating that the modifi cation procedure has
concluded.
After the data has been entered, it will be possible to:
- Pass on to the following window by pressing the
B
key.
- Go back to the previous window by pressing the
A
key.
- Press the
D
key to return to the selection of the menus.
• Set the extent for increase of setting in ECONOMY mode
The proposed example hypothesises that
the automatic increase (if necessary) at
each control during Economy mode is
0.5°C.
A
B
C
D
Incr. optimization
ESC
0.5 C
Δ
+
When the system demands domestic hot water, the unit will
produce hot water at the temperature indicated in this parameter
(the value can be between 30.0 and 70.0°C); to set this value it
is necessary to:
(1) Enter modifi cation mode by pressing the
C
key; after
this key has been pressed, the current band value will be
highlighted.
(2) Press the
A
or
B
key to modify the cooling work setting
of the chiller.
(3) Press the
C
key to confi rm the value entered; once this
key has been pressed, the current setting will be highlighted
normally, thus indicating that the modifi cation procedure has
concluded.
After the data has been entered, it will be possible to:
- Pass on to the following window by pressing the
B
key.
- Go back to the previous window by pressing the
A
key.
- Press the
D
key to return to the selection of the menus.
ATTENTION: this parameter is read only if the unit
has the Moducontrol board.
• Set the domestic hot water temperature for the chiller
In the proposed example, this parameter
is read-only as the selected unit (ANLI) is
equipped with a moducontrol board.
A
B
C
D
Hot setting for
ESC
60.0 C
sanitary water