26
Aermec 17.12 Cod. 5799550_01
17. INSTALLATION
17.1. PRELIMINARY FUNCTIONS
Prepare the installation for an electrical power supply and connection for the wired control panel.
Prepare a suitable condensate drain system.
To install the unit proceed as follows.
- For wall mounted installations maintain
a minimum distance of 160 mm from the
floor.
- For ducted installations provide the duct
connections to the unit and refer to
the drawing for dimensional data. The
discharge is provided with a connection
flange.
- For wall or ceiling installations use expan-
sion plugs (not provided) and ensure the
unit is installed level.
- For ceiling hung installations use four M8
threaded rods to support the frame. Fix
the unit to the threaded rods using eight
nuts of which four are self locking nuts.
Adjust the nuts to ensure that the unit is
installed level.
- WARNING: The fan coil unit must be
installed perfectly level otherwise the
condensate may not discharge correctly.
- Carry out the hydraulic connections as
detailed in the relevant chapter. It is
recommended that the water piping is
properly insulated.
- Carry out the condensate discharge
connection as detailed in the relevant
chapter. Fan coil units operating as heat-
ing only do not require a condensate
discharge.
- Carry out the electrical connections as
detailed in the relevant chapter and as
shown on the electrical wiring diagrams.
- Carry out the installation and connection
of any accessories.
- Start the fan coil unit and check the
operation of the components and all the
functions.
160
mm
160
mm
17.2. UNIT INSTALLATION
When using the flange, supplied with the
machine, do the following:
Take out the bag containing the
components supplied with the fan
compartment by removing the air filter in
advance, as indicated in the instructions
Fit first the two side bars using four screws
in the bag supplied screwing them into
the 4 holes in the sides of the unit
Paste the / The adhesive strips in the lower
part of front and rear cross-members,
Lay the two crosspieces to the car and
through the remaining 4 screws to fix the
cross to those previously placed
Note in the event of non-use of the flange,
however, extract the bag of accessories
out of the car.
INSTALLATION OF THE AIR OUTLET FLANGE