background image

030 -040 -130 - 140 -230 -240 - 330 - 340

VED

IVEDPI 1902 - 4460510_00

FAN COILS

for horizontal and vertical ducted installation

Technical Manual

Summary of Contents for VED

Page 1: ...030 040 130 140 230 240 330 340 VED IVEDPI 1902 4460510_00 FAN COILS for horizontal and vertical ducted installation Technical Manual ...

Page 2: ...y units with air quality sensors up to 3 optimising the performance in air conditioning and heating ensuring comfort and energy savings INDEX IMPORTANT INFORMATION AND MAINTENANCE 18 PACKAGING 18 USE 18 UNIT DESCRIPTION 19 SYSTEM EXAMPLES 20 MAIN COMPONENTS 20 COMPONENT DESCRIPTION 21 INSTALLATION INFORMATION 23 ROTATINGTHE COIL 26 TECHNICAL DATA 27 COOLING CAPACITY 28 PRESSURE DROPS COOLING ONLY ...

Page 3: ...ECIAL CLEANING The possibility of removing the fan coil unit inspection panels carried out only by personnel suitably qualified allows detailed cleaning of the internal parts particularly for installations with high occupancy or requiring elevated hygiene standards DURING OPERATION Always leave the filter in the fan coil unit during operation otherwise dust in the air will dirty the surfaces of th...

Page 4: ...range of control panel accessories Prepared for installation into the VMF system Wide possibility of different available static pressures Versions with 6 speed fan motor from which the preferred 3 are selected Versions with 7 speed fan motor from which the preferred 3 are selected Centrifugal fan designed for low noise levels G3 class filter Air intake filter easily extracted for periodic cleaning...

Page 5: ...g 6Vent drain on coil 7Hydraulic connections 8Condensate discharge 9Mounting slot 10 Air filter intake 11 Filter lock 10Centrifugal fan 12Electric motor electrical box 13Electric motor 14 Front panel enclosure lower 15 Electrical connections VED 030 VED 040 VED 130 VED 140 VED 230 VED 240 VED 330 VED 340 2 3 1 4 6 17 13 11 14 15 16 10 11 5 7 8 9 18 19 12 5 20 21 C F C VC F VC C F C VC F VC SA VC F...

Page 6: ...standard velocities Refer to the wiring diagram before modifying the motor connections VED0_ VED1_ VED2 6 speed fan motor VED3 7 speed fan motor STRUCTURE Manufactured in galvanised sheet steel of adequate thickness Class 1 internal insulation Posterior part has fixing holes for installation Intake and discharge openings are designed to connect the fan coil unit to any type of air ducting The disc...

Page 7: ...ion of the 3 way valve accessory is recommended Water temperature In order to avoid air stratification and therefore achieve better mixing it is advised not supply the fan coil unit with water hotter than 65 C The use of very hot water could cause creaking due to the thermal expansion of the different components plastics and metals This does not cause damage to the unit if the maximum operating te...

Page 8: ...ections in the motor electric box The fan coil units are supplied with the connections to the standard velocities Refer to the wiring diagram before modifying the motor connections If the valve is installed the minimum temperature water sensor can be installed in two positions in its mount in the coil to the flow tube upstream of the valve Refer to the thermostat manual before selecting the positi...

Page 9: ...ed to use the condensate drain connection on the side of the hydraulic connections For horizontal installations mount the condensate discharge drain connection provided loose Care should be taken to seal the fitting between the drain pan and the drain connection with silicone sealant Seal the drain not used Connect the drain pan fitting to the condensate drain system Use a drain tube that must be ...

Page 10: ... constant updates Always refer to the wiring diagrams inside the unit The control panel cannot be mounted on a metallic wall unless this is permanently earthed Carefully read the instructions before installing the control panel and if necessary proceed with the configuration of the panel Some controls panels require connection to other components supplied as accessories ensure these are available ...

Page 11: ...charg es on both sides remove the electrical connections from the right side remove the knock out and move the grommet 9 from right to left move the electrical connections to the left side passing through the grommet 9 move the terminal block 10 and the earth connection 11 to the left side ROTATING THE COIL A B 180 COIL ROTATION DRAWING VED040 VED140 VED240 VED340 A B 180 VED030 VED130 VED230 VED3...

Page 12: ... 250 296 480 525 538 624 760 824 4 l h L 170 193 358 390 445 499 633 685 Water pressure drops 4 kPa H 9 14 31 23 44 37 18 26 4 kPa M 7 12 27 20 36 31 14 21 4 kPa L 3 5 15 11 25 16 10 16 Air flow rate m3 h H 285 277 433 420 590 570 805 775 m3 h M 256 249 397 386 524 509 704 685 m3 h L 161 160 287 280 417 406 572 563 Fans tipo centrifugal n 1 1 2 2 2 2 3 3 Input power Pa H 61 61 60 60 64 63 66 64 Pa...

Page 13: ...s w Sensitive cooling capacity Qv m3 h Air flow rate H maximum speed M medium speed L minimum speed NB The yield values marked in bold indicate the nominal value To calculate the cooling capacity yielded the values shown in the table must be multiplied by the corrective factors referred to the different speeds Sensitive yield values greater than the total yield indicate that cooling occurs without...

Page 14: ... 31 1480 1480 1324 1535 1208 1208 1092 1092 975 975 19 21 1914 986 1648 845 1356 696 1022 543 594 362 23 1904 1123 1640 982 1349 837 1018 685 592 501 25 1895 1255 1633 1114 1344 970 1015 818 592 592 27 1885 1383 1624 1242 1337 1097 1010 941 744 744 29 1875 1512 1615 1373 1330 1230 1004 1004 861 861 31 1867 1639 1610 1500 1327 1327 1092 1092 975 975 21 21 2299 981 2038 842 1754 700 1439 555 1073 39...

Page 15: ...31 1732 1732 1549 1668 1414 1414 1278 1278 1140 1140 19 21 2239 1072 1928 919 1587 756 1196 590 695 393 23 2227 1221 1918 1067 1578 910 1191 744 692 545 25 2217 1364 1911 1211 1573 1055 1188 889 692 692 27 2205 1504 1900 1350 1564 1193 1181 1023 870 870 29 2193 1643 1890 1493 1556 1337 1175 1174 1007 1007 31 2184 1781 1884 1631 1552 1477 1278 1278 1140 1140 21 21 2690 1066 2384 915 2052 761 1684 6...

Page 16: ... 2444 2582 2230 2230 2015 2015 1799 1799 19 21 3532 1660 3041 1422 2503 1171 1886 913 1096 609 23 3513 1890 3026 1652 2490 1408 1879 1153 1092 844 25 3497 2111 3014 1875 2481 1633 1873 1377 1092 1075 27 3479 2328 2997 2090 2467 1846 1863 1584 1373 1373 29 3460 2544 2981 2311 2454 2070 1853 1817 1588 1588 31 3446 2758 2971 2525 2448 2287 2015 2015 1799 1799 21 21 4243 1651 3761 1416 3236 1178 2656 ...

Page 17: ... 2683 2928 2448 2448 2212 2212 1975 1975 19 21 3877 1882 3339 1613 2747 1328 2071 1036 1204 690 23 3856 2143 3321 1874 2733 1597 2063 1307 1199 957 25 3839 2394 3309 2126 2724 1851 2056 1561 1199 1199 27 3819 2640 3290 2370 2708 2094 2045 1796 1507 1507 29 3798 2885 3273 2621 2694 2348 2034 2034 1743 1743 31 3782 3127 3262 2863 2687 2593 2212 2212 1975 1975 21 21 4657 1872 4129 1606 3553 1336 2916...

Page 18: ... 2789 3336 2545 2545 2300 2300 2053 2053 19 21 4030 2144 3471 1837 2856 1512 2152 1180 1251 787 23 4009 2442 3453 2135 2841 1820 2144 1489 1246 1090 25 3991 2727 3440 2422 2831 2109 2138 1778 1246 1246 27 3970 3007 3420 2700 2815 2385 2126 2047 1567 1567 29 3948 3287 3402 2986 2800 2675 2115 2115 1812 1812 31 3932 3563 3391 3262 2794 2794 2300 2300 2053 2053 21 21 4841 2133 4292 1829 3693 1522 303...

Page 19: ...78 3725 2991 2991 2703 2703 2413 2413 19 21 4737 2395 4080 2052 3357 1689 2530 1317 1471 878 23 4712 2727 4058 2384 3339 2032 2520 1663 1465 1217 25 4691 3046 4043 2705 3328 2355 2513 1986 1465 1465 27 4666 3358 4020 3015 3309 2663 2499 2285 1842 1842 29 4641 3670 3999 3334 3291 2987 2486 2486 2130 2130 31 4622 3978 3985 3642 3284 3284 2703 2703 2413 2413 21 21 5691 2381 5045 2043 4341 1700 3562 1...

Page 20: ...77 4618 3721 3721 3362 3362 3001 3001 19 21 5892 2969 5074 2543 4175 2094 3147 1633 1829 1089 23 5861 3380 5048 2955 4154 2519 3135 2061 1822 1509 25 5835 3776 5029 3353 4139 2920 3125 2462 1822 1822 27 5803 4163 5000 3738 4115 3302 3109 2833 2291 2291 29 5772 4551 4974 4133 4094 3703 3092 3092 2649 2649 31 5748 4933 4957 4515 4084 4084 3362 3362 3001 3001 21 21 7078 2952 6275 2533 5399 2107 4431 ...

Page 21: ...71 4930 3989 3989 3604 3604 3217 3217 19 21 6316 3169 5439 2715 4476 2235 3373 1743 1961 1162 23 6283 3608 5411 3154 4453 2689 3361 2200 1953 1610 25 6255 4030 5391 3579 4437 3117 3350 2628 1953 1953 27 6221 4444 5360 3990 4412 3525 3332 3024 2456 2456 29 6188 4857 5332 4412 4388 3952 3314 3314 2840 2840 31 6162 5265 5314 4820 4378 4366 3604 3604 3217 3217 21 21 7588 3152 6726 2703 5788 2249 4750 ...

Page 22: ...2362 2186 2013 10 2597 2415 2233 2054 1876 15 2432 2245 2057 1870 1683 40 5 1881 1705 1532 1356 1185 10 1727 1543 1361 1177 987 15 1498 1294 1048 682 391 VED030 Ta D B C 16 18 20 22 24 Tw C Ph Ph Ph Ph Ph in dt W W W W W 70 5 3351 3177 3004 2835 2667 10 4041 4683 3688 3514 3341 15 3930 3751 3575 3398 3227 60 5 3472 3296 3117 2943 2769 10 3246 3072 2901 2730 2561 15 3117 2943 2769 2596 2424 50 5 25...

Page 23: ...3419 3077 40 5 3439 3117 2801 2479 2167 10 3158 2821 2489 2152 1804 15 2739 2366 1916 1247 715 VED340 Ta D B C 16 18 20 22 24 Tw C Ph Ph Ph Ph Ph in dt W W W W W 70 5 9950 9435 8919 8418 7918 10 11998 13906 10951 10435 9919 15 11670 11139 10615 10091 9583 60 5 10310 9786 9255 8739 8223 10 9638 9122 8614 8106 7606 15 9255 8739 8223 7707 7199 50 5 7613 7105 6605 6113 5628 10 7262 6754 6245 5745 5245...

Page 24: ...2660 2485 50 5 2628 2453 2280 2110 1943 10 2507 2331 2156 1983 1810 15 2347 2167 1986 1805 1624 40 5 1816 1646 1479 1309 1144 10 1667 1489 1314 1136 952 15 1446 1249 1012 658 378 VED030 BV030 Ta D B C 16 18 20 22 24 Tw C Ph Ph Ph Ph Ph in dt W W W W W 70 5 2017 1913 1808 1707 1605 10 2432 2819 2220 2115 2011 15 2366 2258 2152 2046 1943 60 5 2090 1984 1876 1772 1667 10 1954 1849 1746 1643 1542 15 1...

Page 25: ...PS COOLING ONLY 2 PIPE SYSTEM PRESSURE DROPS HEATING ONLY 4 PIPE SYSTEM PRESSURE DROPS HEATING ONLY 0 10 20 30 40 50 60 70 80 90 0 100 200 300 400 500 600 700 VED 030I VED 130I VED 230I 0 0 440 0 881 1 321 1 761 2 201 2 642 3 082 0 34 68 102 136 171 205 239 273 307 Coil pressure drops kPa 0 20 40 60 80 100 120 0 200 400 600 800 1000 1200 1400 1600 1800 VED 030I VED 040I VED 130I VED 140I VED 230I ...

Page 26: ... it is possible to increase maximum speed by modifying the settings of the motor dip switches see Installation information chapter FLOW STATIC PRESSURE VED 030 VED 40 0 10 20 30 40 50 60 70 80 90 0 0 0015 0 0029 0 0044 0 0058 0 0073 0 0087 0 0102 0 0116 0 0131 150 200 250 300 350 400 450 500 88 29 117 72 147 14 176 57 206 00 235 43 264 86 294 29 V1 V2 V3 V4 V5 V6 Air flow rate m3 h Input Pa 0 10 2...

Page 27: ...7 0 0102 0 0116 147 14 176 57 206 00 235 43 264 86 294 29 323 72 353 15 382 58 412 00 Air flow rate m3 h Input Pa VED 140 0 10 20 30 40 50 60 70 80 250 300 350 400 450 500 550 600 650 700 V2 V3 V1 V4 V5 V6 0 0 0015 0 0029 0 0044 0 0058 0 0073 0 0087 0 0102 0 0116 147 14 176 57 206 00 235 43 264 86 294 29 323 72 353 15 382 58 412 00 Input Pa Air flow rate m3 h ...

Page 28: ...0 0102 0 0116 147 14 176 57 206 00 235 43 264 86 294 29 323 72 353 15 382 58 412 00 Air flow rate m3 h Input Pa 0 10 20 30 40 50 60 70 80 90 400 450 500 550 600 650 700 750 800 850 900 V1 V2 V3 V4 V5 V6 0 0 0015 0 0029 0 0044 0 0058 0 0073 0 0087 0 0102 0 0116 0 0131 235 43 264 86 294 29 323 72 353 15 382 58 412 00 441 43 470 86 500 29 529 72 Input Pa Air flow rate m3 h ...

Page 29: ...9 323 72 353 15 382 58 412 00 441 43 470 86 500 29 529 72 559 15 588 58 618 01 647 44 Air flow rate m3 h Input Pa VED 340 0 10 20 30 40 50 60 70 80 90 100 500 550 600 650 700 750 800 850 900 950 1000 1050 1100 V2 V3 V1 V4 V5 V6 V7 0 0 0015 0 0029 0 0044 0 0058 0 0073 0 0087 0 0102 0 0116 0 0131 0 0145 294 29 323 72 353 15 382 58 412 00 441 43 470 86 500 29 529 72 559 15 588 58 618 01 647 44 Input ...

Page 30: ... Yield GLYCOL WATER AT 10 GLYCOL WATER AT 35 GLYCOL WATER AT 20 IN COOLING MODE IN HEATING MODE Average glycol water temperature Corrective factor Average glycol water temperature Corrective factor Average glycol water temperature Corrective factor Average glycol water temperature Corrective factor Average glycol water temperature Corrective factor Key ...

Page 31: ... 0 32 6 28 4 31 2 29 8 25 6 19 4 18 0 13 9 2500 31 5 30 1 26 0 28 3 26 8 23 0 15 7 14 1 10 8 3150 28 3 26 6 23 6 25 1 23 2 20 6 12 6 10 6 8 3 4000 24 1 22 7 18 4 20 6 19 3 14 9 6 8 5 4 5 4 5000 21 4 20 4 14 5 17 7 16 9 10 1 5 0 3 7 3 7 6300 17 4 16 4 10 3 13 8 13 0 6 0 5 6 3 5 3 5 8000 13 0 11 6 7 4 9 8 8 1 4 8 7 5 4 9 4 9 10000 11 9 8 6 9 1 10 9 8 0 7 9 11 2 8 5 8 5 dB A tot 55 5 54 50 0 53 5 52 ...

Page 32: ... 28 4 31 9 30 8 25 5 22 2 21 0 15 9 2500 32 3 31 1 26 0 29 0 27 8 22 9 18 5 17 1 12 8 3150 29 0 27 6 23 6 25 8 24 2 20 5 15 2 13 6 10 3 4000 24 8 23 7 18 4 21 4 20 3 14 8 10 9 8 4 7 4 5000 22 2 21 4 14 5 18 6 17 9 10 0 9 2 6 7 5 7 6300 18 2 17 4 10 3 14 6 14 0 5 9 9 0 6 5 5 5 8000 13 7 12 6 7 4 10 5 9 1 4 7 10 4 7 9 6 9 10000 12 4 9 6 9 1 11 4 9 0 7 8 14 0 11 5 10 5 dB A tot 56 2 55 0 50 0 49 2 53...

Page 33: ... 6 46 6 44 8 41 9 26 1 24 4 21 2 1000 46 9 46 0 39 7 43 3 42 5 36 0 25 1 24 2 17 5 1250 43 9 42 5 38 5 40 4 39 0 34 8 21 5 20 2 15 6 1600 39 3 38 0 33 5 35 7 34 4 29 9 15 9 14 6 10 2 2000 38 0 36 6 32 4 34 2 32 8 28 5 13 4 12 0 7 9 2500 35 5 34 1 30 0 31 2 29 8 25 9 9 7 8 1 4 8 3150 32 3 30 6 27 6 28 1 26 2 23 5 6 6 4 6 2 3 4000 28 1 26 7 22 4 23 6 22 3 17 8 6 4 2 5 4 2 5000 25 4 24 4 18 5 20 7 19...

Page 34: ...da ambiente SC Scheda di controllo Electronic control board Platine de contrôle Steuerschaltkreis Tarjeta electrónica de control SW Sonda minima temperatura acqua Water low temperature sensor Sonde minimum temp eau Wasserfühler Sonda temperatura mínima del agua TR Trasformatore Transformer Transformateur Transformator Transformador TSR Termostato a riarmo automatico Automatic resetting thermostat ...

Page 35: ...femelle Wasseranschlüsse für Wärmetauscher für reinen Heizbetrieb Innengewinde Conexiones hidráulicas batería sólo calor hembra 030 040 130 140 230 240 330 340 Ø 1 2 G 1 2 G 1 2 G 1 2 G Attacchi scarico condensa diametro esterno Condensate discharge connections external diameter Raccords d évacuation des condensats diamètre extérieur Anschlüsse für Kondensatablass Außendurchmesser Conexionesdedesc...

Page 36: ...ale Manual resetting thermostat Thermostat à réarmement manuel Thermostat manueller Entriegelung Termostato de rearme manual VCF Valvola solenoide Solenoid valve Vanne solenoide Magnetventil Válvula solenoide VC Valvola solenoide caldo Solenoid valve hot Vanne magnétique chaud Magnetventil Heizbetrieb Válvula solenoide para calor VF Valvola solenoide freddo Solenoid valve cold Vanne magnétique fro...

Page 37: ... 5 6 M 1 CM MA BL MA BL MIN RO MED MA MAX NE COM BL Low Hi VED030 040 130 140 230 240 SCHEMA DI COLLEGAMENTO MOTORE MOTOR CONNECTION DIAGRAM SCHEMA DE RACCORDEMENT MOTEUR ANSCHLUSSPLAN MOTOR ESQUEMA DE CONEXIONADO ELÉCTRICO DEL MOTOR Le velocità disponibili sono numerate da 1 a 6 in ordine decrescente di velocità Available speeds are numbered from 1 to 6 following a speed decreasing order Lesvites...

Page 38: ...lectriques étant constamment mis à jour il faut absolument se référer à ceux fournis à bord de nos appareils Die Schaltpläne werden ständig aktualisiert deswegen muss man sich stets auf das mit dem Gerät gelieferte Schaltschema beziehen El cableado de las máquinas es sometido a actualizaciones constantes Por favor para cada unidad hagan referencia a los esquemas suministrados con la misma VMF_E1 V...

Page 39: ...aciones constantes Por favor para cada unidad hagan referencia a los esquemas suministrados con la misma SCHEMI ELETTRICI WIRING DIAGRAMS SCHEMAS ELECTRIQUES SCHALTPLÄNE ESQUEMAS ELÉCTRICOS 10k SA 4 3 2 1 Only master CN11 SA 1 E0 1 Slave 1 5 TTL SW 30 m MAX E0 1 Master VC E4 BL GR MA AR V1 V2 V3 V1 V2 V3 L N N PH VMF SIT3 F 2A INPUT OUTPUT MIN MED MAX 10k VH BL GR MA AR RO E0 CN9 JP1 CN11 PF2 C1 T...

Page 40: ...a los esquemas suministrados con la misma SCHEMI ELETTRICI WIRING DIAGRAMS SCHEMAS ELECTRIQUES SCHALTPLÄNE ESQUEMAS ELÉCTRICOS 10k SA 4 3 2 1 Only master SW VH VC E4 V1 V2 V3 V1 V2 V3 L N N PH VMF SIT3 F 2A INPUT OUTPUT MIN MED MAX 10k BL GR MA AR RO 230V 50Hz PE L N IG VMF SIT3 VMF E1 VMF E4 E1 CN9 JP1 CN11 PF2 C8 T1 C1 CN1 CN7 B CN7 A CN10 B CN10 A CN17 CN27 1 TX RX 2 GND SW SA N V3 V2 V1 L N Y2...

Page 41: ...485 4 V Pan 3 GND 485 5 GND Pan CN16 C2 SW SW1 SLOT EXPANSION L N IG PE VF VC MS PE VF VC MS VMF E1 master slave VMF E5 VMF E4 Los esquemas eléctricos están sujetos a modificaciones continuas por lo tanto es obligatorio tomar la referencia de los que se encuentran a bordo de la máquina A l l w i r i n g d i a g r a m s a r e c o n s t a n t l y u p d a t e d P l e a s e r e f e r t o t h e o n e s...

Page 42: ...ÄNE ESQUEMASELECTRICOS TTL Seriale locale TTL Local serial TTL Liaison série locale TTL Lokale serielle Schnittstelle TTL Serial Local Los esquemas eléctricos están sujetos a modificaciones continuas por lo tanto es obligatorio tomar la referencia de los que se encuentran a bordo de la máquina A l l w i r i n g d i a g r a m s a r e c o n s t a n t l y u p d a t e d P l e a s e r e f e r t o t h e...

Page 43: ...tido a actualizaciones constantes Por favor para cada unidad remitirse a los esquemas suministrados con la misma SCHEMIELETTRICI WIRINGDIAGRAMS SCHEMASELECTRIQUES ELEKTRISCHESCHALTPLÄNE ESQUEMASELECTRICOS Only Master 4 3 2 1 VMF E4 CN17 1 TX RX 2 GND 2 B 485 1 A 485 4 V Pan 3 GND 485 5 GND Pan CN16 RS485 12V TTL CN10 B CN10 A CN27 ON 1 2 3 4 5 6 7 8 DIP 1 CE 1 SP 1 CN8 CN17 1 TX RX 2 GND 2 B 485 1...

Page 44: ...ply 12Vdc 24Vac Los esquemas eléctricos están sujetos a modificaciones continuas por lo tanto es obligatorio tomar la referencia de los que se encuentran a bordo de la máquina A l l w i r i n g d i a g r a m s a r e c o n s t a n t l y u p d a t e d P l e a s e r e f e r t o t h e o n e s s u p p l i e d w i t h t h e u n i t Nos schémas électriques étant constamment mis à jour il faut absolument ...

Page 45: ...ster 22AWG Los esquemas eléctricos están sujetos a modificaciones continuas por lo tanto es obligatorio tomar la referencia de los que se encuentran a bordo de la máquina A l l w i r i n g d i a g r a m s a r e c o n s t a n t l y u p d a t e d P l e a s e r e f e r t o t h e o n e s s u p p l i e d w i t h t h e u n i t Nos schémas électriques étant constamment mis à jour il faut absolument se ré...

Page 46: ...F E5 MAX 30m Power Supply CN12 A B GND VMF E5 12Vdc Los esquemas eléctricos están sujetos a modificaciones continuas por lo tanto es obligatorio tomar la referencia de los que se encuentran a bordo de la máquina A l l w i r i n g d i a g r a m s a r e c o n s t a n t l y u p d a t e d P l e a s e r e f e r t o t h e o n e s s u p p l i e d w i t h t h e u n i t Nos schémas électriques étant consta...

Page 47: ...an sich stets auf das mit dem Gerät gelieferte Schaltschema beziehen El cableado de las máquinas es sometido a actualizaciones constantes Por favor para cada unidad hagan referencia a los esquemas suministrados con la misma SCHEMI ELETTRICI WIRING DIAGRAMS SCHEMAS ELECTRIQUES SCHALTPLÄNE ESQUEMAS ELÉCTRICOS BL V1 V2 V3 V1 V2 V3 L N N PH SIT3 F 2A INPUT OUTPUT MIN MED MAX SIT3 V1 V2 V3 Control Pane...

Page 48: ...den ständig aktualisiert deswegen muss man sich stets auf das mit dem Gerät gelieferte Schaltschema beziehen El cableado de las máquinas es sometido a actualizaciones constantes Por favor para cada unidad hagan referencia a los esquemas suministrados con la misma SCHEMI ELETTRICI WIRING DIAGRAMS SCHEMAS ELECTRIQUES SCHALTPLÄNE ESQUEMAS ELÉCTRICOS BL L N L N N L VED 1 2 5 6 7 8 9 10 3 4 BL NE MA RO...

Page 49: ...s électriques étant constamment mis à jour il faut absolument se référer à ceux fournis à bord de nos appareils Die Schaltpläne werden ständig aktualisiert deswegen muss man sich stets auf das mit dem Gerät gelieferte Schaltschema beziehen El cableado de las máquinas es sometido a actualizaciones constantes Por favor para cada unidad hagan referencia a los esquemas suministrados con la misma SCHEM...

Page 50: ...érer à ceux fournis à bord de nos appareils Die Schaltpläne werden ständig aktualisiert deswegen muss man sich stets auf das mit dem Gerät gelieferte Schaltschema beziehen El cableado de las máquinas es sometido a actualizaciones constantes Por favor para cada unidad hagan referencia a los esquemas suministrados con la misma SCHEMI ELETTRICI WIRING DIAGRAMS SCHEMAS ELECTRIQUES SCHALTPLÄNE ESQUEMAS...

Page 51: ...lisiert deswegen muss man sich stets auf das mit dem Gerät gelieferte Schaltschema beziehen El cableado de las máquinas es sometido a actualizaciones constantes Por favor para cada unidad hagan referencia a los esquemas suministrados con la misma SCHEMI ELETTRICI WIRING DIAGRAMS SCHEMAS ELECTRIQUES SCHALTPLÄNE ESQUEMAS ELÉCTRICOS L N L N N L VED 1 2 5 6 7 8 9 10 3 4 BL NE MA RO M M 1 MV BL NE MA R...

Page 52: ... auf das mit dem Gerät gelieferte Schaltschema beziehen El cableado de las máquinas es sometido a actualizaciones constantes Por favor para cada unidad hagan referencia a los esquemas suministrados con la misma SCHEMI ELETTRICI WIRING DIAGRAMS SCHEMAS ELECTRIQUES SCHALTPLÄNE ESQUEMAS ELÉCTRICOS BL L N L N N L VED 1 2 5 6 7 8 9 10 3 4 BL NE MA RO M M 1 MV BL NE MA RO MIN MED MAX 5 5 1 4 4 3 3 2 2 6...

Page 53: ...an sich stets auf das mit dem Gerät gelieferte Schaltschema beziehen El cableado de las máquinas es sometido a actualizaciones constantes Por favor para cada unidad hagan referencia a los esquemas suministrados con la misma SCHEMI ELETTRICI WIRING DIAGRAMS SCHEMAS ELECTRIQUES SCHALTPLÄNE ESQUEMAS ELÉCTRICOS L N L N N L VED 1 2 5 6 7 8 9 10 3 4 BL NE MA RO M M 1 MV BL NE MA RO MIN MED MAX 5 5 1 4 4...

Page 54: ...sich stets auf das mit dem Gerät gelieferte Schaltschema beziehen El cableado de las máquinas es sometido a actualizaciones constantes Por favor para cada unidad hagan referencia a los esquemas suministrados con la misma SCHEMI ELETTRICI WIRING DIAGRAMS SCHEMAS ELECTRIQUES SCHALTPLÄNE ESQUEMAS ELÉCTRICOS L N L N N L VED 1 2 5 6 7 8 9 10 3 4 BL NE MA RO M M 1 MV BL NE MA RO MIN MED MAX 5 5 1 4 4 3 ...

Page 55: ...eichen der maximalen Temperatur und Feuchtigkeitswerte siehe Abschnitt DURCHSCHNITTLICHE MINDEST WASSERTEMPERATUR Se han alcanzado las condiciones límites de temperatura y humedad descritas en MÍNIMA TEMPERATURA MEDIA DEL AGUA SOLUZIONE REMEDY SOLUTION ABHILFE SOLUCIÓN Scegliere la velocità corretta sul pannello comandi Select the speed on the control panel Choisir la vitesse sur la panneau de com...

Page 56: ...56 IVEDPY 1902 4460510_00 ...

Page 57: ...sschrittes behält sich Aermec S p A vor in der Produktion Änderungen und Verbesserungen ohne Ankündigung dur chzuführen ILos datos técnicos indicados en la presente documentación no son vinculantes Aermec S p A se reserva el derecho de realizar en cualquier momento las modificaciones que estime necesarias para mejorar el producto AERMEC partecipa al Programma EUROVENT FCU I prodotti interessati fi...

Page 58: ...430 VED 440 VED 530 VED 540 VED 441 VED 541 VED 630 VED 640 VED 730 VED 740 VED 641 VED 741 FAN COIL FOR HORIZONTAL AND VERTICAL DUCTED INSTALLATION T E C H N I C A L M A N U A L IVEDPY 2005 4879010_04 VED ...

Page 59: ...AERMEC is involved in the Eurovent programme FCU Products covered by the programme can be found on the site www eurovent certification com ...

Page 60: ...rying out repairs under guarantee AERMEC S p A declines all liability for any damage due to improper use of the machine or the partial or superficial reading of the information contained in this manual The information contained in this manual conform to the description of the units at the time of drafting This document has been prepared with reference to the pre series or prototypes the technical ...

Page 61: ...lare sull imballo per conoscere il numero di macchine impilabili Stacking control the packing to know the number of machines that can be stacked Empilement vérifier sur l emballage pour connaître le nombre d appareils pouvant être empilés Stapelung DieAnzahl der stapelbaren Geräte wird durch die Symbole auf denVerpackungen ermittelt Apilamiento observe en el embalaje para saber cuántos equipos pue...

Page 62: ...it in crowded areas or venues requiring high hygiene standards DURING OPERATIONS Always leave the filter on the fan coil during operation otherwise dust in the air could soil the coil surface area WHAT IS NORMAL In the cooling operation water vapour may be present in the air delivery of the fan coil In the heating operation a slight hiss might be heard close to the fan coil Sometimes the fan coil ...

Page 63: ...filtration class G3 Air intake filter easily removable for periodic cleaning Accessories for 3 way valve with 4 connections Accessories 2 way valve for the systems to variable water flow rate Internal insulating class 1 Full compliance with the accident pre vention standards Ease of installation and maintenance Discharge flange incorporated in the unit Main features of the VED fancoils Vertical in...

Page 64: ...re designed to connect the fancoil to all types of air ducting The delivery outlet includes the coupling flange CONDENSATE DRAIN Every device is equipped with a con densate collection tray for both ver tical and horizontal installation The fan coil drip tray has got 2 condensate discharges on the right and left hand side It is recommended to use the condensate discharge on the water connections PL...

Page 65: ...erage and minimum speed are obtained by multiplying the values obtained from the table at maximum speed by the indicated correction factors The water pressure drops respectively for the 3 4 row coils heating and cooling and 1 2 row heating only are illustrated in the diagrams The correction factors when the unit operates with glycol water for cool ing and heating function modes are shown in the gr...

Page 66: ...rature C 80 Maximum recommended water inlet temperature C 65 Maximum operating pressure bar 8 Minimum water flow rate Main coil l h 300 300 300 300 300 300 Maximum water flow rate Main coil l h 3000 3000 3000 3000 3000 3000 Minimum water flow rate Heating Only Coil l h 100 100 Maximum water flow rate Heating Only Coil l h 1500 1500 External temperature limits Ta C 0 Ta 40 Relative humidity limits ...

Page 67: ...2000 Minimum E cu m h 790 780 1120 1100 1380 1370 1640 1600 Useful static head with filter installed Rated Pa 55 50 40 35 68 63 47 37 Maximum E Pa 72 70 70 56 75 75 69 69 Average E Pa 50 50 50 50 50 50 50 50 Minimum E Pa 24 24 25 32 30 30 32 32 Motor speed connections Rated V5 V5 V5 V5 V5 V5 V5 V5 Maximum E V5 V5 V5 V5 V5 V5 V5 V5 Average E V3 V3 V4 V4 V3 V3 V3 V3 Minimum E V1 V1 V2 V2 V2 V1 V1 V1...

Page 68: ...alled Rated Pa 50 35 63 37 Maximum E Pa 70 56 75 69 Average E Pa 50 50 50 50 Minimum E Pa 24 32 30 32 Motor speed connections Rated V5 V5 V5 V5 Maximum E V5 V5 V5 V5 Average E V3 V4 V3 V3 Minimum E V1 V2 V1 V1 Number of fans no 2 2 3 3 Input power Rated W 240 282 376 411 Maximum E W 222 267 339 371 Average E W 178 230 268 285 Minimum E W 135 172 224 234 Input power Maximumhead W 290 300 436 440 Ma...

Page 69: ...8602 6520 8619 7252 8636 7622 21 10905 5075 10871 5803 10855 6532 10838 7261 10821 7616 23 13257 5774 13240 6511 13207 7236 13190 7597 7 3 15 4995 4478 5064 5064 5339 5339 5976 5976 6606 6606 6916 6916 17 6876 4477 6859 5207 6836 5928 6830 6650 6951 6951 7042 7042 19 8886 4445 8869 5182 8853 5913 8819 6627 8811 7349 8786 7699 21 11021 5135 10988 5863 8819 6627 10938 7311 10930 7672 23 13307 5804 1...

Page 70: ... 17 651 651 1301 1301 2368 2368 3177 3177 3905 3905 4255 4255 19 671 671 1306 1306 2397 2397 3183 3183 3911 3911 4267 4267 21 2477 1531 3177 2471 3762 3364 4301 4236 4553 4553 23 5804 2638 5804 3350 5918 4103 6010 4489 15 3 15 1283 1283 2010 2010 2689 2689 3346 3346 3986 3986 4307 4307 17 1286 1286 2013 2013 2695 2695 3355 3355 3997 3997 4312 4312 19 1875 1366 2268 2185 2741 2741 3360 3360 4003 40...

Page 71: ...94 5294 6099 6099 6877 6877 7263 7263 17 5228 3567 5534 4455 5933 5355 6392 6249 6931 6931 7276 7276 19 8035 3765 8035 4556 8008 5326 8088 6136 8274 6969 8381 7388 21 10770 4624 10751 5407 10732 6182 10712 6956 10712 7344 23 13537 5399 13518 6182 13479 6953 13479 7346 9 3 15 4217 4013 4676 4676 5424 5424 6166 6166 6897 6897 7263 7263 17 6199 3994 6172 4766 6232 5558 6425 6365 6917 6917 7276 7276 1...

Page 72: ...8 17 755 755 1508 1508 2747 2747 3685 3685 4529 4529 4935 4935 19 779 737 1515 1515 2780 2780 3691 3691 4536 4536 4948 4948 21 2873 1642 3685 2649 4363 3607 4988 4542 5281 4995 23 6731 2829 6731 3593 6864 4400 6970 4814 15 3 15 1488 1488 2331 2331 3119 3119 3881 3881 4622 4622 4995 4995 17 1492 1492 2334 2334 3126 3126 3891 3891 4636 4636 5002 5002 19 2175 1465 2630 2343 3179 3179 3897 3897 4642 4...

Page 73: ...5 5685 5685 6411 6411 6771 6771 17 4873 3610 5158 4508 5530 5420 5958 5958 6461 6461 6783 6783 19 7490 3810 7490 4611 7465 5390 7539 6209 7713 7053 7812 7476 21 10040 4680 10022 5472 10004 6257 9986 7039 9986 7433 23 12619 5463 12601 6256 12565 7037 12565 7435 9 3 15 3931 3931 4359 4359 5056 5056 5747 5747 6430 6430 6771 6771 17 5778 4042 5754 4823 5809 5625 5989 5989 6448 6448 6783 6783 19 7966 4...

Page 74: ...422 3422 4216 4216 4594 4594 17 704 704 1406 1406 2560 2560 3435 3435 4222 4222 4600 4600 19 726 726 1412 1412 2591 2591 3441 3441 4228 4228 4613 4613 21 2678 1662 3435 2681 4067 3650 4650 4597 4923 4923 23 6275 2863 6275 3636 6399 4453 6498 4872 15 3 15 1387 1387 2173 2173 2908 2908 3618 3618 4309 4309 4656 4656 17 1390 1390 2176 2176 2914 2914 3627 3627 4321 4321 4662 4662 19 2027 1482 2452 2371...

Page 75: ...0 5858 5858 6749 6749 7610 7610 8037 8037 17 5785 3877 6123 4842 6565 5821 7073 6792 7669 7669 8052 8052 19 8891 4092 8891 4952 8861 5789 8950 6669 9156 7575 9274 8030 21 11918 5026 11897 5877 11875 6720 11854 7560 11854 7983 23 14980 5868 14959 6719 14916 7558 14916 7985 9 3 15 4666 4362 5174 5174 6002 6002 6823 6823 7632 7632 8037 8037 17 6859 4342 6830 5180 6896 6041 7110 6918 7654 7654 8052 80...

Page 76: ...039 3039 4063 4063 5005 5005 5454 5454 17 835 835 1669 1669 3039 3039 4077 4077 5012 5012 5461 5461 19 862 801 1677 1677 3076 3076 4085 4085 5019 5019 5476 5476 21 3179 1785 4077 2880 4828 3920 5520 4937 5844 5429 23 7448 3075 7448 3905 7595 4783 7713 5232 15 3 15 1647 1647 2579 2579 3452 3452 4294 4294 5115 5115 5527 5527 17 1651 1651 2583 2583 3459 3459 4305 4305 5130 5130 5535 5535 19 2406 1592...

Page 77: ...74 13411 7 15 5573 5573 6707 6707 7921 7921 9126 9126 10290 10290 10867 10867 17 7822 6146 8280 7675 8877 8877 9564 9564 10370 10370 10887 10887 19 12022 6486 12022 7849 11982 9176 12101 10571 12380 12007 12539 12539 21 16115 7967 16086 9316 16057 10652 16028 11984 16028 12654 23 20255 9301 20226 10651 20168 11980 20168 12657 9 3 15 6309 6309 6996 6996 8115 8115 9225 9225 10320 10320 10867 10867 1...

Page 78: ...57 4110 4110 5493 5493 6767 6767 7374 7374 17 1130 1130 2257 2257 4110 4110 5513 5513 6777 6777 7384 7384 19 1165 1165 2267 2267 4159 4159 5523 5523 6787 6787 7404 7404 21 4299 2829 5513 4565 6528 6214 7464 7464 7902 7902 23 10071 4874 10071 6189 10270 7581 10429 8294 15 3 15 2227 2227 3488 3488 4667 4667 5807 5807 6916 6916 7474 7474 17 2232 2232 3493 3493 4677 4677 5821 5821 6936 6936 7484 7484 ...

Page 79: ... 7 15 6595 6322 7938 7938 9375 9375 10800 10800 12178 12178 12861 12861 17 9257 6194 9799 7735 10505 9299 11318 10850 12272 12272 12884 12884 19 14227 6537 14227 7911 14180 9248 14321 10654 14651 12101 14840 12828 21 19071 8029 19037 9389 19003 10735 18968 12078 18968 12753 23 23971 9374 23937 10734 23868 12074 23868 12756 9 3 15 7467 6969 8279 8279 9604 9604 10918 10918 12213 12213 12861 12861 17...

Page 80: ...15 1337 1337 2671 2671 4864 4864 6501 6501 8008 8008 8727 8727 17 1337 1337 2671 2671 4864 4864 6524 6524 8020 8020 8739 8739 19 1379 1280 2683 2683 4923 4917 6536 6536 8032 8032 8762 8762 21 5087 2851 6524 4600 7726 6263 8833 7887 9351 8672 23 11919 4912 11919 6238 12154 7640 12343 8358 15 3 15 2635 2635 4128 4128 5523 5523 6872 6872 8185 8185 8845 8845 17 2641 2641 4133 4133 5535 5535 6889 6889 ...

Page 81: ... 7 15 6158 6158 7412 7412 8753 8753 10084 10084 11371 11371 12009 12009 17 8643 6825 9149 8522 9809 9809 10568 10568 11459 11459 12031 12031 19 13284 7203 13284 8716 13240 10189 13372 11738 13680 13333 13856 13856 21 17807 8847 17775 10345 17743 11828 17711 13308 17711 14051 23 22382 10328 22350 11827 22286 13303 22286 14055 9 3 15 6972 6972 7731 7731 8968 8968 10194 10194 11404 11404 12009 12009 ...

Page 82: ...8 1248 2494 2494 4541 4541 6070 6070 7478 7478 8149 8149 17 1248 1248 2494 2494 4541 4541 6092 6092 7489 7489 8160 8160 19 1287 1287 2505 2505 4596 4596 6103 6103 7500 7500 8182 8182 21 4750 3141 6092 5069 7214 6900 8248 8248 8731 8731 23 11129 5412 11129 6873 11349 8418 11525 9209 15 3 15 2461 2461 3854 3854 5157 5157 6416 6416 7643 7643 8259 8259 17 2466 2466 3860 3860 5168 5168 6433 6433 7665 7...

Page 83: ...5 7257 6982 8734 8734 10315 10315 11883 11883 13399 13399 14151 14151 17 10185 6841 10781 8542 11559 10269 12453 11983 13503 13503 14177 14177 19 15654 7220 15654 8737 15602 10213 15758 11766 16121 13364 16328 14167 21 20984 8867 20946 10369 20909 11856 20871 13339 20871 14084 23 26375 10353 26337 11855 26262 13334 26262 14088 9 3 15 8216 7696 9110 9110 10568 10568 12013 12013 13438 13438 14151 14...

Page 84: ...3 16535 10287 7 15 1471 1471 2939 2939 5351 5351 7153 7153 8812 8812 9602 9602 17 1471 1471 2939 2939 5351 5351 7179 7179 8825 8825 9615 9615 19 1517 1414 2952 2952 5416 5416 7192 7192 8838 8838 9641 9641 21 5598 3149 7179 5081 8501 6917 9719 8710 10289 9578 23 13114 5425 13114 6889 13373 8438 13581 9231 15 3 15 2900 2900 4542 4542 6077 6077 7561 7561 9006 9006 9732 9732 17 2906 2906 4548 4548 609...

Page 85: ...1 0 90 0 91 0 92 Average speed 0 79 0 76 0 83 0 86 Minimum speed 0 59 0 57 0 69 0 72 Water flow rate l h Tw water inlet temperature air inlet temperature 20 C Heating capacity kW Water flow rate l h Tw water inlet temperature air inlet temperature 20 C Heating capacity kW 0 500 1000 1500 2000 2500 3000 3500 0 5 10 15 20 25 Tw 20 C Tw 30 C Tw 40 C Tw 50 C Tw 60 C VED 430 0 500 1000 1500 2000 2500 3...

Page 86: ... rated speed For the rest of the speeds the values must be multiplied by the following values VED 540 541 630 640 k Ph k Ph k Ph k Ph Rated speed 1 1 1 1 Maximum speed 0 90 0 93 0 88 0 91 Average speed 0 84 0 90 0 74 0 76 Minimum speed 0 7 0 79 0 61 0 61 0 500 1000 1500 2000 2500 3000 3500 0 5 10 15 20 25 30 Tw 20 C Tw 30 C Tw 40 C Tw 50 C Tw 60 C VED 540 0 500 1000 1500 2000 2500 3000 3500 0 2 4 ...

Page 87: ... rest of the speeds the values must be multiplied by the following values 0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000 0 10 20 30 40 50 Tw 20 C Tw 30 C Tw 40 C Tw 50 C Tw 60 C VED 730 0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000 0 10 20 30 40 50 Tw 20 C Tw 30 C Tw 40 C Tw 50 C Tw 60 C VED 740 0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000 0 5 10 15 20 25 Tw 20 C Tw 30 C Tw 40 C Tw ...

Page 88: ...2300 55 32 57 78 56 80 59 41 54 09 32 38 54 54 32 48 2400 59 72 62 38 61 32 64 14 58 39 34 96 58 88 35 06 2500 64 28 67 14 66 00 69 03 62 85 37 62 63 37 37 74 2600 68 98 72 05 70 83 74 08 67 44 40 37 68 01 40 50 2700 73 83 77 11 75 80 79 28 72 18 43 21 72 79 43 34 2800 78 82 82 33 80 93 84 65 77 07 46 14 77 71 46 28 2900 83 96 87 70 86 21 90 17 82 09 49 14 82 78 49 29 3000 89 25 93 22 91 63 95 84 ...

Page 89: ...63 23 02 2300 42 75 46 23 41 51 46 56 53 15 25 49 53 76 24 94 2400 46 15 49 91 44 81 50 27 57 39 27 52 58 04 26 92 2500 49 67 53 71 48 23 54 10 61 76 29 62 62 47 28 98 2600 53 30 57 64 51 76 58 06 66 28 31 78 67 04 31 10 2700 57 05 61 69 55 40 62 14 70 94 34 02 71 75 33 28 2800 60 91 65 87 59 14 66 35 75 74 36 32 76 60 35 53 2900 64 88 70 16 63 00 70 67 80 68 38 69 81 60 37 85 3000 68 96 74 57 66 ...

Page 90: ... 56 20 30 77 21 36 30 39 19 72 2400 59 72 66 54 58 96 60 67 33 22 23 06 32 81 21 29 2500 64 28 71 61 63 46 65 30 35 76 24 82 35 31 22 91 2600 68 98 76 85 68 10 70 07 38 37 26 63 37 89 24 59 2700 73 83 82 26 72 89 75 00 41 07 28 50 40 55 26 32 2800 78 82 87 82 77 82 80 07 43 85 30 43 43 30 28 10 2900 83 96 93 55 82 89 85 29 46 71 32 41 46 12 29 93 3000 89 25 99 43 88 11 90 66 49 65 34 45 49 02 31 8...

Page 91: ... rate and speed of the fan V1 V5 STATIC PRESSURE Useful head Pa VED 440 0 20 40 60 80 100 120 140 620 720 820 920 1020 1120 1220 1320 1420 1520 V2 V3 V1 V4 V5 0 0 0029 0 0058 0 0087 0 0116 0 0174 0 0203 0 0145 364 92 423 78 482 63 541 49 600 35 659 21 718 06 776 92 835 78 894 64 Air flow rate m3 h VED 430 0 20 40 60 80 100 120 140 620 720 820 920 1020 1120 1220 1320 1420 1520 V2 V3 V1 V4 V5 0 0 00...

Page 92: ...eeds The graph shows the useful static pressure of the machines with the uprated multispeed motor in function of the air flow rate and speed of the fan V1 V5 STATIC PRESSURE 0 20 40 60 80 100 120 140 620 720 820 920 1020 1120 1220 1320 1420 1520 V2 V3 V1 V4 V5 364 92 423 78 482 63 541 49 600 35 659 21 718 06 776 92 835 78 894 64 0 0 0029 0 0058 0 0087 0 0116 0 0174 0 0203 0 0145 Air flow rate m3 h...

Page 93: ...te and speed of the fan V1 V5 STATIC PRESSURE VED 540 0 20 40 60 80 100 120 140 800 900 1000 1100 1200 1300 1400 1500 1600 1700 470 86 529 72 588 58 647 44 706 29 765 15 824 01 882 87 941 72 1000 58 V2 V3 V1 V4 V5 0 0 0029 0 0058 0 0087 0 0116 0 0174 0 0203 0 0145 Air flow rate m3 h Useful head Pa VED 530 0 20 40 60 80 100 120 140 800 900 1000 1100 1200 1300 1400 1500 1600 1700 V2 V3 V1 V4 V5 470 ...

Page 94: ...eds The graph shows the useful static pressure of the machines with the uprated multispeed motor in function of the air flow rate and speed of the fan V1 V5 STATIC PRESSURE 0 20 40 60 80 100 120 140 800 900 1000 1100 1200 1300 1400 1500 1600 1700 V2 V3 V1 V4 V5 0 0 0029 0 0058 0 0087 0 0116 0 0174 0 0203 0 0145 470 86 529 72 588 58 647 44 706 29 765 15 824 01 882 87 941 72 1000 58 Air flow rate m3...

Page 95: ...00 V2 V3 V1 V4 V5 647 44 765 15 882 87 1000 58 1236 01 1353 73 1471 44 0 0 0029 0 0058 0 0087 0 0116 0 0174 0 0203 0 0145 1118 30 Air flow rate m3 h Useful head Pa The fan coils in the VED series have been designed to make it possible to adjust the static pressure supplied by the fan upon pres sure drops in the duct by choosing an appropriate set of three speeds The graph shows the useful static p...

Page 96: ...0145 Air flow rate m3 h Useful head Pa VED 641 The fan coils in the VED series have been designed to make it possible to adjust the static pressure supplied by the fan upon pres sure drops in the duct by choosing an appropriate set of three speeds The graph shows the useful static pressure of the machines with the uprated multispeed motor in function of the air flow rate and speed of the fan V1 V5...

Page 97: ...00 V2 V3 V1 V4 V5 1294 87 824 01 941 72 1059 44 1177 16 1412 59 1530 30 1648 02 0 0 0029 0 0058 0 0087 0 0116 0 0174 0 0203 0 0145 Useful head Pa Air flow rate m3 h The fan coils in the VED series have been designed to make it possible to adjust the static pressure supplied by the fan upon pres sure drops in the duct by choosing an appropriate set of three speeds The graph shows the useful static ...

Page 98: ...8 02 Air flow rate m3 h Useful head Pa VED 741 The fan coils in the VED series have been designed to make it possible to adjust the static pressure supplied by the fan upon pres sure drops in the duct by choosing an appropriate set of three speeds The graph shows the useful static pressure of the machines with the uprated multispeed motor in function of the air flow rate and speed of the fan V1 V5...

Page 99: ... 20 CORRECTION FACTORS WHEN OPERATING USING GLYCOL WATER COOLING FUNCTION MODE HEATING FUNCTION MODE Average glycoled water temperature Correction factor Average glycoled water temperature Correction factor Average glycoled water temperature Correction factor Average glycoled water temperature Correction factor Average glycoled water temperature Correction factor Key ...

Page 100: ... 0 32 0 2500 48 8 47 3 43 3 44 2 42 7 38 7 35 1 33 6 29 6 3150 45 7 44 2 40 2 40 8 39 3 35 3 30 8 29 3 25 3 4000 42 6 41 1 37 1 37 5 36 0 32 0 27 0 25 5 21 5 5000 38 9 37 4 33 4 33 1 31 6 27 6 24 0 22 5 18 5 6300 34 7 33 2 29 2 30 4 28 9 24 9 14 0 12 5 8 5 8000 31 0 29 5 25 5 26 1 24 6 20 6 13 0 11 5 7 5 1000 26 9 25 4 21 4 21 3 19 8 15 8 12 3 10 8 6 8 dB A tot 63 0 61 5 E 57 5 E 59 0 57 5 E 53 5 ...

Page 101: ... 6 35 6 2500 49 4 47 9 43 9 46 3 44 8 40 8 38 8 37 3 33 3 3150 46 3 44 8 40 8 43 0 41 5 37 5 35 0 33 5 29 5 4000 43 4 41 9 37 9 39 8 38 3 34 3 31 2 29 7 25 7 5000 39 7 38 2 34 2 35 8 34 3 30 3 26 6 25 1 21 1 6300 36 3 34 8 30 8 32 1 30 6 26 6 24 5 23 0 19 0 8000 32 5 31 0 27 0 28 1 26 6 22 6 19 8 18 3 14 3 10000 27 8 26 3 22 3 23 6 22 1 18 1 15 1 13 6 9 6 dB A tot 63 5 62 0 E 58 0 E 61 0 59 5 E 55...

Page 102: ...7 41 7 2500 54 4 52 9 48 9 50 0 48 5 44 5 43 9 42 4 38 4 3150 50 8 49 3 45 3 46 5 45 0 41 0 39 7 38 2 34 2 4000 47 7 46 2 42 2 42 7 41 2 37 2 34 3 32 8 28 8 5000 43 2 41 7 37 7 37 0 35 5 31 5 28 3 26 8 22 8 6300 38 6 37 1 33 1 32 3 30 8 26 8 23 8 22 3 18 3 8000 35 2 33 7 29 7 28 7 27 2 23 2 20 18 5 14 5 10000 30 2 28 7 24 7 23 7 22 2 18 2 15 2 13 7 9 7 dB A tot 69 5 68 0 E 64 0 E 66 0 64 5 E 60 5 ...

Page 103: ... 56 8 52 8 55 4 53 9 49 9 50 4 48 9 44 9 2500 54 9 53 4 49 4 51 8 50 3 46 3 46 9 45 4 41 4 3150 51 3 49 8 45 8 48 3 46 8 42 8 43 2 41 7 37 7 4000 48 0 46 5 42 5 44 8 43 3 39 3 38 4 36 9 32 9 5000 43 5 42 0 38 0 39 5 38 0 34 0 32 5 31 0 27 0 6300 39 0 37 5 33 5 34 8 33 3 29 3 27 8 26 3 22 3 8000 35 7 34 2 30 2 31 2 29 7 25 7 24 0 22 5 18 5 10000 30 8 29 3 25 3 26 2 24 7 20 7 19 1 17 6 13 6 dB A tot...

Page 104: ...probe to be used for 4 pipe systems Water valves VJP Control and balancing combination valve for 2 and 4 pipe systems to install outside the unit supplied without fittings and hydraulic com ponents The valve which can guarantee a constant water flow rate in the terminal within its operating range VCT These are 3 way ball valves made of bronze with female female connections Ø 1 2 That can be servo ...

Page 105: ...he fan coil Water valves 3 way valve kit VED430 VED440 VED530 VED540 VED630 VED640 VED730 VED740 3wayvalvekit Maincoil VCF45C VCF45C VCF45C VCF45C VCF47C VCF47C VCF47C VCF47C VED432 VED441 VED532 VED541 VED632 VED641 VED732 VED741 3wayvalvekit Maincoil VCF45C VCF45C VCF45C VCF45C VCF47C VCF47C VCF47C VCF47C Secondarycoilx4 pipe VCF45H VCF45H VCF45H VCF45H VCF47H VCF47H VCF47H VCF47H 230V power sup...

Page 106: ...lenum with rectangular flanges Ver 430 432 440 441 530 532 540 541 630 632 640 641 730 732 740 741 RPA450V RPA450V RPA450V RPA450V RPA450V RPA450V RPA450V RPA450V RPA670V RPA670V RPA670V RPA670V RPA670V RPA670V RPA670V RPA670V Intake plenum with circular flanges Ver 430 432 440 441 530 532 540 541 630 632 640 641 730 732 740 741 PA450V PA450V PA450V PA450V PA450V PA450V PA450V PA450V PA670V PA670V...

Page 107: ...el for VMF E1 stand alone or for a WMF network in which the first is a VMF E1 Single unit To be combined with a VMF E1 thermostat Fan coil network To be combined with VMF E1 Master thermostats VED combined with control panels with thermostat PXAE 1 1A Command panels with thermostat Combinations allowed for installation on a single unit mandatory combination with SIT3 Combinations permitted for net...

Page 108: ...D fancoils are equipped with 5 speed motors 3 operating speeds of which can be selected by changing the connections in the electrical box of the motor The fancoils are provided with connections to the standard speed See the wiring diagram before changing the motor connections If a three way valve is installed the mini mum water temperature sensor can be installed in two locations in its housing in...

Page 109: ...mbination with components supplied as acces sories check availability WARNING Make sure the control panel supports the load of the electric motor otherwise placed an SIT3 inter face accessory between the fan and the control panel WARNING The units that are equipped with VMF series thermostats must be combined with an VMF SIT interface accessory When combining to control panels the relative wiring ...

Page 110: ... electrical wirings to the left side through the cable grommet Move the support plate the control board the earthing u bolt and any electric devices from the right side to the left side Reassemble the front closure panel COIL ROTATION A B 180 COIL ROTATION DIAGRAM The fan coil drip tray has got 2 condensate discharges on the right and left hand side It is recommended to use the condensate discharg...

Page 111: ...1 2 G 1 2 G 1 2 G 1 2 G Condensate discharge connections external diameter mm 20 5 20 5 20 5 20 5 20 5 20 5 20 5 20 5 Ø20 5 1509 1504 789 150 440 174 25 1558 1533 1453 40 40 329 423 280 316 351 307 109 379 15 326 247 287 46 10 20 VED 630 640 730 740 632 641 732 741 Main coil water connections female Ø 3 4 G 3 4 G 3 4 G 3 4 G 3 4 G 3 4 G 3 4 G 3 4 G heating only coil water connections female Ø 1 2 ...

Page 112: ...c BL bleu GR gris GV jaune vert MA marron NE noir RO rouge AR Orange BI Weiß BL Blau GR Grau GV Gelb Grün MA Braun NE Schwarz RO Rot AR Naranja BI Blanco BL Azul GR Gris GV Amarillo Verde MA Marrón NE Negro RO Rojo F Fusibile Fuse Fusible Sicherung Fusible IG Interruttore generale Master switch Interrupteur général Hauptschalter Interruptor general M Morsettiera Control board Bornier Klemmleiste C...

Page 113: ... máquinas es sometido a actualizaciones constantes Por favor para cada unidad hagan referencia a los esquemas suministrados con la misma SCHEMI ELETTRICI WIRING DIAGRAMS SCHEMAS ELECTRIQUES SCHALTPLÄNE ESQUEMAS ELÉCTRICOS 10k SA 4 3 2 1 Only master CN11 SA 1 E0 1 Slave 1 5 TTL SW 30 m MAX E0 1 Master VC E4 BL GR MA AR V1 V2 V3 V1 V2 V3 L N N PH VMF SIT3 F 2A INPUT OUTPUT MIN MED MAX 10k VH BL GR M...

Page 114: ...ra cada unidad hagan referencia a los esquemas suministrados con la misma SCHEMI ELETTRICI WIRING DIAGRAMS SCHEMAS ELECTRIQUES SCHALTPLÄNE ESQUEMAS ELÉCTRICOS 10k SA 4 3 2 1 Only master SW VH VC E4 V1 V2 V3 V1 V2 V3 L N N PH VMF SIT3 F 2A INPUT OUTPUT MIN MED MAX 10k BL GR MA AR RO 230V 50Hz PE L N IG VMF SIT3 VMF E1 VMF E4 E1 CN9 JP1 CN11 PF2 C8 T1 C1 CN1 CN7 B CN7 A CN10 B CN10 A CN17 CN27 1 TX ...

Page 115: ...16 C2 SW SW1 SLOT EXPANSION L N IG PE VC VH MS PE VC VH MS WMF E0 WMF E1 Only Master 4 3 2 1 VMF E4 VMF E1 master slave VMF E5 VMF E4 Los esquemas eléctricos están sujetos a modificaciones continuas por lo tanto es obligatorio tomar la referencia de los que se encuentran a bordo de la máquina A l l w i r i n g d i a g r a m s a r e c o n s t a n t l y u p d a t e d P l e a s e r e f e r t o t h e ...

Page 116: ... ESQUEMASELECTRICOS TTL Seriale locale TTL Local serial TTL Liaison série locale TTL Lokale serielle Schnittstelle TTL Serial Local Los esquemas eléctricos están sujetos a modificaciones continuas por lo tanto es obligatorio tomar la referencia de los que se encuentran a bordo de la máquina A l l w i r i n g d i a g r a m s a r e c o n s t a n t l y u p d a t e d P l e a s e r e f e r t o t h e o ...

Page 117: ...tido a actualizaciones constantes Por favor para cada unidad remitirse a los esquemas suministrados con la misma SCHEMIELETTRICI WIRINGDIAGRAMS SCHEMASELECTRIQUES ELEKTRISCHESCHALTPLÄNE ESQUEMASELECTRICOS Only Master 4 3 2 1 VMF E4 CN17 1 TX RX 2 GND 2 B 485 1 A 485 4 V Pan 3 GND 485 5 GND Pan CN16 RS485 12V TTL CN10 B CN10 A CN27 ON 1 2 3 4 5 6 7 8 DIP 1 CE 1 SP 1 CN8 CN17 1 TX RX 2 GND 2 B 485 1...

Page 118: ...2 A B GND VMF E5 12Vdc 24Vac Los esquemas eléctricos están sujetos a modificaciones continuas por lo tanto es obligatorio tomar la referencia de los que se encuentran a bordo de la máquina A l l w i r i n g d i a g r a m s a r e c o n s t a n t l y u p d a t e d P l e a s e r e f e r t o t h e o n e s s u p p l i e d w i t h t h e u n i t Nos schémas électriques étant constamment mis à jour il fau...

Page 119: ... CN12 A B GND VMF E5 12Vdc Los esquemas eléctricos están sujetos a modificaciones continuas por lo tanto es obligatorio tomar la referencia de los que se encuentran a bordo de la máquina A l l w i r i n g d i a g r a m s a r e c o n s t a n t l y u p d a t e d P l e a s e r e f e r t o t h e o n e s s u p p l i e d w i t h t h e u n i t Nos schémas électriques étant constamment mis à jour il faut ...

Page 120: ...F E5 MAX 30m Power Supply CN12 A B GND VMF E5 12Vdc Los esquemas eléctricos están sujetos a modificaciones continuas por lo tanto es obligatorio tomar la referencia de los que se encuentran a bordo de la máquina A l l w i r i n g d i a g r a m s a r e c o n s t a n t l y u p d a t e d P l e a s e r e f e r t o t h e o n e s s u p p l i e d w i t h t h e u n i t Nos schémas électriques étant consta...

Page 121: ...dig aktualisiert deswegen muss man sich stets auf das mit dem Gerät gelieferte Schaltschema beziehen El cableado de las máquinas es sometido a actualizaciones constantes Por favor para cada unidad hagan referencia a los esquemas suministrados con la misma SCHEMI ELETTRICI WIRING DIAGRAMS SCHEMAS ELECTRIQUES SCHALTPLÄNE ESQUEMAS ELÉCTRICOS BL V1 V2 V3 V1 V2 V3 L N N PH SIT3 F 2A INPUT OUTPUT MIN ME...

Page 122: ...den ständig aktualisiert deswegen muss man sich stets auf das mit dem Gerät gelieferte Schaltschema beziehen El cableado de las máquinas es sometido a actualizaciones constantes Por favor para cada unidad hagan referencia a los esquemas suministrados con la misma SCHEMI ELETTRICI WIRING DIAGRAMS SCHEMAS ELECTRIQUES SCHALTPLÄNE ESQUEMAS ELÉCTRICOS BL L N L N N L VED 1 2 5 6 7 8 9 10 3 4 BL NE MA RO...

Page 123: ...s électriques étant constamment mis à jour il faut absolument se référer à ceux fournis à bord de nos appareils Die Schaltpläne werden ständig aktualisiert deswegen muss man sich stets auf das mit dem Gerät gelieferte Schaltschema beziehen El cableado de las máquinas es sometido a actualizaciones constantes Por favor para cada unidad hagan referencia a los esquemas suministrados con la misma SCHEM...

Page 124: ...lisiert deswegen muss man sich stets auf das mit dem Gerät gelieferte Schaltschema beziehen El cableado de las máquinas es sometido a actualizaciones constantes Por favor para cada unidad hagan referencia a los esquemas suministrados con la misma SCHEMI ELETTRICI WIRING DIAGRAMS SCHEMAS ELECTRIQUES SCHALTPLÄNE ESQUEMAS ELÉCTRICOS L N L N N L VED 1 2 5 6 7 8 9 10 3 4 BL NE MA RO M M 1 MV BL NE MA R...

Page 125: ... auf das mit dem Gerät gelieferte Schaltschema beziehen El cableado de las máquinas es sometido a actualizaciones constantes Por favor para cada unidad hagan referencia a los esquemas suministrados con la misma SCHEMI ELETTRICI WIRING DIAGRAMS SCHEMAS ELECTRIQUES SCHALTPLÄNE ESQUEMAS ELÉCTRICOS BL L N L N N L VED 1 2 5 6 7 8 9 10 3 4 BL NE MA RO M M 1 MV BL NE MA RO MIN MED MAX 5 5 1 4 4 3 3 2 2 6...

Page 126: ...an sich stets auf das mit dem Gerät gelieferte Schaltschema beziehen El cableado de las máquinas es sometido a actualizaciones constantes Por favor para cada unidad hagan referencia a los esquemas suministrados con la misma SCHEMI ELETTRICI WIRING DIAGRAMS SCHEMAS ELECTRIQUES SCHALTPLÄNE ESQUEMAS ELÉCTRICOS L N L N N L VED 1 2 5 6 7 8 9 10 3 4 BL NE MA RO M M 1 MV BL NE MA RO MIN MED MAX 5 5 1 4 4...

Page 127: ...sich stets auf das mit dem Gerät gelieferte Schaltschema beziehen El cableado de las máquinas es sometido a actualizaciones constantes Por favor para cada unidad hagan referencia a los esquemas suministrados con la misma SCHEMI ELETTRICI WIRING DIAGRAMS SCHEMAS ELECTRIQUES SCHALTPLÄNE ESQUEMAS ELÉCTRICOS L N L N N L VED 1 2 5 6 7 8 9 10 3 4 BL NE MA RO M M 1 MV BL NE MA RO MIN MED MAX 5 5 1 4 4 3 ...

Page 128: ...ximalen Temperatur und Feuchtigkeitswerte siehe Abschnitt DURCHSCHNITTLICHE MINDEST WASSERTEMPERATUR Se han alcanzado las condiciones límites de temperatura y humedad descritas en MÍNIMA TEMPERATURA MEDIA DEL AGUA SOLUZIONE REMEDY SOLUTION ABHILFE SOLUCIÓN Scegliere la velocità corretta sul pannello comandi Select the speed on the control panel Choisir la vitesse sur la panneau de commandes Die Ge...

Page 129: ... Fortsschrittes behält sich Aermec S p A vor in der Produktion Änderungen und Verbesserungen ohne Ankündigung dur chzuführen ILos datos técnicos indicados en la presente documentación no son vinculantes Aermec S p A se reserva el derecho de realizar en cualquier momento las modificaciones que estime necesarias para mejorar el producto AERMEC partecipa al Programma EUROVENT FCU I prodotti interessa...

Page 130: ...4 8 8 0 9 8 1 _ 0 3 2 1 0 6 VED_I INVERTER FAN COILS for horizontal and vertical ducted installation Technical Manual VED 030 I_VED 741 I 110 240 V 50 60Hz ...

Page 131: ...any years of experi ence and in depth engineering research and it is manufactured using top quality materials and cutting edge technologies In addition the CE mark guarantees that our appliances fully comply with the requirements of the European Directives in terms of safety Il livello qualitativo è sotto costante sorveglianza ed i prodotti AERMEC sono pertanto sinonimo di Sicurezza Qualità e Affi...

Page 132: ...f Components 11 Operating Range 12 Technical Data 13 Technical Data 14 Cooling Capacity 15 Heating Power Yielded 2 Pipe System 32 Power Yielded With Heating Only Coil 4 Pipes And 4 Connections 35 Pressure Drops Cooling Only 37 2 Pipe System Pressure Drops Heating Only 37 4 Pipe System Pressure Drops Heating Only 37 Correction Factors In Functioning With Glycol Water 40 Preliminary Operations 41 In...

Page 133: ...ieren wenn sein Gewicht die 25kg übersteigt NO transportar la máquina solos si su peso es superior a los 25Kg NON lasciare gli imballi sciolti durante il trasporto Non rovesciare DO NOT leave boxes unsecured during transportation Do not overturn NE PAS laisser les emballages sans attaches durant le transport Ne pas renverser NICHT die Verpackungen wäh rend des Transports geöffnet lassen Nicht stür...

Page 134: ...to Standards in force on this subject in different countries WARNINGS REGARDING SAFETY AND IN STALLATION STANDARDS Follow the indications below to install the equipment correctly The completion of all operations according to specific requi rements is left to the experience of the installer The unit must be installed to enable main tenance and or repairs Do not modify or tamper with the units as da...

Page 135: ...ort and storage the unit and the accessories must always be protected against bad weather VERIFICATIONS UPON RECEPTION Visually check the unit upon recep tion to make sure that the order corresponds with what is indicated in the transport documents packaging is intact the unit is intact all the components have been pro vided Indicate any damage or missing com ponents on the transport document HAND...

Page 136: ...l dirty the coil surface IT IS NORMAL When in cooling mode water vapour can come out of the fan coil air flow When in heating mode a slight hissing sound can be heard near the fan coil The fan coil may sometimes emit unpleasant odours due to the accumulation of substances present in the envi ronment clean the filter more often especially if the room is not aired out regularly During operation nois...

Page 137: ... especially if the room is not aired out regularly During operation noise and or a creaking sound may be heard from inside the device due to the heat expansion of the elements plastic and metal however this does not indicate a fault and does not cause damage to the unit unless the maximum input water temperature is exceeded OPERATION ANOMALIES In case of anomalous operation remove the voltage from...

Page 138: ... of horizontal installation 2 pipe systems VED 030 I Standard coil VED 040 I Larger coil VED 130 I Standard coil VED 140 I Larger coil VED 230 I Standard coil VED 240 I Larger coil VED 330 I Standard coil VED 340 I Larger coil VED 530 I Standard coil VED 540 I Larger coil VED 730 I Standard coil VED 740 I Larger coil 4 pipe systems VED 030 I With heating coil VCF available as accessory VED 130 I W...

Page 139: ...completely developed within the industrial group It is a permanent magnet motor with low peak current and easily adjustable speed It is not affected by electromagnet interfer ence The fact that it is brushless means less fric tion and reduced wear Through the dedicated inverter device it is possible to continuously control the rotor speed and torque by simply acting on the stator currents The elec...

Page 140: ...erature of ambient air Ta C 21 23 25 27 29 31 Wet bulb temperature of ambient air Ta C 15 3 3 3 3 3 3 17 3 3 3 3 3 3 19 3 3 3 3 3 3 21 6 5 4 3 3 3 23 8 7 6 5 5 MINIMUM AVERAGE WATER TEMPERATURE Tw C If the fan coil runs continuously in cooling mode in an environment with high relative humidity condensate may form on the air flow This condensate could drip onto the floor and onto any underlying obj...

Page 141: ...rops 4 kPa H 9 14 31 23 44 37 18 26 4 kPa M 7 12 27 20 36 31 14 21 4 kPa L 3 5 15 11 25 16 10 16 Air flow rate m3 h H 285 277 433 420 590 570 805 775 m3 h M 256 249 397 386 524 509 704 685 m3 h L 161 160 287 280 417 406 572 563 Centrifugal type fans n 1 1 2 2 2 2 3 3 Useful static pressure Pa H 61 61 60 60 64 63 66 64 Pa M 50 50 50 50 50 50 50 50 Pa L 21 21 26 26 32 32 33 34 Input power W H 36 36 ...

Page 142: ...6 37 37 4 kPa L 12 19 19 35 27 27 Air flow rate m3 h H 1520 1500 1460 2410 2350 2350 m3 h M 1400 1380 1360 2040 2000 2000 m3 h L 1120 1100 1060 1640 1600 1600 Centrifugal type fans n 2 2 2 3 3 3 Useful static pressure Pa H 58 56 56 69 69 69 Pa M 50 50 50 50 50 50 Pa L 32 32 32 32 32 32 Input power W H 205 205 185 370 370 363 W M 170 170 163 245 245 240 W L 115 115 106 140 140 138 Sound power inlet...

Page 143: ...imum speed NB The yield values marked in bold indicate the nominal value To calculate the cooling capacity yielded the values shown in the table must be multiplied by the corrective factors referred to the different speeds Sensitive yield values greater than the total yield indicate that cooling occurs without dehumidification In this case take into account the sensitive yield values only Thecooli...

Page 144: ...1 31 1480 1480 1324 1535 1208 1208 1092 1092 975 975 19 21 1914 986 1648 845 1356 696 1022 543 594 362 23 1904 1123 1640 982 1349 837 1018 685 592 501 25 1895 1255 1633 1114 1344 970 1015 818 592 592 27 1885 1383 1624 1242 1337 1097 1010 941 744 744 29 1875 1512 1615 1373 1330 1230 1004 1004 861 861 31 1867 1639 1610 1500 1327 1327 1092 1092 975 975 21 21 2299 981 2038 842 1754 700 1439 555 1073 3...

Page 145: ... 31 1732 1732 1549 1668 1414 1414 1278 1278 1140 1140 19 21 2239 1072 1928 919 1587 756 1196 590 695 393 23 2227 1221 1918 1067 1578 910 1191 744 692 545 25 2217 1364 1911 1211 1573 1055 1188 889 692 692 27 2205 1504 1900 1350 1564 1193 1181 1023 870 870 29 2193 1643 1890 1493 1556 1337 1175 1174 1007 1007 31 2184 1781 1884 1631 1552 1477 1278 1278 1140 1140 21 21 2690 1066 2384 915 2052 761 1684 ...

Page 146: ...2 2444 2582 2230 2230 2015 2015 1799 1799 19 21 3532 1660 3041 1422 2503 1171 1886 913 1096 609 23 3513 1890 3026 1652 2490 1408 1879 1153 1092 844 25 3497 2111 3014 1875 2481 1633 1873 1377 1092 1075 27 3479 2328 2997 2090 2467 1846 1863 1584 1373 1373 29 3460 2544 2981 2311 2454 2070 1853 1817 1588 1588 31 3446 2758 2971 2525 2448 2287 2015 2015 1799 1799 21 21 4243 1651 3761 1416 3236 1178 2656...

Page 147: ...9 2683 2928 2448 2448 2212 2212 1975 1975 19 21 3877 1882 3339 1613 2747 1328 2071 1036 1204 690 23 3856 2143 3321 1874 2733 1597 2063 1307 1199 957 25 3839 2394 3309 2126 2724 1851 2056 1561 1199 1199 27 3819 2640 3290 2370 2708 2094 2045 1796 1507 1507 29 3798 2885 3273 2621 2694 2348 2034 2034 1743 1743 31 3782 3127 3262 2863 2687 2593 2212 2212 1975 1975 21 21 4657 1872 4129 1606 3553 1336 291...

Page 148: ...7 2789 3336 2545 2545 2300 2300 2053 2053 19 21 4030 2144 3471 1837 2856 1512 2152 1180 1251 787 23 4009 2442 3453 2135 2841 1820 2144 1489 1246 1090 25 3991 2727 3440 2422 2831 2109 2138 1778 1246 1246 27 3970 3007 3420 2700 2815 2385 2126 2047 1567 1567 29 3948 3287 3402 2986 2800 2675 2115 2115 1812 1812 31 3932 3563 3391 3262 2794 2794 2300 2300 2053 2053 21 21 4841 2133 4292 1829 3693 1522 30...

Page 149: ...278 3725 2991 2991 2703 2703 2413 2413 19 21 4737 2395 4080 2052 3357 1689 2530 1317 1471 878 23 4712 2727 4058 2384 3339 2032 2520 1663 1465 1217 25 4691 3046 4043 2705 3328 2355 2513 1986 1465 1465 27 4666 3358 4020 3015 3309 2663 2499 2285 1842 1842 29 4641 3670 3999 3334 3291 2987 2486 2486 2130 2130 31 4622 3978 3985 3642 3284 3284 2703 2703 2413 2413 21 21 5691 2381 5045 2043 4341 1700 3562 ...

Page 150: ...077 4618 3721 3721 3362 3362 3001 3001 19 21 5892 2969 5074 2543 4175 2094 3147 1633 1829 1089 23 5861 3380 5048 2955 4154 2519 3135 2061 1822 1509 25 5835 3776 5029 3353 4139 2920 3125 2462 1822 1822 27 5803 4163 5000 3738 4115 3302 3109 2833 2291 2291 29 5772 4551 4974 4133 4094 3703 3092 3092 2649 2649 31 5748 4933 4957 4515 4084 4084 3362 3362 3001 3001 21 21 7078 2952 6275 2533 5399 2107 4431...

Page 151: ...371 4930 3989 3989 3604 3604 3217 3217 19 21 6316 3169 5439 2715 4476 2235 3373 1743 1961 1162 23 6283 3608 5411 3154 4453 2689 3361 2200 1953 1610 25 6255 4030 5391 3579 4437 3117 3350 2628 1953 1953 27 6221 4444 5360 3990 4412 3525 3332 3024 2456 2456 29 6188 4857 5332 4412 4388 3952 3314 3314 2840 2840 31 6162 5265 5314 4820 4378 4366 3604 3604 3217 3217 21 21 7588 3152 6726 2703 5788 2249 4750...

Page 152: ...438 5775 5775 5218 5218 4657 4657 19 21 9144 4781 7875 4096 6480 3372 4884 2630 2839 1754 23 9096 5444 7834 4759 6446 4057 4865 3320 2828 2430 25 9055 6081 7805 5401 6424 4703 4850 3965 2828 2828 27 9007 6705 7760 6020 6387 5318 4824 4563 3555 3555 29 8959 7329 7719 6657 6353 5963 4799 4799 4112 4112 31 8922 7944 7693 7272 6339 6339 5218 5218 4657 4657 21 21 10985 4755 9738 4079 8380 3394 6877 269...

Page 153: ...438 5775 5775 5218 5218 4657 4657 19 21 9144 4781 7875 4096 6480 3372 4884 2630 2839 1754 23 9096 5444 7834 4759 6446 4057 4865 3320 2828 2430 25 9055 6081 7805 5401 6424 4703 4850 3965 2828 2828 27 9007 6705 7760 6020 6387 5318 4824 4563 3555 3555 29 8959 7329 7719 6657 6353 5963 4799 4799 4112 4112 31 8922 7944 7693 7272 6339 6339 5218 5218 4657 4657 21 21 10985 4755 9738 4079 8380 3394 6877 269...

Page 154: ...675 6675 6031 6031 5384 5384 19 21 10570 5123 9103 4389 7490 3613 5645 2818 3282 1879 23 10514 5833 9056 5099 7451 4347 5624 3557 3269 2603 25 10467 6515 9021 5786 7426 5038 5607 4249 3269 3269 27 10411 7184 8970 6450 7383 5698 5577 4889 4110 4110 29 10356 7852 8923 7132 7344 6389 5547 5547 4753 4753 31 10313 8511 8893 7791 7327 7058 6031 6031 5384 5384 21 21 12698 5095 11256 4370 9686 3636 7949 2...

Page 155: ...675 6675 6031 6031 5384 5384 19 21 10570 5123 9103 4389 7490 3613 5645 2818 3282 1879 23 10514 5833 9056 5099 7451 4347 5624 3557 3269 2603 25 10467 6515 9021 5786 7426 5038 5607 4249 3269 3269 27 10411 7184 8970 6450 7383 5698 5577 4889 4110 4110 29 10356 7852 8923 7132 7344 6389 5547 5547 4753 4753 31 10313 8511 8893 7791 7327 7058 6031 6031 5384 5384 21 21 12698 5095 11256 4370 9686 3636 7949 2...

Page 156: ... 9313 9313 8313 8313 19 21 16321 9086 14055 7784 11565 6408 8717 4999 5067 3333 23 16235 10346 13982 9044 11505 7710 8684 6309 5047 4617 25 16162 11556 13929 10263 11465 8936 8657 7535 5047 5047 27 16076 12742 13850 11440 11399 10105 8611 8611 6345 6345 29 15989 13927 13777 12650 11340 11332 8564 8564 7339 7339 31 15923 15096 13731 13819 11313 11313 9313 9313 8313 8313 21 21 19606 9036 17380 7751 ...

Page 157: ... 9313 9313 8313 8313 19 21 16321 9086 14055 7784 11565 6408 8717 4999 5067 3333 23 16235 10346 13982 9044 11505 7710 8684 6309 5047 4617 25 16162 11556 13929 10263 11465 8936 8657 7535 5047 5047 27 16076 12742 13850 11440 11399 10105 8611 8611 6345 6345 29 15989 13927 13777 12650 11340 11332 8564 8564 7339 7339 31 15923 15096 13731 13819 11313 11313 9313 9313 8313 8313 21 21 19606 9036 17380 7751 ...

Page 158: ...66 10812 10812 9651 9651 19 21 18948 8990 16318 7703 13427 6341 10120 4946 5883 3298 23 18848 10237 16234 8949 13358 7629 10082 6242 5860 4569 25 18764 11435 16172 10155 13312 8843 10051 7456 5860 5824 27 18664 12608 16080 11320 13235 9999 9997 8580 7367 7367 29 18564 13781 15995 12518 13165 11213 9943 9843 8521 8521 31 18487 14937 15942 13674 13135 12386 10812 10812 9651 9651 21 21 22763 8941 201...

Page 159: ...66 10812 10812 9651 9651 19 21 18948 8990 16318 7703 13427 6341 10120 4946 5883 3298 23 18848 10237 16234 8949 13358 7629 10082 6242 5860 4569 25 18764 11435 16172 10155 13312 8843 10051 7456 5860 5824 27 18664 12608 16080 11320 13235 9999 9997 8580 7367 7367 29 18564 13781 15995 12518 13165 11213 9943 9843 8521 8521 31 18487 14937 15942 13674 13135 12386 10812 10812 9651 9651 21 21 22763 8941 201...

Page 160: ...446 3262 3080 2899 2720 15 3309 3125 2940 2756 2574 50 5 2722 2541 2362 2186 2013 10 2597 2415 2233 2054 1876 15 2432 2245 2057 1870 1683 40 5 1881 1705 1532 1356 1185 10 1727 1543 1361 1177 987 15 1498 1294 1048 682 391 VED030I Ta D B C 16 18 20 22 24 Tw C Ph Ph Ph Ph Ph in dt W W W W W 70 5 3351 3177 3004 2835 2667 10 4041 4683 3688 3514 3341 15 3930 3751 3575 3398 3227 60 5 3472 3296 3117 2943 ...

Page 161: ...91 3314 10 4831 4315 3807 3291 2759 15 4190 3619 2931 1907 1094 VED330I Ta D B C 16 18 20 22 24 Tw C Ph Ph Ph Ph Ph in dt W W W W W 70 5 9547 9052 8557 8077 7597 10 11512 13342 10507 10012 9517 15 11197 10687 10185 9682 9195 60 5 9892 9390 8880 8385 7890 10 9247 8752 8265 7777 7297 15 8880 8385 7890 7395 6907 50 5 7305 6817 6337 5865 5400 10 6967 6480 5992 5512 5032 15 6525 6022 5520 5017 4515 40 ...

Page 162: ...e performances at medium and minimum speed are obtained by multiplying the values in the graphic by the corrective factors indicated for each speed NB The yield values marked in bold indicate the nominal value Key Tw C Inlet water temperature Ta D B C Inlet water temperature with dry bulb Ph w Heating power yielded H maximum speed M medium speed L minimum speed The heating power yielded indicated ...

Page 163: ... 5 2158 1956 1757 1555 1360 10 1982 1770 1562 1350 1132 15 1719 1485 1203 783 449 POWER YIELDED WITH HEATING ONLY COIL 4 pipes VED541I Ta D B C 16 18 20 22 24 Tw C Ph Ph Ph Ph Ph in dt W W W W W 70 5 8041 7625 7208 6803 6399 10 9696 11238 8850 8433 8016 15 9431 9002 8578 8155 7745 60 5 8332 7909 7479 7062 6645 10 7789 7372 6961 6551 6146 15 7479 7062 6645 6228 5818 50 5 6153 5742 5338 4940 4548 10...

Page 164: ...NLY 0 20 40 60 80 100 120 140 0 68 136 205 273 341 409 478 0 200 400 600 800 1000 1200 1400 1600 1800 0 0 881 1 761 2 642 3 522 4 403 5 283 6 164 7 045 7 925 VED 030I VED 040I VED 130I VED 140I VED 230I VED 240I VED 330I VED 340I 0 20 40 60 80 100 120 140 160 180 0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000 0 2 20 4 40 6 60 8 81 11 01 13 21 15 41 17 61 19 81 22 01 VED 530I VED 540I VED 541I ...

Page 165: ... 100 120 0 0 0029 0 0058 0 0087 0 0116 0 0145 0 0174 0 100 200 300 400 500 600 0 59 118 177 325 294 353 2 V 5 V 7 V 9 V 0 20 40 60 80 100 120 0 200 400 600 800 1000 VED130I 7 V 9 V 5 V 2 V 0 0 0029 0 0058 0 0087 0 0116 0 0145 0 0174 0 118 235 353 471 589 VED230I 0 20 40 60 80 100 120 0 200 400 600 800 1000 1200 7 V 9 V 5 V 2 V 0 0 0029 0 0058 0 0087 0 0116 0 0145 0 0174 0 118 235 353 471 589 706 V...

Page 166: ...01 1118 0 20 40 60 80 100 120 300 500 700 900 1100 1300 1500 1700 1900 2 V 5 V 7 V 9 V VED540I 0 0 0029 0 0058 0 0087 0 0116 0 0145 0 0174 177 294 412 530 647 765 883 1001 1118 1236 0 20 40 60 80 100 120 300 500 700 900 1100 1300 1500 1700 1900 2100 2 V 5 V 7 V 9 V VED541I 532I 0 0 0029 0 0058 0 0087 0 0116 0 0145 0 0174 0 20 40 60 80 100 120 500 1000 1500 2000 2500 3000 3500 2 V 5 V 7 V 9 V VED73...

Page 167: ...e Yield GLYCOL WATER AT 10 GLYCOL WATER AT 35 GLYCOL WATER AT 20 IN COOLING MODE IN HEATING MODE Average glycol water temperature Corrective factor Average glycol water temperature Corrective factor Average glycol water temperature Corrective factor Average glycol water temperature Corrective factor Average glycol water temperature Corrective factor Key ...

Page 168: ...pport the frame Fasten the unit to 4 threaded bars using 8 nuts 4 of which must be self locking Use the nuts to adjust the height and make sure that the unit is installed horizontally ATTENTION The fan coil must be installed perfectly horizontal Otherwise condensate water drain cannot be guaranteed Make the hydraulic connections as described in the relative chapter Make the connection of the conde...

Page 169: ...ls for each phase 2 The neutral wire section must be sized considering a working current equal to 170 of the value absorbed by the overall load of the fan coils for each phase SPECIFICATIONS OF THE CONNECTION CABLES Use H05V K or N07V K power cables with 300 500 V insulation enclosed inside a pipe or trough Use a cable with a minimum cross section of 1 mm2 All the cables must be enclosed inside a ...

Page 170: ... OFF After 1 5 min the ALARM led is permanently on Motor off Auto Restart alarm If the conditions persist after 1 5 min the alarm becomes permanent Alarm led on led ON the system switches off Overvoltage Undervoltage Overcurrent Overload Flashing ALARM led 0 5sec ON 0 5sec OFF Speed reduction Power limitation Safety control Temperature limitation STOP Alarm led permanently ON Motor off To reset th...

Page 171: ...ided by the fan coil to the pressure drops of the same duct it is possible to increase the maximum speed in the VED I fan coils To increase fan speed modify the settings of the dip switches located on the VED I motor and driver Attention Follow the settings indicated in the table for each size of VED I DIP SWITCH SETTING ONLY FOR UNITS WITH DUCTED INSTALLATION ...

Page 172: ... 0 32 6 28 4 31 2 29 8 25 6 19 4 18 0 13 9 2500 31 5 30 1 26 0 28 3 26 8 23 0 15 7 14 1 10 8 3150 28 3 26 6 23 6 25 1 23 2 20 6 12 6 10 6 8 3 4000 24 1 22 7 18 4 20 6 19 3 14 9 6 8 5 4 5 4 5000 21 4 20 4 14 5 17 7 16 9 10 1 5 0 3 7 3 7 6300 17 4 16 4 10 3 13 8 13 0 6 0 5 6 3 5 3 5 8000 13 0 11 6 7 4 9 8 8 1 4 8 7 5 4 9 4 9 10000 11 9 8 6 9 1 10 9 8 0 7 9 11 2 8 5 8 5 dB A tot 55 5 54 50 0 53 5 52 ...

Page 173: ...6 28 4 31 9 30 8 25 5 22 2 21 0 15 9 2500 32 3 31 1 26 0 29 0 27 8 22 9 18 5 17 1 12 8 3150 29 0 27 6 23 6 25 8 24 2 20 5 15 2 13 6 10 3 4000 24 8 23 7 18 4 21 4 20 3 14 8 10 9 8 4 7 4 5000 22 2 21 4 14 5 18 6 17 9 10 0 9 2 6 7 5 7 6300 18 2 17 4 10 3 14 6 14 0 5 9 9 0 6 5 5 5 8000 13 7 12 6 7 4 10 5 9 1 4 7 10 4 7 9 6 9 10000 12 4 9 6 9 1 11 4 9 0 7 8 14 0 11 5 10 5 dB A tot 56 2 55 0 50 0 49 2 5...

Page 174: ... 4 32 9 31 8 26 5 24 2 23 0 17 9 2500 34 3 33 1 28 0 30 0 28 8 23 9 20 5 19 1 14 8 3150 31 0 29 6 25 6 26 8 25 2 21 5 17 2 15 6 12 3 4000 26 8 25 7 20 4 22 4 21 3 15 8 12 9 10 4 9 4 5000 24 2 23 4 16 5 19 6 18 9 11 0 11 2 8 7 7 7 6300 20 2 19 4 12 3 15 6 15 0 6 9 11 0 8 5 7 5 8000 15 7 14 6 9 4 11 5 10 1 5 7 12 4 9 9 8 9 10000 14 4 11 6 11 1 12 4 10 0 8 8 16 0 13 5 12 5 dB A tot 58 2 57 0 52 0 55 ...

Page 175: ...4 6 46 6 44 8 41 9 26 1 24 4 21 2 1000 46 9 46 0 39 7 43 3 42 5 36 0 25 1 24 2 17 5 1250 43 9 42 5 38 5 40 4 39 0 34 8 21 5 20 2 15 6 1600 39 3 38 0 33 5 35 7 34 4 29 9 15 9 14 6 10 2 2000 38 0 36 6 32 4 34 2 32 8 28 5 13 4 12 0 7 9 2500 35 5 34 1 30 0 31 2 29 8 25 9 9 7 8 1 4 8 3150 32 3 30 6 27 6 28 1 26 2 23 5 6 6 4 6 2 3 4000 28 1 26 7 22 4 23 6 22 3 17 8 6 4 2 5 4 2 5000 25 4 24 4 18 5 20 7 1...

Page 176: ...2 46 7 42 7 41 1 39 6 35 6 2500 49 4 47 9 43 9 46 3 44 8 40 8 38 8 37 3 33 3 3150 46 3 44 8 40 8 43 0 41 5 37 5 35 0 33 5 29 5 4000 43 4 41 9 37 9 39 8 38 3 34 3 31 2 29 7 25 7 5000 39 7 38 2 34 2 35 8 34 3 30 3 26 6 25 1 21 1 6300 36 3 34 8 30 8 32 1 30 6 26 6 24 5 23 0 19 0 8000 32 5 31 0 27 0 28 1 26 6 22 6 19 8 18 3 14 3 10000 27 8 26 3 22 3 23 6 22 1 18 1 15 1 13 6 9 6 dB A tot 63 5 62 0 E 58...

Page 177: ... 7 47 7 2000 58 3 56 8 52 8 55 4 53 9 49 9 50 4 48 9 44 9 2500 54 9 53 4 49 4 51 8 50 3 46 3 46 9 45 4 41 4 3150 51 3 49 8 45 8 48 3 46 8 42 8 43 2 41 7 37 7 4000 48 0 46 5 42 5 44 8 43 3 39 3 38 4 36 9 32 9 5000 43 5 42 0 38 0 39 5 38 0 34 0 32 5 31 0 27 0 6300 39 0 37 5 33 5 34 8 33 3 29 3 27 8 26 3 22 3 8000 35 7 34 2 30 2 31 2 29 7 25 7 24 0 22 5 18 5 10000 30 8 29 3 25 3 26 2 24 7 20 7 19 1 1...

Page 178: ...lve with insulating casing connections and insulated copper tubes VCFD3 324 Kit composed of 2 way motorised valve with insulating casing connections and insulated copper tubes Forheatingonlycoil 230V 50Hz 24V 50Hz VCF45 4543 Kit composed of 3 way motorised valve with connections and insulated copper tubes VCFD4 424 Kit composed of 2 way motorised valve with connections and insulated copper tubes V...

Page 179: ... complete features of the control panels are described in the dedicated sheet Some control panels require coupling with other accessories consult the relative documentation ACCESSORIES TO COUPLE WITH THE CONTROL PANELS SIT3 Thermostat interface board Mandatory accessory on the VED units coupled to thermostats different to the VMF System SIT5 Thermostat interface board Allows to realise a network o...

Page 180: ...fic connection Ventilation suspended or activation from Economy mode the sensor indicates the absence of people in the room requires specific con nection Ventilation suspended the contact indicates window open requires specific con nection Installer configuration error or alarm Motor alarm Valve alarm Dirty filter function indicates when it is time to clean the filter the functioning time before c...

Page 181: ...s essen tial for the exchange of information within small fancoil networks up to a max of 6 thermostats and with max length of about 30 metres This was conceived to satisfy the small areas with multiple fancoils that however are to be controlled from a single control point Specifically in this network there is always a master to which the user interface is connected VMF E2 VMF E4 which controls th...

Page 182: ...P1 respectively Circulator maximum 12 configurable zone circulators Boiler boiler consent management for hot water production Heat recovery units maximum 3 consents for programmable heat recovery units according to time periods and or through the air quality detection obtained with VMF VOC accessory Domestic hot water module complete management of domestic hot water pro duction through the control...

Page 183: ...installed on units with horizontal installation Tray BC9 must be installed on units with horizontal installation Attention The BC4 accessory is not compatible with VCF VCFD VCF_X4 AUXILIARY CONDENSATE DRIP TRAY It allows you to drain condensate by means of a pump when it is necessary to exceed level differences It is mounted outside the device Attention the accessory is not compatible with AMP ins...

Page 184: ...ntake both longitudinal and perpendicular to the air flow passing through the VED unit The sides of the RPA_V intake plenum are set for the connection of a circular section channel by means of the KFV accessory KFV KFV RPA_V PA_V INTAKE PLENUM WITH CIRCULAR FLANGES PA_V is an intake plenum made of galvanised sheet metal with plastic circular flanges having variable section This accessory allows co...

Page 185: ...V accessory allows for delivery both longitudinal and perpendicular to the air flow passing through the VED unit The sides of the RPM_V flow plenum are set for the connection of a circular section channel by means of the KFV accessory PM_V FLOW PLENUM WITH CIRCULAR FLANGES KFV KFV RPM_V PM_V is a flow plenum made of galvanised sheet metal fully insulated with plastic circular flanges having variab...

Page 186: ...he PMZ accessory regulates the comfort in the environment by adjusting the air flow to the requirements The structure is made of insulated galva nised sheet metal and self extinguishing material It is equipped with a variable number of circular connections from 2 to 6 featuring 2 position motorised dampers open closed according to the model coupled The damper motor is directly controlled by the wi...

Page 187: ...MENSIONS mm GAF 22 32 42 62 A 561 792 1012 1133 B 270 270 270 300 C 605 836 1056 1177 D 314 314 314 314 E 554 785 1005 1126 F 262 262 262 292 G 500 731 851 1072 H 208 208 208 238 Attention The GA accessory is an alternative to GAF Attention The GAF accessory is alternative to GA B A 60 F D E C 6 48 DIMENSIONS mm Mod A B C D E F GM 22 457 134 502 178 452 128 GM 32 688 134 733 178 683 128 GM 42 908 ...

Page 188: ...ngs must be insulated ther mally Attention The VCF valve and the BC4 tray cannot be installed simultaneously on the same fan coil For further information refer to the accessory manual The kit composed of a 3 way motorised valve an actuator and related hydraulic fittings is suitable for installation in fan coils with both right and left connections The valve is an all or nothing type typically clos...

Page 189: ...oil For further information refer to the accessory manual The VCF_X4L and VCF_X4R valves are designed for fan coils with single coil inserted in 4 pipe systems with Hot and Cold circuits fully separated The kits consist of 2 insulated 3 way valves and 4 connections complete with electro thermal actuators valve insulating cover ing and relative hydraulic fittings The valves are an all or nothing ty...

Page 190: ...ttings must be insulated thermally Attention The VCFD valve and the BC4 tray cannot be installed simultaneously on the same fan coil For further information refer to the accessory manual VCFD 2 way valves kit The kit composed of a 2 way motorised valve an actuator and related hydraulic fittings is suitable for installation in fan coils with both right and left connections The valve is an all or no...

Page 191: ...s and copper pipes For the main coil Power supply 230V 1 50Hz WATER VALVES FOR MAIN COIL ACCESSORIES VCF45H Kit made up from motorised 3 way valves fittings and isolated copper pipes For heating only coil Power supply 230V 1 50Hz VCF47H Kit made up from motorised 3 way valves fittings and isolated copper pipes For heating only coil Power supply 230V 1 50Hz VCF25H Kit made up from motorised 2 way v...

Page 192: ...s Make sure that the drain not used is closed and does not leak The condensate drain network must be properly sized and the pipelines must be positioned in order to maintain a suitable slope along the path min 1 In the case of discharge to the sewer it is advisable to make a siphon which prevents odours from returning into the environ ment Run an operating and condensate drain system seal test by ...

Page 193: ...rical connections to the left side making them pass through the cable gland Move the support plate terminal board earthing jumper and electrical devices from the right to the left side Remount the front closing panel COIL ROTATION TROUBLESHOOTING PROBLEM PROBABLE CAUSE SOLUTION Little outlet air Incorrect speed setting on the control panel Select the correct speed on the control panel Clogged filt...

Page 194: ...Fortsschrittes behält sich Aermec S p A vor in der Produktion Änderungen und Verbesserungen ohne Ankündigung dur chzuführen ILos datos técnicos indicados en la presente documentación no son vinculantes AermecS p A sereservaelderechoderealizarencualquiermomentolasmodificacionesqueestimenecesariasparamejorarelproducto AERMEC partecipa al Programma EUROVENT FCU I prodotti interessati figurano sul sit...