5.
TECHNICAL DATA AND OPERATING LIMITS
OPERATIONAL LIMITS
UL26R
UL36R
UL26RI
UL36RI
Maximum water inlet temperature
°C
80°C
Maximum opera ng pressure
bar
8bar
FLOW LIMITS
Flow rate (min)
l/h
100
150
100
150
Flow rate (max)
l/h
700
1050
700
1050
Minimum average water temperature [°C]
Temperature of the air in the room with dry bulb
21
23
25
27
29
31
Temperature with wet bulb of the air in the
room
15
3
3
3
3
3
3
17
3
3
3
3
3
3
19
3
3
3
3
3
3
21
6
5
4
3
3
3
23
-
8
7
6
5
5
WARNING
Minimum average water tem-
perature
If the fan coil is working in
continuous cooling mode in an
environment where the relative
humidity is high, condensate
might form on the air delivery
and on the outside of the
device. This condensate might
be deposited on any objects
underneath and on the floor.
To avoid condensate on the
external structure of the device
while the fan is functioning,
the average temperature of the
water must not be lower than the
limits shown in the table below,
that depend on the thermo-
hygrometric conditions of the air
in the room.
These limits refer to unit operat-
ing with fan at minimum speed.