COIL ROTATION

If for plumbing reasons it is necessary to rotate the coils, pro-
ceeds as follows:
–  remove the electrical connections from the terminal strip;
–  remove the screws fixing the basin and remove it;
–  remove the screws fixing the coil and remove it;
–  remove the partially cut parts from the right-hand side;
–  rotate the coil and fix it with the previously removed screws;
–  refit the basin fixing it in position with the screws, insert the 

plastic caps supplied, in the holes left free by the plumbing 
connections;

  all the basins can be used for drainage on both sides. 

N.B.: Before connecting the condensate drainage pipe, push in 

the diaphragm off the basin (if present) on the plumbing 
attachment side, seal the drainage not used with the cap 
provided.

–  slide out the electrical connection from the right-hand sided, 

remove the partially cut section and move the cable fairlead 
from the right-hand side to the left;

–  move the motor cable on the left hand side and pass it throu-

gh the cable fairlead ;

–  move the terminal block and the U-bolt of the ground on the 

left-hand side;

–  restore the motor wire electrical connections;

To protect the unit against short circuits, fit an omnipolar ther-
mal-magnetic trip 2A 250V (IG) to the power line with a mini-
mum contact opening distance of 3 mm.
We recommend using differential devices suitable for interve-
ning for currents of different type:

 sinusoidal AC and pulsating DC currents suddenly 

applied or slowly rising. 

 sinusoidal AC with frequency up to 1000 hz

Each control panel can control a single fan coil.

>dZK^dd/>>zWZͳ,Z'/Z&/>dZ

Fire Resistance Class 2 (UL900). 
Easy to remove, it is supplied in a sealed box only to be opened 
when it is to be used.
The electrostatically precharged filter is combined to the nor-
mal mechanical filtration of the air that passes through the fil-
ter, also electrostatic attraction of the dust will noticeably incre-
ase its filtration.
The electrostatic precharge of the filter is spent after two years 
of the box being opened, after this period it behaves like a nor-
mal filter. 
For this reason replacement over two years with a new one is 
recommended (available as a spare part from Aermec after-
sales centres).
Cleaning frequently, removing the dust that has built up using a 
vacuum, the use of water and cleaning substances considerably 
speeds up the electrostatic precharge deterioration.

Summary of Contents for Omnia ULI P Series

Page 1: ... 6904750_00 Omnia ULI P s Ed K KEs dKZ KE DKdKZ E K Es Z KZ Έ Ή INSTALACIÓN COLGANTE PARA USO RESIDENCIAL E K t d Es Zd Z Zh DKdKZ Έ Ή WALL CEILING INSTALLATION FOR RESIDENTIAL USE s Ed KEs ddKZ KE DKdKZ Zh Es Zd Z Έ Ή INSTALLAZIONE PENSILE PER USO RESIDENZIALE KEs dKZ E D d Es Zd Z d h Zd D Zh ͳDKdKZ Έ Ή HÄNGENDE INSTALLATION FÜR DEN HAUSHALTSGEBRAUCH KEs d hZ s Ed d KE s DKd hZ Zh Es Zd Z Έ Ή IN...

Page 2: ...liquid The fancoils used for the cooling must be attached to a conden sate draining system The assembly site must be chosen in such a way that the maxi mum and minimum ambient temperature limits are respected 0 45 C 85 U R To install the unit proceed as follows The filter is fitted in a sealed package to prevent the loss of its electrostatic charge open the box and fit the filter only when the fan...

Page 3: ...e the motor wire electrical connections To protect the unit against short circuits fit an omnipolar ther mal magnetic trip 2A 250V IG to the power line with a mini mum contact opening distance of 3 mm We recommend using differential devices suitable for interve ning for currents of different type sinusoidal AC and pulsating DC currents suddenly applied or slowly rising sinusoidal AC with frequency...

Page 4: ...uilt up dust Avoid water or detergents if possible since they greatly accelerate loss of the filter s electrostatic charge After cleaning and drying the filter fit it on the fancoil by follow ing the removal procedure in reverse order SPECIAL CLEANING The removable drip tray and fan volute ensure thorough clean ing of the unit by specifically trained personnel essential for installations in venues...

Page 5: ...ect control panel setting No cold water Incorrect control panel setting No electrical power Water has not reached operating temperature Temperature and humidity limits specified by MINIMUM AVERAGE WATER TEMPERATURE have been reached SOLUTION Selectthecorrectspeedonthecontrolpanel Clean the filter Remove the obstacle Check the boiler Set the control panel Check the chiller Set the control panel Che...

Page 6: ...GRAMS READING KEY IG Master switch M Terminal strip MS Dip switch MV Fan Motor PE Earthing connection SA Ambient probe SC Control card SW Minimum water temperature probe VCH Solenoid valve Components supplied as optional extras Connections to be made in situ AR Orange BI White BL Blue GR Greet GV Yellow Green MA Brown NE Black RO Red ...

Page 7: ... ULI P Coil connection female Mod ULI 11 P ULI 16 P ULI 26 P ULI 36 P 3 R 1 2 1 2 1 2 1 2 D E KE Ίmm 145 196 80 E C B D 13 6 5 10 10 6 5 14 5 60 465 86 Mod ULI 16 P ULI 26 P ULI 36 P B 494 725 945 C 470 5 701 5 921 5 D 398 629 849 E 504 735 955 ...

Page 8: ...19 D E KE Ίmm ...

Reviews: