FUNCTIONING CHARACTERISTICS

The OMNIA ULI_PC fan coils are supplied ready to operate in the 
standard configuration, but the installer can adapt them to the 
specific needs of the system with special accessories, and can cus-
tomise the functions by adjusting the internal Dip Switches (see 
DIP SWITCH SETTINGS).

System types

The OMNIA ULI_PC series fan coils are designed for 

2-tube sys-

tems with plasmacluster and are configured:
- without valve;
- with 2-way valve and water probe downstream of the valve;
- with 3-way valve and water probe upstream of the valve;

Ventilation

The three-speed ventilation can be controlled either manually 
with the selector in V1, V2 and V3 positions (the fan is used with 
cycles of coming on and off at the selected speed), or automati-
cally with the selector in AUTO position (the fan speed is con-
trolled by the thermostat according to the room temperature).
For systems with valve (Dip.1 = ON) and water probe installation 
upstream of the valve (Dip.2 = ON), there may be a delay (maxi-
mum 2’40”) between the valve start-up and the fan activation 
(exchanger pre-heating).
Ventilation is only allowed when the fins are open; if necessary, 
open them manually.

CHANGING THE SEASON BASED ON WATER

If the thermostat is configured for use without a valve (dip1 

OFF) or with a probe upstream of the valve (dip2 ON), then 
the water temperature detected is the temperature actually 
available on the terminal and therefore the season is forced in 
Heating or Cooling based on its temperature.

35°C 

 31°C 

22°C 

  25°C 

Caldo

 

Freddo

 

Ven

Ɵ

lazione 

disabilitata 

Cooling

Ventilation 

disabled

Heating

In this configuration, the indications on the "C" led match 

the active mode (Red for Hot, Blue for Cold and Blue-Fuchsia or 
Red-Fuchsia in the disabled zone). Ventilation is only enabled 
if the water temperature is suitable for the Hot or Cold modes. 
This helps prevent undesired cold ventilation in the winter 
season, and helps control the switching on and off of all of 
the terminals, based on the actual state of the available water 
(centralised control of On-Off commands and Heating-Cooling 
commands).

CHANGING THE SEASON BASED ON AIR

There are system types that provide the change of season 

based on air. They are:

- 2-pipe system with Water Probe downstream of the valve.
- All 2-pipe systems without water probe.

The season is changed based on the following criterion:

Cooling mode: if the room temperature measured is lower 

than the chosen setpoint in an interval equal to the dead band 
(2°C or 5°C) the system passes to heating mode.

- Heating mode: if the room temperature measured is higher 

than the chosen setpoint in an interval equal to the dead band 
(2°C or 

5°C

Ή

 

the system passes to cooling mode. The dead band 

is decided by dip3 or dip3 OFF has a dead band of 5°C while 
with dip3 ON the dead band is 2°C.

Valve command

If there is a shut-off valve (dip1 ON), the position of the probe 

can be managed from either upstream or downstream of the 
valve (on the standard position engraved in the heat exchanger). 
The substantial difference between the two consists of manag-
ing the ventilation differently. If the water probe is upstream 
of the valve (dip2 ON) or not present, there is a heat exchanger 
pre-heating function that enables the fan after 2'40" from the 
first valve opening.

The valve in question (for heat exchanger pre-heating func-

tion) is Y1. Then the fan inhibition time is automatically calcu-
lated and depends on how long the valve has been closed; it can 

therefore vary from a minimum of 0'00" to a maximum of 2'40".  

Frost Protection (anti-freeze protection)

The anti-freeze protection allows you to check that the room tem-
perature never falls to freezing values, even when the fan coil is 
switched off and the selector (A) is OFF.
In the event that the temperature falls below 7°C, the thermostat 
starts up the fan coil in Heat mode with a setting of 12°C and ven-
tilation in AUTO mode, as long as the water temperature allows it, 
the fan coil is powered and the delivery fin is in the Open position. 
If there is no water probe the fan is always enabled. If the valve has 
an upstream water probe or no water probe, the heat exchanger is 
still pre-heated. 
It emerges from the anti-freeze mode when the temperature 
exceeds 9°C.

Emergency Mode

The emergency mode activates in case of failure or missing 
probe. This is indicated by the flashing yellow LED (D). In case of 
failure or missing SA ambient probe, the thermostat switches to 
the following mode:
- with selector (A) in position OFF, the water valve is closed and 
the fan turned off;
- with selector (A) in position AUTO, V1, V2 and V3, the water 
valve is always open and the fan goes through the on-off cycles 
at V1; in this condition the power from the terminal is manually 
controlled by means of the selector (B): rotating it to the right, 
the duration of the ON cycle increases up to a maximum of 5'20; 
turning it to the left decreases the duration. If there is a fault or 
missing water probe, the thermostat switches to the following 
mode:
- The ventilation is always active
- The season change is made on the basis of the difference 
between the setting made and the actual ambient temperature. 
If the ambient temperature exceeds an interval equal to the 
dead band under the Heating Mode it passes to Cooling Mode; 
If the ambient temperature drops below an interval equal to the 
dead band, Cooling Mode passes to Heating Mode;.

Plasmacluster

The Plasmacluster air purifier activates simultaneously with the 
ventilation function during both Heating and Cooling. When the 
selector (A) is in position "Aux", the machine is only used for air 
purification.
The operation of the device is indicated on the thermostat by 
the yellow LED. 
The Plasmacluster purification system breaks down the water 
and oxygen molecules that are usually in the environment's 
air (“humidity” and “oxygen”), into positive and negative ions. 
These liberated ions in the air will attach themselves to the pol-
luting substances and when they recombine (once activated) 
they decompose into non-toxic sub-products (water, oxygen and 
carbon dioxide etc.).

PACKAGING

The fan coils are sent with standard packaging consisting of pro-
tective shells and boxes.

UNIT INSTALLATION

WARNING :

 

Before carrying out any intervention, use the nec-

essary Personal Protective Equipment.
WARNING: check that the power supply is disconnected 
before carrying out any procedures on the unit.
WARNING: the electrical wirings, the installation of fan coils 
and their accessories must only be carried out by people with 
the proper technical and professional qualifications for the 
installation, conversion, expansion and maintenance of the 
systems and able to check that it is working properly and safe. 

The fan coil should be installed in such a way as to facilitate 
routine (filter cleaning) and extraordinary maintenance opera-
tions, as well as access to the air vent and discharge valves on 
the side of the unit frame (connections side) you are advised 
not to install the fan coil above objects that suffer from damp or 
wet because in some conditions condensation may form on the 
external frame of the equipment with the possibility of dripping 
or failures may occur in the hydraulic system and condensate 

Summary of Contents for Omnia UL 16 N

Page 1: ...RUSHLESS MOTOR ΈECΉ FOR FLOOR INSTALLATION WITH ELECTRONIC THERMOSTAT AND PURIFIER PLASMACLUSTER FOR RESIDENTIAL USE UNITÉ DE VENTILOͳCONVECTEURS AVEC MOTEUR VARIATEUR BRUSHLESS ΈCEΉ POUR L INSTALLATION AU SOL AVEC THERMOSTAT ÉLECTRONIQUE ET PURIFICATEUR PLASMACLUSTER À USAGE D HABITATION FANͳCOILͳEINHEIT MIT INVERTERBÜRSTENLOSEN MOTOR ΈEGΉ FÜR VERLEGUNG MIT ELEKTRONISCHEM THERMOSTAT UND REINIGER ...

Page 2: ... aux position 14 light visualisations uli_pc in the standard configuration 14 functioning characteristics 15 packaging 15 unit installation 15 electrical wirings 16 rotating the coil 16 dip switch configuration 17 important information and maintenance 17 operating limits 18 INDICE TABLE OF CONTENTS INDEX INHALTSVERZEICHN ÍNDICE ...

Page 3: ...rip tray and fan volute ensure thorough clean ing of the unit by specifically trained personnel essential for installations in venues subject to crowding or in those with spe cial hygiene requirements The new centrifugal fan unit is so quiet that at a normal oper ating speed you cannot hear when the OMNIA ULI_PC cuts in The use of the electronic control panels avoids the annoying noise typical of ...

Page 4: ...nked with the type of accessory connected to the thermostat VENTILATION LOGIC IN AUX POSITION SYSTEM VENTILATION DESCRIPTION 2 pipe system Auto VenƟlaƟon funcƟons with the thresholds of Auto mode except in pre venƟlaƟon post venƟlaƟon 2 Pipe System with Plasma Cluster V1 VenƟlaƟon acƟve at minimum speed for environment puriĮcaƟon 2 Pipe System with Bactericide lamp V1 VenƟlaƟon acƟve at minimum sp...

Page 5: ...rom a minimum of 0 00 to a maximum of 2 40 Frost Protection anti freeze protection The anti freeze protection allows you to check that the room tem perature never falls to freezing values even when the fan coil is switched off and the selector A is OFF In the event that the temperature falls below 7 C the thermostat starts up the fan coil in Heat mode with a setting of 12 C and ven tilation in AUT...

Page 6: ...e Continuity of the protection wires The electrical circuits are connected to the 230V mains voltage all the connections and components must therefore be corre spondingly insulated for this voltage CHARACTERISTICS OF THE CONNECTION CABLES Use H05V K or N07V K type cables with 300 500V with insula tion piped or ducted Use power supply cables with a minimum cross section of 1 mm2 All the cables must...

Page 7: ...ter on the outer or inner surfaces of the fan coil this might cause short circuits CLEAN THE FILTER PERIODICALLY Cleaning the filter frequently guarantees enhanced operating efficiency Check whether the filter is very dirty in this case clean it more often Clean frequently remove the dust that has built up using a vac uum cleaner and the use of water and cleaning substances con siderably speeds up...

Page 8: ...emperature of the air in the room with wet bulb C 15 3 3 3 3 3 3 17 3 3 3 3 3 3 19 3 3 3 3 3 3 21 6 5 4 3 3 3 23 8 7 6 5 5 OPERATING ENVIRONMENT ALREADY TRANSLATED OPERATING ENVIRONMENT The units are designed for installaƟon in closed environments in condiƟons of urban non marine atmosphere with non corrosive and non dusty characterisƟcs Under no circumstances the following concentraƟons of pollut...

Page 9: ...ura esterna dell apparec chio Condensation on the unit cabi net Phénomènes de condensation sur la structure exterieure de l appareil Kondenswasserbildung am Gerät Fenómenos de condensación en la estructura externa del aparato SOLUZIONE REMEDY SOLUTION ABHILFE SOLUCIÓN Sceglierelavelocitàcorrettasulpannellocomandi Select the speed on the control panel Choisir la vitesse sur la panneau de commandes ...

Reviews: