16
• REGULATING PARAMETERS (
values in the boxes are default ones):
Visualise
Parameter
Mode
AN
ANZ
HE
CR
IDROBLOC
VENICE
Set point SUMMER
Cold
11 °C
--
22 °C
11 °C
11 °C
11 °C
Hot
11 °C
11 °C
22 °C
11 °C
11 °C
11 °C
Differential SUMMER
Cold
2 °C
--
2 °C
2 °C
2 °C
2 °C
Hot
2 °C
2 °C
2 °C
2 °C
2 °C
2 °C
Set point WINTER
Cold
40 °C
--
40 °C
40 °C
40 °C
40 °C
Hot
41 °C
41 °C
31 °C
41 °C
41 °C
41 °C
Differential WINTER
Cold
3 °C
--
3 °C
3 °C
2 °C
3 °C
Hot
2 °C
2 °C
2 °C
2 °C
2 °C
2 °C
Second summer set point
from outside contact
Cold
12 °C
--
12 °C
12 °C
12 °C
12 °C
Hot
12 °C
12 °C
12 °C
12 °C
12 °C
12 °C
Second winter set point
from outside contact
Cold
40 °C
--
40 °C
40 °C
40 °C
40 °C
Hot
40 °C
40 °C
40 °C
40 °C
40 °C
40 °C
• PROBE PARAMETERS (
values in the boxes are default ones):
Visualise
Parameter
AN
ANZ
HE
CR
IDROBLOC
VENICE
Software version
1.8
1.9
1.9
1.9
1.9
1.9
Summary of Contents for micro chiller 2