17
Cooling capacities are referred to high speed.
To obtain values for other speed, multiply the values read by following factors:
MOD.
FCW
41
Medium speed
total capacity
0.91
sensible capacity
0.88
Minimum speed
total capacity
0.79
sensible capacity
0.75
Water flow rate as at maximum ventilation speed;
Tw [°C]
= Inlet water temperature
Ta w.b. [°C]
= Inlet wet bulbe air temperature
Ta b.s. [°C]
= Dry bulbe air temperature
Pc [W]
= Total cooling capacity
Ps [W]
= Sensible cooling capacity
NOTE: Values of capacity in bold face refer to nominal value.
Values of sensible capacity higher than values of total capacity mean that cooling is without dehumidification in this case
consider only the values of sensible capacity.
Tw [°C]
∆
t
Ta
b.u.
[°C]
Pc Ps Pc Ps Pc Ps Pc Ps Pc Ps Pc Ps
21°C Ta b.s.
23°C Ta b.s.
25°C Ta b.s.
27°C Ta b.s.
29°C Ta b.s.
31°C Ta b.s.
13 3 15
17
1080 921
1489 1270 2098 1789 2634 2246 3144 2680 3636 3100
19
1336 814
1640 1280 2142 1796 2642 2253 3152 2688 3644 3108
21
3308 1383 3264 1788 3333 2218 3515 2664 3783 3110
23
5078 1838 5044 2236 5018 2648 4992 3056
5 15
17
19
868 628
1202 936
1584 1351 1969 1679 2357 2010 2944 2510
21
1541 840
1735 1265 2016 1665 2362 2014 2953 2518
23
2712 1131 2729 1547 2985 1992 3420 2521
7 15
17
19
21
1022 660
1351 1077 1692 1443 2072 1767 2457 2095
23
1753 864
1943 1290 2202 1699 2504 2084
15 3 15
17
19
730 575
1089 929
1541 1314 2133 1819 2660 2268 3161 2695
21
1407 802
1830 1318 2245 1811 2664 2271 3169 2702
23
3644 1399 3627 1811 3627 2224 3757 2659
5 15
17
19
21
885 615
1213 1014 1584 1351 1969 1679 2392 2039
23
1589 818
1779 1242 2046 1646 2427 2056
7 15
17
19
21
23
1042 644
1368 1061 1705 1437 2072 1767