HEAT PUMPS - TECHNICAL MANUAL

ANK 030-045-050 

H-HP-HA

EN

Summary of Contents for ANK030 H

Page 1: ...11_11 6755532_02 HEAT PUMPS TECHNICAL MANUAL ANK 030 045 050 H HP HA EN ...

Page 2: ......

Page 3: ...perience and in depth engineering research and it is built using top quality materials and advanced technologies In addition the CE mark guarantees that our appliances fully comply with the requirements of the European Machinery Directive in terms of safety We constantly monitor the quality level of our products and as a result they are synonymous with Safety Quality and Reliability Product data m...

Page 4: ...m of system water content 30 12 1 Expansion vessel calibration 30 13 Recommended minimum water content 30 14 Sound data 31 14 1 Sound levels 31 15 Calibration of safety and control parameters 31 15 1 Control parameters 31 15 2 Protection device calibration 31 16 General warnings for the installer 32 16 1 Preservation of the documentation 32 16 2 Warnings regarding safety and installation standards...

Page 5: ......

Page 6: ...eating and cooling needs and the production of domestic hot water DHW in medium to small commercial or residential buildings These units have extremely silent functioning and are highly efficient and reliable thanks to the use of exchangers with a large exchange surface and low noise high efficiency scroll compressors 1 1 AVAILABLE VERSION ANK H Standard version ANK HP Version with circulation pum...

Page 7: ...ANK 4 5 6 SIZE 030 045 050 7 MODEL H Heat pumps 8 VERSION Standard P With pump A With storage tank 9 EXECUTION Standard 10 COIL Aluminium 11 FIELD OF USE Standard temperature of water produced up to 39 2 F 4 C 12 EVAPORATOR Standard 13 POWER SUPPLY 5 1 220V 60Hz ...

Page 8: ... Flow switch yes yes yes Safety valve yes yes yes Air vent yes yes yes Hydraulic circuit Version HP 030 045 050 Water filter yes yes yes Flow switch yes yes yes Safety valve yes yes yes Air vent yes yes yes Pump yes yes yes Expansion tank yes yes yes Hydraulic circuit Version HA 030 045 050 Water filter yes yes yes Flow switch yes yes yes Safety valve yes yes yes Air vent yes yes yes Pump yes yes ...

Page 9: ...LPT Low pressure switch VIC 4 way cycle reverse valve CN Coil CV One way valves CO Orifice F Dehydrator filter AL Storage liquid TEV Thermostatic valve BHE Plate exchanger V Fan s H2 O ETURN SYSTEM SIDE H2 O DELIVERY SYSTEM SIDE TEV F CV compressore valvola inversione CV MF FS BHE CO accumulo liquido pompa HPS HPT LPT EV LS CP AL VIC CN ...

Page 10: ...5 2 40 Standard 4 3 HYDRAULIC CIRCUIT STANDARD WATER FILTER Equipped with steel filtering mesh prevents the heat exchangers from clogging FLOW SWITCH It checks that there is circulation of water If this is not the case it blocks the unit SAFETY VALVES Set at 6 bar and the discharge conveyor discharging the excess pressure occurs in the event of abnormal pressures AIR VENT assembled on the upper pa...

Page 11: ...eck based on the pressure rather than on tem perature for absolute stability with DCPX revs adjuster accessory Inverse condensation check for the heat pump functioning mode also in summer with dcpx revs adjuster accessory Pre alarms with automatic reset in the case of alarm a certain number of re starts are allowed before the definitive block alarm on the T to identify wiring errors reverse rotati...

Page 12: ...EN 11_11 6755532_02 5 ACCESSORIES COMPATIBILITY ANK VERS 030 045 050 VT H HP VT9 VT9 VT9 HA VT15 VT15 VT15 VT ANTI VIBRATION Group of anti vibration 12 ...

Page 13: ...ompressors circuits ALL n n 1 1 1 1 1 1 Capacity control ALL 0 100 0 100 0 100 Oil charge ALL oz 30 30 30 PUMP Input power kW 0 2 0 2 0 2 Input current A 0 9 0 9 0 9 Useful head in cooling mode p s i 10 4 10 0 9 1 Useful head in heathing mode p s i 8 9 7 8 6 8 Storage tank gal 26 26 26 EXPANSION VESSEL Capacity oz 169 169 169 Calibration pressure psi 22 22 22 Quantity n 1 1 1 SOUND DATA Sound powe...

Page 14: ...dbreak recommen ds him Operation limit valid only to ANK 050 Operation limit valid only to ANK 030 045 Operation limit valid to all ANK model 7 1 COOLING MODE 7 2 HEATING MODE 25 20 25 30 35 40 45 50 55 60 65 C 68 77 86 95 104 113 122 131 140 149 F 20 15 10 5 0 5 10 15 20 25 30 35 40 45 C 13 4 5 14 23 32 41 50 59 68 77 86 95 104 113 F STANDARD functioning Temperature of the water produced External...

Page 15: ...20 3 16 32797 3 40 2 82 30736 3 66 2 46 7 40781 2 29 5 21 40931 2 59 4 63 38720 2 81 4 03 37670 3 05 3 62 35983 3 22 3 28 34184 3 43 2 92 32085 3 68 2 56 8 42468 2 41 5 16 41456 2 66 4 57 40331 2 87 4 11 39019 3 08 3 71 37445 3 28 3 35 35608 3 49 2 99 33397 3 72 2 63 10 45729 2 53 5 30 44642 2 78 4 71 43405 2 99 4 25 42018 3 19 3 86 40331 3 38 3 49 38345 3 59 3 13 36021 3 81 2 77 12 48765 2 63 5 4...

Page 16: ... 60 7 57265 3 01 5 58 56799 3 40 4 90 53662 3 72 4 23 51967 4 00 3 81 49593 4 30 3 38 47177 4 58 3 02 44464 4 89 2 67 8 59639 3 07 5 69 57859 3 45 4 91 55994 3 78 4 34 53959 4 07 3 88 51755 4 35 3 49 49254 4 62 3 12 46457 4 92 2 77 10 64090 3 21 5 85 62267 3 58 5 10 60317 3 89 4 54 58198 4 17 4 09 55824 4 44 3 68 53154 4 71 3 31 50144 5 00 2 94 12 68032 3 34 5 98 66209 3 69 5 25 64217 4 00 4 71 62...

Page 17: ... 60930 3 72 4 81 59095 4 03 4 30 57598 4 33 3 89 55575 4 65 3 50 53215 4 99 3 12 8 66098 3 49 5 55 63776 3 79 4 93 61904 4 10 4 43 60181 4 40 4 01 58234 4 71 3 62 55799 5 05 3 24 10 71228 3 63 5 75 68869 3 93 5 14 66922 4 22 4 64 65049 4 52 4 22 62990 4 83 3 82 60368 5 15 3 44 12 75498 3 75 5 89 73101 4 06 5 28 71116 4 34 4 80 69169 4 63 4 38 66997 4 93 3 98 64225 5 25 3 59 14 78980 3 87 5 98 7662...

Page 18: ...4 20 59 3 97 2 18 21 91 20 2 71 2 09 15 57 2 78 2 09 15 96 2 94 2 11 16 70 3 19 2 14 17 87 3 63 2 19 19 90 3 93 2 22 21 19 22 2 66 2 15 14 86 2 74 2 16 15 24 2 90 2 18 15 98 3 14 2 20 17 11 3 58 2 25 19 11 3 88 2 29 20 32 24 2 61 2 22 14 09 2 69 2 23 14 48 2 85 2 25 15 19 3 09 2 28 16 30 3 54 2 33 18 20 3 83 2 37 19 43 26 2 56 2 31 13 29 2 64 2 32 13 66 2 80 2 34 14 35 3 04 2 37 15 42 3 48 2 41 17...

Page 19: ...93 20 08 5 31 2 98 21 36 20 3 61 2 86 15 18 3 72 2 87 15 56 3 93 2 90 16 29 4 26 2 93 17 42 4 85 3 00 19 41 5 25 3 05 20 66 22 3 55 2 94 14 49 3 66 2 95 14 86 3 87 2 98 15 59 4 20 3 02 16 69 4 79 3 08 18 64 5 18 3 14 19 81 24 3 49 3 05 13 74 3 59 3 06 14 12 3 81 3 08 14 81 4 13 3 12 15 90 4 73 3 20 17 75 5 12 3 24 18 95 26 3 42 3 17 12 96 3 53 3 18 13 32 3 74 3 21 13 99 4 06 3 24 15 04 4 65 3 31 1...

Page 20: ... 21 46 6 37 3 34 22 84 20 4 34 3 21 16 23 4 46 3 22 16 64 4 72 3 25 17 41 5 11 3 29 18 63 5 82 3 37 20 75 6 29 3 42 22 09 22 4 26 3 30 15 49 4 39 3 31 15 89 4 64 3 34 16 66 5 04 3 39 17 84 5 74 3 46 19 92 6 22 3 52 21 18 24 4 18 3 42 14 69 4 31 3 43 15 09 4 57 3 46 15 83 4 96 3 50 17 00 5 67 3 59 18 97 6 14 3 64 20 26 26 4 10 3 55 13 86 4 23 3 57 14 24 4 48 3 60 14 96 4 87 3 64 16 08 5 58 3 71 18 ...

Page 21: ... 2 33 7 40781 2 49 4 79 40931 2 79 4 30 38720 3 01 3 76 37670 3 25 3 40 35983 3 42 3 09 34184 3 63 2 76 32085 3 88 2 42 8 42468 2 61 4 76 41456 2 86 4 25 40331 3 07 3 85 39019 3 28 3 49 37445 3 48 3 16 35608 3 69 2 83 33397 3 92 2 50 10 45729 2 73 4 91 44642 2 98 4 40 43405 3 19 3 99 42018 3 39 3 64 40331 3 58 3 30 38345 3 79 2 97 36021 4 01 2 63 12 48765 2 83 5 05 47603 3 07 4 54 46329 3 28 4 14 ...

Page 22: ... 2 49 7 57265 3 21 5 23 56799 3 60 4 63 53662 3 92 4 02 51967 4 20 3 63 49593 4 50 3 23 47177 4 78 2 89 44464 5 09 2 56 8 59639 3 27 5 34 57859 3 65 4 64 55994 3 98 4 12 53959 4 27 3 70 51755 4 55 3 33 49254 4 82 2 99 46457 5 12 2 66 10 64090 3 41 5 51 62267 3 78 4 83 60317 4 09 4 32 58198 4 37 3 90 55824 4 64 3 52 53154 4 91 3 17 50144 5 20 2 82 12 68032 3 54 5 64 66209 3 89 4 98 64217 4 20 4 48 ...

Page 23: ...11 60930 3 92 4 56 59095 4 23 4 10 57598 4 53 3 73 55575 4 85 3 36 53215 5 19 3 00 8 66098 3 69 5 25 63776 3 99 4 68 61904 4 30 4 22 60181 4 60 3 84 58234 4 91 3 48 55799 5 25 3 11 10 71228 3 83 5 45 68869 4 13 4 89 66922 4 42 4 43 65049 4 72 4 04 62990 5 03 3 67 60368 5 35 3 31 12 75498 3 95 5 60 73101 4 26 5 03 71116 4 54 4 59 69169 4 83 4 19 66997 5 13 3 82 64225 5 45 3 46 14 78980 4 07 5 68 76...

Page 24: ...67 2 34 17 16 3 97 2 38 18 25 20 2 71 2 29 12 97 2 78 2 29 13 30 2 94 2 31 13 92 3 19 2 34 14 89 3 63 2 39 16 59 3 93 2 42 17 66 22 2 66 2 35 12 38 2 74 2 36 12 70 2 90 2 38 13 32 3 14 2 40 14 26 3 58 2 45 15 93 3 88 2 49 16 93 24 2 61 2 42 11 74 2 69 2 43 12 06 2 85 2 45 12 66 3 09 2 48 13 59 3 54 2 53 15 17 3 83 2 57 16 19 26 2 56 2 51 11 08 2 64 2 52 11 38 2 80 2 54 11 96 3 04 2 57 12 85 3 48 2...

Page 25: ... 3 13 18 79 5 31 3 18 20 02 20 3 61 3 06 14 19 3 72 3 07 14 55 3 93 3 10 15 23 4 26 3 13 16 31 4 85 3 20 18 20 5 25 3 25 19 39 22 3 55 3 14 13 57 3 66 3 15 13 92 3 87 3 18 14 61 4 20 3 22 15 65 4 79 3 28 17 50 5 18 3 34 18 62 24 3 49 3 25 12 89 3 59 3 26 13 25 3 81 3 28 13 91 4 13 3 32 14 94 4 73 3 40 16 70 5 12 3 44 17 85 26 3 42 3 37 12 19 3 53 3 38 12 53 3 74 3 41 13 17 4 06 3 44 14 16 4 65 3 5...

Page 26: ...72 3 45 16 40 5 11 3 49 17 56 5 82 3 57 19 59 6 29 3 62 20 87 22 4 26 3 50 14 61 4 39 3 51 14 99 4 64 3 54 15 72 5 04 3 59 16 85 5 74 3 66 18 83 6 22 3 72 20 04 24 4 18 3 62 13 88 4 31 3 63 14 26 4 57 3 66 14 97 4 96 3 70 16 08 5 67 3 79 17 97 6 14 3 84 19 20 26 4 10 3 75 13 12 4 23 3 77 13 48 4 48 3 80 14 17 4 87 3 84 15 24 5 58 3 91 17 13 6 06 3 97 18 30 28 4 01 3 90 12 35 4 14 3 91 12 70 4 39 3...

Page 27: ...t water temperature 104 F 40 C Outlet water temperature 113 F 45 C Medium water temperature 109 4 F 43 C For different temperatures from 43 C 109 4 F use the correction table of factors 0 2 4 7 9 11 13 15 18 20 22 gpm 0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000 l h 030 045 050 0 25 50 75 100 kPa 0 9 17 26 34 ft h 0 2 3 5 ft h 0 5 10 15 kPa 0 4 9 13 22 gpm 18 0 1000 2000 3000 5000 l h 4000 A...

Page 28: ... 13 15 18 20 22 gpm ANK 030 ANK 050 ANK 045 Water flow rate Useful static pressures The static pressures stated here are at net of the pressure drops of the heat exchang ers filter storage tank Therefore are to be considered USEFUL TO SYSTEM The static pressures are calculated in cooling mode WITH PRESENCE OF GLYCOL for static pressures useful to system PLEASE CONTACT COMPANY 28 ...

Page 29: ...duce desired water tempe rature is on the lower axis 2 If you wish to calculate the percentage of glycol on the basis of the temperature of the water produced enter from the right axis and on rea ching the curve draw a vertical line which in turn will intercept all the other curves the points ob tained from the upper curves represent the coef ficients for the correction of the cooling capacity and...

Page 30: ...rence H is equal to 20 m the calibration value of the vessel will be 2 3 bar If calibration value obtained from formula is less than 1 5 bar that is for H 12 25 keep calibration as standard ANK Hydraulic height H m 30 25 20 15 12 25 Calibration of expansion vessel bar 3 2 2 8 2 3 1 8 1 5 Recommended values of water content l 1 257 303 348 394 419 Recommended values of water content l 2 116 136 157...

Page 31: ...ation of the cooling water temperature 39 2 F 4 C 44 6 F 7 C 64 4 F 18 C Differential thermostat in cooling mode 9 F 5 C 9 F 5 C 9 F 5 C ANK 030 ANK 045 ANK 050 Auxiliary magnet circuit breaker Fan pump A 220V 1 60Hz 4 Compressor magnet circuit breaker A 220V 1 60Hz 20 High pressure pressure switch bar 42 42 Low pressure transducer bar 2 2 High pressure transducer bar 40 5 40 5 15 CALIBRATION OF S...

Page 32: ...estined to this use compatibly with their performance features Any contractual or extracontractual liability of the Company is excluded for injury damage to persons animals or objects owing to installation regulation and maintenance errors or improper use All uses not expressly indicated in this manual are prohibited 16 1 PRESERVATION OF THE DOCUMEN TATION 1 The instructions along with all the rel...

Page 33: ...ndle the machine ANK 020 085 on horizon tal surfaces se fork lift trucks or similar in the most appropriate manner paying attention to the distribu tion of the unit weight The length of the pipes must be such to allow posi tioning of the lifting belts and relative safety pins Position the unit in the place indicated by the customer placing a rubber covering between the base and the support min thi...

Page 34: ...RAULIC COMPO NENTS ANK HYDRAULIC COMPONENTS SUGGESTED EXTERNAL UNIT ATTENTION The choice and the installation of components external to the ANK H up to the installer who must ope rate according to the rules of good technical design and in compliance with the regulations in force in the country of destination ATTENTION The hydraulic pipes connecting to the machine must be properly si zed to the act...

Page 35: ...HP HYDRAULIC COMPONENTS SUGGESTED EXTERNAL UNIT ATTENTION The choice and the installation of components external to the ANK H up to the installer who must ope rate according to the rules of good technical design and in compliance with the regulations in force in the country of destination ATTENTION The hydraulic pipes connecting to the machine must be properly si zed to the actual flow of water re...

Page 36: ...move any residue such as weld spatter slag rust or other impurities from the pipes These substances may otherwise accumulate in and cause a machi ne malfunction The connecting pipes should be supported so as not to weigh with their weight on the unit 1 FL 3 5 5 12 6 6 2 4 4 11 11 9 7 8 4 10 13 14 PH 6 8 Electric conductivity less than 200 mV cm 25 C Chloride ions less than 50 ppm Sulphuric acid io...

Page 37: ...ty valve 5 Area mixer valve 6 Zone pump 7 Zone flow probe 8 DHW request thermostat 9 Probe for DHW mixer management 10 DHW integrative resistance 11 DHW mixer valve Component not managed 37 V3V VT 2 4 5 6 7 3 8 9 10 11 zona 1 zona 2 M 6 7 6 7 zona 3 1 19 SYSTEM EXAMPLE zone 2 zone 3 zone 1 ...

Page 38: ...8 1 20 4 16 2 VT9 ANK030 HP 154 199 359 35 7 28 4 20 0 15 9 VT9 ANK030 HA 189 217 633 12 0 11 7 22 6 22 0 16 1 15 6 VT15A ANK045 H 165 204 362 34 9 28 9 19 8 16 4 VT9 ANK045 HP 175 203 352 35 6 29 2 19 3 15 9 VT9 ANK045 HA 210 220 643 10 7 10 8 23 8 24 0 15 3 15 4 VT15A ANK050 H 172 204 362 34 9 28 9 19 8 16 4 VT9 ANK050 HP 182 203 352 35 6 29 2 19 3 15 9 VT9 ANK050 HA 217 A A B B Yg Xg Yg Xg ANK ...

Page 39: ...mm 18 in 1281 mm 50 in 450 mm 18 in 1450 mm 57 in 21 DIMENSION mm 22 ANTIVIBRATION POSITIONING mm ANK H HP 030 045 050 ANK H HP 030 045 050 ANK HA 030 045 050 ANK HA 030 045 050 841 mm 33 in 410 mm 16 in 841 841 mm 33 in 569 mm 22 in 360 mm 14 in 46 mm 2 in ...

Page 40: ... 9 in 110 mm 4 in 53 6 mm 2 1 in IN OUT Ø 1 Ø 1 40 23 HYDRAULIC CONNECTION 23 1 ANK 030 045 050 HA 23 2 ANK 030 045 050 H 205 mm 8 in 389 mm 15 in 503 mm 20 in 110 mm 4 in IN OUT Ø 1 Ø 1 Reducer for connection STANDARD SUPPLIED ...

Page 41: ... and connection cables depending on the length the type of cable The absorption of the unit and the physi cal location and the ambient tempera ture ATTENTION Check the tightening of all power wire clamps on commissioning and after 30 days from start up Subsequently check the tightening of all the power clamps every six months Loose terminals can cause overheating of the cables and components 24 2 ...

Page 42: ...The unit is correctly fixed to the support surface 3 The minimum technical spaces have been respected 4 The hydraulic connections have been made respecting the inlet and outlet 5 The hydraulic plant has been loaded and bled 6 The hydraulic circuit cocks are open 7 The electric connections have been made correctly 8 The voltage is within the tolerance of 10 of the unit nominal value 9 Earthing is c...

Page 43: ...s com pressor block and not pump block which remains active along with the switch on of the resistance if installed To restore normal functions the temperature of the outlet water must rise above 4 C Rearm is manual WHENEVER THIS ALARM INTERVENES WE ADVISE YOU CALL THE NEAREST AFTER SALES SERVICE IMMEDIATELY 26 7 WATER FLOW RATE ALARM The MODUCONTROL manages a water flow rate alarm controlled by t...

Page 44: ...at the liquid indicator indicates the dry circuit dry green In the case of partial loss the circuit must be emptied com pletely before being re loaded The R410A refrigerant must only be loaded in the liquid state Functioning conditions that are different to the nominal conditions can give rise to values that are greatly different The sealing test or the search for leaks must only be performed usin...

Page 45: ...the next parameter use the arrow keys Fig B To modify a parameter just select it press the key shown in Fig A modify the value using the arrow keys shown in Fig B To confirm the modification press the key shown in Fig A again Fig A Fig B PASSWORD 000 How to modify a parameter in the user menu To enter the INSTALLER menu press the key shown in Fig A Once the key has been pressed the password must b...

Page 46: ... question 5 Envisioned Set the parameter ASA index A INSTALLER MENU with the value 1 4 Is a 3 way diverter valve envisioned in the DHW production circuit Reply Operations to be performed Not envisioned Go to question 5 Envisioned Set the parameter AAS index C INSTALLER menu with the appropriate value in sec onds This parameter indicates the stand by time for inversion of the 3 way diverter valve o...

Page 47: ...fastened badly Functioning outside of operational limits Check Pressure switch functions badly Replace the component Circuit breaker protection intervention Check power supply voltage Check electric isolation of the windings High discharge pressure High external air temperature High water input temperature Check Insufficient air flow Insufficient water flow Check fan functioning Check pump functio...

Page 48: ...at any time all the modifications deemed necessary for improving the product 37040 Bevilacqua VR Italy Via Roma 996 Tel 39 0442 633111 Telefax 39 0442 93730 39 0442 93566 www aermec com carta riciclata recycled paper papier recyclé recycled Papier recycled paper recycled paper papier recyclé recycled papier ...