ID
Code
Data description
0
SetFreddo
Cooling mode setting
1
SetCaldo
Heating mode setting
2
Dif.Grad
Step differential setting for thermostat
3
Tot. diff.
Total differential setting per thermostat
15
S.CaldoR
Heating mode setting for managing the heat recovery unit
16
D.Grad.R
Step differential setting for thermostat managing the heat recovery unit
17
D.Tot.R
Total differential setting for thermostat managing the heat recovery unit
41
2° Set F.
Second cooling set
42
2° Set C.
second heating set
Table ANALOGUE WRITE (Code 06)
ID
Data description
0
Standby/On command (toggle) 0=OFF 1=ON
1
Cooling/Heating mode command (toggle) 0=COLD 1=HOT
2
Safety reset command 1=RESET
3
Local/remote command (toggle) 0=LOCAL 1=REMOTE
Table DIGITAL WRITE (Code 05)
ID
Data description
35 Circuit 1 capacity control valve load
36 Circuit 1 inversion load
37 Circuit 1 bypass valve load
38 Circuit 1 fan load
39 Circuit 1 exchanger heater load
40 Circuit 1 liquid valve load
41
Circuit 1 secondary compressor load
42 Circuit 2 compressor load
43 Circuit 2 capacity control valve load
44 Circuit 2 inversion load
45 Circuit 2 bypass valve load
46 Circuit 2 fan load
47
Circuit 2 exchanger heater load
48 Circuit 2 liquid valve load
49 Circuit 2 secondary compressor load
50 Circuit 1 VRT heat recovery unit valve load
51
Circuit 2 VRT heat recovery unit valve load
ID
Data description
52 Circuit 1 VB heat recovery unit valve load
53 Circuit 1 VR heat recovery unit valve load
54 Circuit 2 VB heat recovery unit valve load
55 Circuit 2 VR heat recovery unit valve load
56 Integration 1 resistance load
57 Integration 2 resistance load
58 Integration 3 resistance load
59 Evaporator pump 2 load
60 Evaporator pump 3 load
80 Heat recovery unit flow switch alarm
81
Circuit 1A compressor heating alarm
82 Circuit 2A compressor heating alarm
83 Evaporator pump 1 heating alarm
84 Evaporator pump 2 heating alarm
85 Evaporator pump 3 heating alarm
86 Circuit 1 evaporator antifreeze alarm
87 Circuit 2 evaporator antifreeze alarm
Table DIGITAL READ (Code 01)
20