6.5 Add fresh air (option) 
 

Ø

 

The series AP is fitted with an aperture for additional air. (Figure 5.1 - Pos. 7)

 

Ø

  With the help of a flange D= 100 mm (optional accessories, article no. 6109-

0020) fresh air can be added over this opening. In addition an appropriate wall 
opening (D = 80 mm) is to be created behind the equipment, over which fresh 
air will then be sucked from outside 

 
6.6 Putting into operation 

 

Ø

  After a transport and the installation the dryer should rest in it´s final position for 

approx 15 minutes. During this period of time, the oil inside the refrigerating 
system, that was foamed during transport will return into the compressor. We 
recommend this procedure since it extends the service life of the compressor. 

Ø

  If the dryer has been installed correct, it should start automatically with hygrostat 

in Pos. I and On-/Off-switch in pos. I (figure 5.3). First the compressor starts and 
after a while the fan will also start. This function is to avoid to high starting 
current.  

 
6.7 Hygrostat control 

 

The air dryers of the AP-series dispose of a hygrostat for setting the required 
humidity value. This hygrostat is located in the operation panel. It makes that the air 
dryer cuts in as soon as the ambient humidity exceeds the preset value. If the 
humidity value falls below the set value, the hygrostat will switch off the unit. 
 
Pos. 0    = Switched off 

 

Pos. 1    = Continues working 

 

80-100% = The dehumidifier switches off  

when a humidity of approx. 80- 
95% r.h. has achieved. And  
switches on again when humidity  
is higher than 80 - 95%. 

 

60 - 80% = The dehumidifier switches off  

when a humidity of approx. 60- 
80% r.h. has achieved. And  
switches on again when humidity is higher than 60 - 80%. 

 

40 - 60% = The dehumidifier switches off when a humidity of approx. 40 - 60% r.h.  

has achieved. And switches on again when humidity is higher than 60 –  
60% r.h. 

 

20 - 40% = The dehumidifier switches off when a humidity of approx. 20- 40% r.h.  

has achieved. And switches on again when humidity is higher than 20 –  
40% r.h. 

 

The smooth setting option of the hygrostat makes a very convenient humidity 
control possible for you. If very precise values are requested, you should match the 
hygrostat with the information on a precise hygrometer. 

Summary of Contents for AP 50

Page 1: ...page 1 of 17 Instruction manual _____________________________________ Swimming pool dehumidifier AP 50 AP 70 _____________________________________ Valid 12 2010...

Page 2: ...P 70 8 6 Installation and transport 9 6 1 Place of installation 9 6 2 Fixing at a wall 9 6 3 Electrical connection 10 6 4 Condensate removal 10 6 5 Add fresh air 11 6 6 Putting into operation 11 6 7 H...

Page 3: ...ping in order to be able to send the device safe for guarantee repair In order to save space you open simply the adhesive tape with a knife and you fold the carton 2 Mode of functioning The AP air dry...

Page 4: ...ected The condensation dryers are intended for the drying of air with atmospheric pressure Risk by accessory Hoses for condensate removal must be fit expertly and must not take the protective devices...

Page 5: ...atmospheres for example ammonia and wood acid high chlorine concentration In rooms with water which shows a pH value outside of 7 0 to 7 4 Remark In The case of lower pH value corrosion occurs at all...

Page 6: ...2 3 Connection box for electrical supply see 6 3 4 Cable entries see 6 3 5 Room temperature sensor for ThermoLogic see 6 9 6 Spacer distance to the wall 7 Bleed air fresh air aperture see 6 5 8 Apertu...

Page 7: ...d 4 Cover for e box 5 Cover for compressor 5 3 Operation panel On Off switch Neon green Voltage on Neon green defrost mode Hygrostat see hygrostat control 6 7 Unit has been switched off because adjust...

Page 8: ...page 8 of 17 5 4 Dimensions AP 50 5 5 Dimensions AP 70...

Page 9: ...pirit level on all axles accurately ATTENTION The dryer is not suitable as seat furniture Damages by inappropriate treatment and use lead to expiring the guarantee 6 1 Place of Installation ATTENTION...

Page 10: ...cm per meter away from the dryer into a discharge The condensate connector is factory installed left down at the machine Depending on the situation in the room the connector can also be changed to th...

Page 11: ...Hygrostat control The air dryers of the AP series dispose of a hygrostat for setting the required humidity value This hygrostat is located in the operation panel It makes that the air dryer cuts in as...

Page 12: ...if the ambient temperature is higher lower than the allowed working range 32 C 3 C As soon as the allowed temperature has reached the compressor switches on again automatically If the Thermologic swi...

Page 13: ...sions width height depth 824 mm 740 mm 261 mm weight 54 kg refrigerant CFC free R134a filling charge see type plate Capacity in acc to DIN EN 810 E Temperature relative humidity capacity l day Power c...

Page 14: ...does not run Is the unit supplied with voltage Check the main cable and the main fuse The humidity value adjusted at the hygrostat is achieved The dryer will start again after exceeding the adjusted...

Page 15: ...ons of AERIAL air dryers we recommend get in touch with your supplier The producer AERIAL GmbH you reach under 0049 40 526879 0 or www aerial de 10 Disposal Please do not dispose this unit with the do...

Page 16: ...page 16 of 17 11 circuit diagram AP 50 AP 70...

Page 17: ...yer ready for connection Related standards EN ISO 12100 Safety of Machinery EN 61 000 Electromagnetic Compatibility EMC Basic Specification Emitted Interference EN 60 335 2 40 Safety of electric appli...

Reviews: