page 1 of 14 

 
 
 
 
 
 

 

Instruction manual 

 
_____________________________________ 

 
Dehumidifier 

 AD 810 

_____________________________________ 
 

 

 
 
 
 
 
 
valid: 10-2010 
 
 

Summary of Contents for AD 810

Page 1: ...page 1 of 14 Instruction manual _____________________________________ Dehumidifier AD 810 _____________________________________ valid 10 2010 ...

Page 2: ...d transport 5 6 Operation 6 1 Electrical connection 6 6 2 Putting into operation 6 6 3 Operation panel 7 6 4 Hygrostat control 7 8 6 5 Condensate removal 8 9 6 6 Automatic defrosting 9 7 Operating conditions 9 10 8 Technical data 10 11 9 Service and maintenance 11 10 Trouble shooting 12 13 11 Disposal 13 12 Manufacturer s declaration 14 ...

Page 3: ...uld be noticed after unpacking the equipment please contact immediately your respective seller or specialized dealer Before putting your air dryer into operation for the very first time these instructions for operation should be studied very thoroughly Thus you can make sure that this appliance will operate perfectly for a long period of time saving yourselves unnecessary repairs and expenses In t...

Page 4: ...ntal conditions The AD dehumidifier works according to the condensation principle with heat recovery The fan shown indicatively below suck the moist air through a cool register evaporator The air becomes so far chilled under the point of condensation here that the moist air condense as water and flows through the pump out into a sump The chilled and dried air is warmed up at the condenser again Th...

Page 5: ...e must of course be determined and kept Unclear competences are a safety hazard The operator must make the operating instruction available for the user and make sure that the user did understand the manual 5 Installation and transport The dehumidifiers of series AD 810 are conceived for the mobile or stationary employment During the setting up and transportation of the dehumidifier the following i...

Page 6: ... or inappropriate operation as well as by inadequate environmental conditions can be avoided For using the air dryer please proceed as follows Ø After having been transported the air dryer should rest for about 15 min During this period of time the oil inside the refrigerating system that was foamed during transport will return into the compressor We recommend this procedure since it extends the s...

Page 7: ...on 80 100 The dehumidifier switches off when a humidity of approx 80 95 r h has achieved And switches on again when humidity is higher than 80 95 60 80 The dehumidifier switches off when a humidity of approx 60 80 r h has achieved And switches on again when humidity is higher than 60 80 40 60 The dehumidifier switches off when a humidity of approx 40 60 r h has achieved And switches on again when ...

Page 8: ...floors or paintings antiques and similar things should not be fallen below a humidity of 55 Ask your technical consultant in the case of special applications 6 5 Condensate removal The dehumidifier AD 810 is serially equipped with a built in condensate pump The condensate pump is placed below the air filter behind the back plate In the back plate a connector and a button is placed Afitting connect...

Page 9: ...automatic hot gas defrosting It ensures that depending on the extent of ice formation the appliance will be defrosted automatically according to the following principle Ø A temperature sensor measures the condition existing in a critical area of the evaporator Ø It transmits the signal for defrosting to the DryLogic electronic The DryLogic finds out if defrosting is necessary and it will start def...

Page 10: ...ly air movings around the dryer can annoy or affect the function of the dryer as the air flow of the dryer can not flow as planned In the case of doubtful operating conditions it is recommended to contact the Technical Department of Messrs AERIAL or a specialized dealer Using an AD air dryer under inadequate operating conditions will entail that the warranty becomes null and void 8 Technical data ...

Page 11: ... Remove filter holder see 1 1 Ø Remove filter and clean or organize new one Ø Remove cover front top panel Ø Check pump all hose connections and hoses Ø Blow out device cautiously with compressed air wear protective goggles In this case it might ensure that all components are cleaned Compressor evaporator condenser ect Ø mount cover front top panel Ø Clean case with moist cloth Do not use aggressi...

Page 12: ...al cable the socket and the main fuse The humidity value adjusted at the hygrostat is achieved The dryer will start again after exceeding the adjusted humidity There is a fault at the condensate pumpe In that case the red neon in the operation panel see Pt 1 1 lights up Check the pump and all cables Let repair the unit by an expert 4 Strong icing up at the evaporator Put the dryer into a room with...

Page 13: ...ions of AERIAL air dryers we recommend get in touch with your supplier The producer AERIAL GmbH you reach under 0049 40 526879 0 or www aerial de 11 Disposal Please do not dispose this unit with the domestic waste and please do not dispose this unit in the environment We dispose this unit for you free of charge and environment friendly Please contact us Alternative your local waste management ente...

Page 14: ...eady for connection Related standards EN ISO 12100 Safety of Machinery EN 61 000 Electromagnetic Compatibility EMC Basic Specification Emitted Interference EN 60 335 2 40 Safety of electric appliances for domestic use and similar purposes In the case of changings at the unit this manufacturer s declaration becomes void Norderstedt 01 10 2010 sign stamp Karsten Meier General Manager AERIAL GmbH Ost...