Page 13 of 29
Select the location in a way to ensure optimum circulation of the dehumidifier air
in your room.
The air dehumidifier must be installed on a flat ground.
By using an air dehumidifier humidity values of 30% r. h. can be
reached. If lower values are required an adsorption dryer must be
used. Contact your technical advisor.
In case of doubts about the operating conditions your technical advisor can help
you.
Electrical connection
DANGER
Danger to life due to electric shock
Prior to commissioning the technical data of the air
dehumidifier must be compared with the conditions
prevailing in the room of installation!
The following items must be checked prior to electrical connection of the air
dehumidifier:
The mains voltage must be in conformity with the voltage of the air
dehumidifier!
Socket outlet and supply system must be sufficiently fused!
In damp locations or on building sites a residual current circuit breaker must
be installed!
The appliance coupler must be suitable for the building socket outlet!
The socket outlet used must be grounded properly!
Connect the power cable to the power outlet.
Connect condensate drain hose
CAUTION
Material damage / insufficient performance due to improper
connection of condensate drain hose
Without water collecting tank The rear hose end must be
in a lower position than the front hose end (drain pipe):
minimum slope 5%, i. e. 5 cm / meter.
Do not immerse the hose end in water (water back-up
may occur).
Never bend the hose.