6.2. THE S-PRE/DAY-NIGHT/T SENSOR'S ELECTRICAL CONNECTIONS WITH 

THIRD PARTY MODBUS SYSTEM

Disconnect the electrical power supply before any operations. The S-PRE/DAY-NIGHT/T communicates 
with other components through Modbus connection which is made by a RS485 interface connected 
through a double RJ45 connector for daisy chain linking.

All the components are linked to each other via a daisy-chain whose length should not exceed 200 m 
with shielded CAT5E cable or better. At the beginning and at the end of the daisy-chain, a termination 
is needed. An electrical control board that contains a converter USB -> RS485 and a BUS polariza-
tion is necessary for the Modbus connection schemes. Aereco offers an optimal solution of electrical 
control board (ref: ADX1785EX) that is adapted to its prsence Modbus sensors

Modbus connection to the occupancy sensor

2W-Modbus on RJ45 socket pin-out

6. 

THE S-PRE/DAY-NIGHT/T SENSOR'S CONNECTIONS WITH   

    THIRD PARTY MODBUS SYSTEM

6.1. SETTINGS OF THE S-PRE/DAY-NIGHT/T SENSOR FOR THIRD PARTY 

MODBUS SYSTEM

15 indexation positions are allowed for Modbus addressing: position 1 to position F included. 
Address 0 is the broadcast address, this address is then forbidden.

Important: Several sensors up to 15 can be connected to the bus in daisy-chain. Every 

sensor must have a specific Modbus address (1...F). This Modbus address has to be 

different from a sensor to another one.

Note: the sensors are delivered in position 0. They must be manipulated with extreme care.

Modbus address rotary switch for selecting 
sensors ( on the sensor's PCB)

1

3

4

5

2

TF5414_B

B

A C D

E

F

0

Summary of Contents for CAP1669

Page 1: ...INSTALLATION AND MAINTENANCE INSTRUCTION ENGLISH VERSION S PRE DAY NIGHT T MODBUS SENSOR HUB 8 SE ACCESSORIES THIRD PARTY MODBUS SYSTEM TF6582_A_NOT_INST_PRE_SENSOR_MODBUS Aereco S A ...

Page 2: ...ate of the unit Before carrying out any operation on the appliance unplug or disconnect it from the power supply and ensure it can not be accidentally restored Power cable modification or replacement must only be carried out by qualified personnel or by After sales Service in order to avoid any accident Children being supervised not to play with appliance 1 INTRODUCTION This document presents the ...

Page 3: ...ped with claws for installation in false ceiling Location of sensors ceiling positioning in a detection zone zone located at least at 1 meter from walls considered as zone where there are few movements height installation ceiling position up to 3 5 meters 3 5 m max 3 m min 4 2 m max 1 m 2 m 3 6 m 2 m 2 8 m max 2 8 m max Dead zone Day detection of the presence of light naturel light or artificial l...

Page 4: ...her one The index numbers must be incremented to each other so that there is no digit jump Example Presence sensor bedroom A 1 because Hub SE outlet n 1 is connected to bedroom A Presence sensor bedroom B 2 because Hub SE outlet n 2 is connected to bedroom B Presence sensor bedroom C 3 because Hub SE outlet n 3 is connected to bedroom C CO2 sensor in living room 4 because Hub SE outlet n 4 is conn...

Page 5: ...e Hub SE cannot be started accidentally The Hub SE communicates to the other components through ModBus connection All the components are linked other via a daisy chain At the beginning and at the end of the daisy chain a termination is needed B B B C D D A 230 VAC Modbus connection to the occupancy sensor A Hub SE B Sensors C Compensation valve at exhaust D ModBus Termination RJ 45 Supply 230 V 1 ...

Page 6: ...onnection schemes Aereco offers an optimal solution of electrical control board ref ADX1785EX that is adapted to its prsence Modbus sensors Modbus connection to the occupancy sensor 2W Modbus on RJ45 socket pin out 6 THE S PRE DAY NIGHT T SENSOR S CONNECTIONS WITH THIRD PARTY MODBUS SYSTEM 6 1 SETTINGS OF THE S PRE DAY NIGHT T SENSOR FOR THIRD PARTY MODBUS SYSTEM 15 indexation positions are allowe...

Page 7: ...r Cut and free the wires coming from the RJ45 connector and connect directly to the terminal block of the controller Second possibility is to use an adaptor RJ45 RJ45 to terminal block 6 4 APPLICATION DEVELOPMENT FOR MODBUS SENSOR Th diagram below shows the connexion between the Computer and sensors Note Aereco developed a customised kit for connecting PC and sensors you can easily order with the ...

Page 8: ...se Time 1fc ms typ 500ms Built in temperature sensor1 Temperature working range 2 C to 50 C Accuracy 0 5 C ensured at 25 C Conversion Gain 10mV C LED Indicators Yellow LED for Modbus traffic indicator Red LED for presence indicator Electrical specifications Power supply 12 VDC Power consumption standby mode 2mA Max Power consumption detection mode 3mA Max Connection Type 2xRJ45 shielded Operating ...

Page 9: ...fter sales service In any case the warranty may not cover additional costs of labour transport or compensation of any kind The warranty does not cover damage due to improper installation in this manual improper use or attempted repair by unauthorized personnel In case of problems please contact your installer or your reseller 9 CONFORMITY AND STANDARD The S PRE DAY NIGHT T Modbus sensor is CE cert...

Page 10: ...SOR_MODBUS Copyright Aereco All data and pictures in this document are non contractual and are subject to change without prior notice Aereco S A 62 rue de Lamirault Collégien 77615 MARNE LA VALLEE CEDEX 3 FRANCE www aereco com ...

Reviews: