1.

 

GENERAL INTRODUCTION

 

AERCO Modulex EXT gas fired boilers are modulating input boilers that require an adequate volume 
and pressure of natural or  propane gas for proper  operation. The gas requirements  specified herein 
must be satisfied for efficient combustion. Designers and installers must adhere to the specifications 
of AERCO and of the local authorities having jurisdiction. A thorough understanding and knowledge of 
these guidelines is required for the successful design and installation of Modulex EXT boilers.   

2.

 

GAS TRAIN COMPONENTS

 

The Modulex EXT is a cast aluminum body boiler consisting of mutually connected combustion chambers, 
each  having  its  own  gas  train  (gas  valve,  pre-combustion  chamber,  and  burner),  blower,  air  pressure 
switch,  check  valve,  igniter,  and  flame  detector.  Each  group  of  these  components  is  referred  to  as  a 
module.  The  gas  train  components  have  been designed  to  operate  at  high combustion  and  seasonal 
efficiencies  by  closely  controlling  both  the  volume  and  air/fuel  mixture  to  the  burner.  Below  are 
descriptions of each of the gas train components for each module.     

  GAS  VALVE 

–  An  electronic,  modulating  gas  valve  with  100%  tight  shutoff.  It  controls  the 

amount of gas delivered to the burner.     

  PRE-COMBUSTION CHAMBER 

– A plastic chamber mounted to the blower, where combustion 

air and gas mix prior to entering the burner, providing controlled combustion. The outlet of the 
chamber leads to a check valve, which prevents any backflow of combustion gases.   

  LOW  NOx  BURNER 

–  A  metal  fiber  mesh  covering  a  stainless  steel  burner  head  on  which 

combustion occurs. The burner operation is stable throughout the entire input range of the boiler. 
 

NOTE:

 

The optimum gas pressure for the Modulex EXT boiler is 7.0” W.C. However, the 

Modulex EXT boiler can be safely operated at pressures ranging from 3.5” W.C. to 10.5” W.C.  

3.

 

GAS PRESSURE REQUIREMENTS

 

AERCO Modulex EXT boilers require a stable gas input pressure. The inlet supply to the unit must be 

at least 3.5 

“ W.C. when firing at maximum input. A minimum supply gas pressure switch prevents the 

boiler from operating without sufficient pressure. Maximum allowable gas pressure is 

10.5” W.C.  Static 

gas pressure (when the unit is not firing) may vary, however actual gas pressure should be measured 
when the unit is in operation (firing). Measure the gas pressure with a manometer at the port provided 
in  the  inlet  manifold.  In  a  multiple  boiler  installation,  gas  pressure  should  initially  be  set  for  a  single 
boiler  in  operation  and  then  remaining  boilers  should  be  staged  on  at  full  fire  to  ensure  that  gas 
pressures never fall below the minimum allowable pressure of 3.5” W.C. 

An external gas pressure regulator is mandatory for the State of Massachusetts, regardless of supply 
pressure; for all other jurisdictions, a lock-up style regulator is required when supply pressure is greater 
than 10.5” W.C. (see Fig. 1). The regulator must be installed with at least 2 feet of pipe between the 
regulator and the unit gas inlet. The regulator discharge range must able to maintain 3.5” W.C. Gas 
regulators are self-contained with tapped diaphragm vent ports allowing the diaphragm to change its 
position. These vents typically require piping to the outside.  

Every Modulex boiler requires a manual shutoff valve. CSA requires that no other components can be 
installed  between  the  boiler  and  this  shutoff  valve  except  for  pipe  fittings  such  as  a  pipe  union.  If  an 
external regulator is used, an additional isolation/service valve must be installed upstream of the regulator 
(see 

Figure 1

).  Gas  piping should contain  ground  unions for  removal  of  the gas piping to the  unit for 

maintenance or service as required. Gas piping should never obstruct removal of the unit side panels and 
should not be supported from the unit itself. Gas piping should be supported properly from the floor or 
overhead as the installation allows. 

Summary of Contents for EXT Series

Page 1: ...rranty of any kind with respect to this material including but not limited to implied warranties of merchantability and fitness for a particular application AERCO International is not liable for errors appearing in this manual or for incidental or consequential damages occurring in connection with the furnishing performance or use of these materials Heating and Hot Water Solutions AERCO Internatio...

Page 2: ... boiler can be safely operated at pressures ranging from 3 5 W C to 10 5 W C 3 GAS PRESSURE REQUIREMENTS AERCO Modulex EXT boilers require a stable gas input pressure The inlet supply to the unit must be at least 3 5 W C when firing at maximum input A minimum supply gas pressure switch prevents the boiler from operating without sufficient pressure Maximum allowable gas pressure is 10 5 W C Static ...

Page 3: ...ultiple units are installed some utilities and local codes require a full size drip leg on the main gas supply line in addition to the drip leg at each unit The bottom of the gas drip leg s should be removable without disassembling any gas piping The weight of the gas pipe should not be supported from the bottom of the drip leg The drip leg s should not be used to support any or part of the gaspip...

Page 4: ...onnected input within the allowable gas pressure drop The allowable minimum and maximum gas pressure for each device should be considered Whenever the minimum and maximum gas pressures vary between devices gas pressure regulators at each unit should be installed to allow regulation at any individual unit Gas pressure must never exceed the maximum allowable rating of any connected device The total ...

Page 5: ...above or behind boiler Gas piping should not be installed directly over top or front of any part ofboiler Figure 2 Typical Multiple Boiler Gas Manifold Construction Ensure proper clearances for maintenance Piping should not interfere with the removal of the unit s sheet metal nor impede maintenance Observe service clearances around the boiler as listed below and as shown in Figures 3 4 and 5 EXT 4...

Page 6: ...6 0288 Figure 3 MODULEX EXT 450 2S 1100 2S Boiler Clearances Figure 4 MODULEX EXT 1500 2S 3000 2S Boiler Clearances NOTE Standard locations for components connections are on the right hand side Dotted lines show alternate flue locations For EXT 1500 2S 3000 2S Figure 4 use 32 81 28mm for vent flue at any side as needed and 24 60 96mm all others ...

Page 7: ...es Piping Application Guide TAG 0096 AERCO International Inc 100 Oritani Dr Blauvelt NY 10913 Page 7 of 7 Phone 800 526 0288 10 06 2021 Figure 5 MODULEX EXT Boiler Top Clearances MLX 1500 2S 3000 2S MLX 450 2S 1100 2S ...

Reviews: