aerauliqa QR400ABP Installation Manual Download Page 14

14

It allows to adjust the various speeds.

Press OK to enter.

Use 

 or 

 to choose speed 1, speed 2, speed 3 or Holiday.

Press OK to select.

The setting ranges are:

speed 1: 10% ÷ 80% 

speed 2: 20% ÷ 90% 

speed 3: 60% ÷ 100% 

Holiday: 10% ÷ 40%

Use 

 or 

 to increase or decrease the speed percentage.

Press OK to select.

Press ESC to go back to the previous menu.

The factory settings (DEFAULT) are:

speed 1: 40%

speed 2: 70%

speed 3: 100%

Holiday: 20%

Installer menu

6 Heating Threshold
7 Dehumidification
8 Speed Setting
9 Airflow Balancing
10 F7 filter

Installer menu

6 Heating Threshold
7 Dehumidification
8 Speed Setting
9 Airflow Balancing
10 F7 filter

It allows to adjust the balancing of the two airflows.

Press OK to enter.

“Supply airflow” is highlighted.

Press OK to enter.

The setting range is: -20% ÷ +20% 

Use 

 or 

 to adjust supply airflow against extract airflow.

Press OK to select.

Press ESC to go back to the previous menu.

The factory settings (DEFAULT) is 0%.

To be selected only in case an F7 filter is installed at the supply air side (Fig. 7.a).

Press OK to enter.

Use 

 or 

 to choose “Not installed” or “Installed”.

Press OK to select.

The factory setting (DEFAULT) is “Installed”. 

Installer menu

6 Heating Threshold
7 Dehumidification
8 Speed Setting
9 Airflow Balancing
10 F7 filter

Installer menu

11 Filter Alarm interval
12 Working Hours Counter
13 Save settings
14 Load settings
15 Restore Default Settings

It allows to set the Filter Alarm period: the system has a timer which activates the “Filter” 

warning on the LCD at regular intervals.

Press OK to enter. 

Use 

 or 

 to choose among 2-3-6 months or OFF.

Press OK to select. 

The factory setting (DEFAULT) is 3 months if F7 filter is “Installed” or 6 months if F7 filter 

is “Not installed”.

Installer menu

11 Filter Alarm interval
12 Working Hours Counter
13 Save settings
14 Load settings
15 Restore Default Settings

The system keeps trace of the actual working hours of the unit. This value cannot be 

changed. Data is saved both on the motherboard and on the control panel CTRL-DSP, to 

be safe in case of fault. 

Press OK to enter.

Press OK or ESC to go back to the previous menu.

It allows to save the setting of the #1 (prototype) installation in the internal memory of the 

CTRL-DSP to be loaded afterwards in other units. 

Press OK to enter.

Use 

 or 

 to choose the position where to save hte setting. Up to 8 differrent settings 

can be saved.

Press OK to select. 

Press OK to confirm.

Press ESC to go back to the previous menu.

Installer menu

11 Filter Alarm interval
12 Working Hours Counter
13 Save settings
14 Load settings
15 Restore Default Settings

Summary of Contents for QR400ABP

Page 1: ...ion 2 3 1 General 2 3 2 Dimensions and Weight 3 3 3 Connections 3 3 4 Space required 4 3 5 Rating label 4 4 Transport and Storage 4 5 Installation 4 5 1 Unpacking 4 5 2 Where how to install 4 5 3 Inst...

Page 2: ...r than those specified in this manual This appliance can be used by children aged from 8 years and above and persons with reduced physical sensory or mental capabilities or lack of experience and know...

Page 3: ...e Winter condensation drainage Summer condensation drainage A B D C F E A B C D LEFT Connections from and to outside are set on the left side of the unit front view DEFAULT RIGHT Connections from and...

Page 4: ...veled before it is put into operation Place the unit preferably in a separate room e g storage laundry room or similar WARNING Make sure that specific warnings and cautions in Chapter 2 Precautions ar...

Page 5: ...ccordance with local rules and regulations 5 b Use the wall fixing bracket as template to indicate where to drill the holes in the wall make sure it is at spirit level Use appropriate screws and wall...

Page 6: ...ns SLAVE input 1 10V J2 jumper for SLAVE mode AC power supply Heat output max 250Vac 5A Dehumidifier output max 250Vac 5A Boost momentary switch BST IAQ input Air Quality i e SEN CO2 HY input i e SEN...

Page 7: ...t settings of the 0 10V signal to the motors Airflow and consumption refer to one single motor Table 6 b indicates the efficiency of the heat exchanger and of the condensation produced in different cl...

Page 8: ...250 500 1 K 2 K 4 K 8K Tot 3m Intake 73 61 67 69 59 56 50 43 75 47 Supply 72 61 63 65 56 50 41 31 74 43 Extract 73 60 63 65 57 51 42 31 74 44 Exhaust 73 61 66 67 58 55 49 41 75 46 Breakout 71 64 62 67...

Page 9: ...eset the Filter Alarm ESC key to exit and go back to the previous menu OK key to enter the selected menu to go DOWN with the menu selection to go UP with the menu selection to power off the ventilatio...

Page 10: ...at speed 1 Press ESC or wait for about 60 sec to go back to the operation screen Fig 7 c In case of activation of either HY or IAQ sensor inputs OR logic the unit speed increases by 15 and the sensor...

Page 11: ...boost speed Press OK to select The factory setting DEFAULT is 15 Time options are 15 30 45 60 Time is flashing use increase the time and to decrease Press OK to select User menu 1 Mode Selection 2 Bo...

Page 12: ...lows to select the orientation of the duct connections from and to outside LEFT or RIGHT paragraph 3 3 Press OK to enter Use or to choose Press OK for setting The factory setting DEFAULT is LEFT 7 2 I...

Page 13: ...s intalled at intake air side Fig 7 a HEAT output Fig 5 g is activated and heating icon displays on LCD when T21 HEATING THRESHOLD Fig 7 a POST the heating element is intalled at supply air side Fig 7...

Page 14: ...idification 8 Speed Setting 9 Airflow Balancing 10 F7 filter Installer menu 11 Filter Alarm interval 12 Working Hours Counter 13 Save settings 14 Load settings 15 Restore Default Settings It allows to...

Page 15: ...QR400ABP is equipped with a physical bypass which allows to mitigate the heat exchange when the indoor and outdoor temperature combinations are such that the heat exchange is not recommended In this c...

Page 16: ...re life time lubricated and maintenance free It is possible to easily disconnect and replace the fans if necessary Filters The filters are of filter quality G4 for both the supply air and extract air...

Page 17: ...may differ per situation depending on the internal and external environmental conditions Press FILTER button Fig 7 b to reset the Filter Alarm Filters must be replaced every year Clean the heat exchan...

Page 18: ...18 Fig 8 i Fig 8 h Fig 8 j Fig 8 k Fig 8 l Fig 8 m...

Page 19: ...ll 1 Drainage parts have not been installed correctly 2 Drain connection below the unit has a too low water level fill it up with water 3 Check filters Change of filters required 4 Check ducting syste...

Page 20: ...2 Control typology Local demand control Central demand control Manual control no DCV o1 Maximum internal leakage rate 0 6 o2 Maximum external leakage rate 0 4 p1 Internal mixing rate N A p2 External m...

Page 21: ...21 NOTE...

Page 22: ...22 NOTE...

Page 23: ...23 NOTE...

Page 24: ...office viaCorsica10 25125Brescia C F e P IVA VAT 03369930981 REA BS 528635 Tel 39 030 674681 Fax 39 030 6872149 www aerauliqa com info aerauliqa it Aerauliqa srl reserves the right to modify make impr...

Reviews: