22
Speed 100%
Lw dB - SOUND POWER OCTAVE BAND
Lp dB(A)
63
125
250
500
1K
2K
4K
8K
Tot
@3m
Intake
76
64
70
72
62
59
53
46
78
50
Supply
75
64
66
68
59
53
44
34
77
46
Extract
76
63
66
68
60
54
45
34
77
47
Exhaust
76
64
69
70
61
58
52
44
78
49
Breakout
74
67
65
70
62
56
48
36
77
48
Speed 80%
Lw dB - SOUND POWER OCTAVE BAND
Lp dB(A)
63
125
250
500
1K
2K
4K
8K
Tot
@3m
Intake
67
63
70
69
60
58
51
43
74
48
Supply
65
61
65
66
57
51
42
31
71
44
Extract
66
61
65
65
58
53
43
32
71
44
Exhaust
66
62
68
69
59
56
50
43
71
47
Breakout
61
66
65
67
57
53
45
33
71
45
Speed 60%
Lw dB - SOUND POWER OCTAVE BAND
Lp dB(A)
63
125
250
500
1K
2K
4K
8K
Tot
@3m
Intake
57
57
69
57
51
49
42
33
70
41
Supply
55
55
64
54
49
43
34
24
65
37
Extract
60
54
62
53
49
44
34
24
65
36
Exhaust
57
56
68
57
51
49
42
33
69
41
Breakout
56
55
61
54
50
45
35
25
64
36
Speed 40%
Lw dB - SOUND POWER OCTAVE BAND
Lp dB(A)
63
125
250
500
1K
2K
4K
8K
Tot
@3m
Intake
51
51
58
47
40
38
28
21
60
31
Supply
53
51
57
44
37
31
23
16
59
29
Extract
53
48
55
44
38
32
22
16
58
27
Exhaust
52
50
56
48
40
37
29
22
59
30
Breakout
53
48
53
45
39
32
22
16
57
27
Table 6.c
Sound level: dB(A) figures are average spherical free-field, for comparitive use only.
6.2 Before starting the system
When the installation is finished, check that:
• Filters are mounted correctly.
• The unit is installed in accordance with the instructions.
• The unit is correctly wired.
• Eventual outdoor and exhaust air dampers and silencers are installed and that the duct system is correctly connected to the unit.
• All ducts are sufficiently insulated and installed according to local rules and regulations.
• Outdoor air intake is positioned with sufficient distance to pollution sources (kitchen ventilator exhaust, central vacuum system
exhaust or similar).
• The unit is correctly set and commissioned.