6 coMMissioninG
6.1 setting fan speed
The speed of the unit can be adjusted during installation according to required ventilation rate.
figures 6. a-d
below show performance curve at different settings of the 0-10V signal to the motors. Consumption refers to the 2
motors.
figures 6. b-e
indicate the data of the enthalpic heat exchanger.
tables 6. c-f
indicate the sound level at the different speeds.
fig. 6.a
Intake curve according to Reg.
1253/2014 (ErP).
Static Pressure - Pa
Airflow - m
3
/h
Curve
Speed %
W
max
m
3
/h
max
A (min)
23
9
36
B
30
17
88
C
46
33
139
D
60
41
153
E
77
51
172
F
92
100
230
G (max)
100
160
281
0
50
100
150
200
250
300
350
400
450
500
550
600
0
20
40
60
80
100
120
140
160
180
200
220
240
260
280
300
A
B
C
D
E
F
G
0
10
20
30
40
50
60
70
80
90
100
0
40
80
120
160
200
240
280
Curva di efficienza termica
Curva di efficienza igrometrica
fig. 6.b
Data of the enthalpic heat
exchanger.
Test conditions:
Indoor air 25°C 50% RH;
External air 5°C 70% RH.
Efficiency
-
%
Airflow - m
3
/h
QR280E
Thermical efficiency curve
Hygrometric efficiency curve
10