AEMT TIME MARK 2732 Manual Download Page 2

INSTALLATION

 

 

Connect the control wiring to the terminals with the contact 
markings (refer to the diagram on the unit).   Apply power.

 

 

For manual reset

, a jumper connection is added on the reset 

terminals and the reset button on the top of the monitor is 
used.

 

 

For remote reset

, a remote normally-closed button can be 

added (both manual reset buttons can be used in this 
configuration). 
 

ADJUSTMENT

 

 

Set the time delay to the required amount of delay.  If the 
desired trip level is known, set the trip adjustment to that point.  
A slight adjustment up or down may be necessary to allow for 
tolerance variations.

 

 

Usually a trip is desired only if the current changes from the 
present nominal.  For calibration, turn the TRIP DELAY 
clockwise to the maximum delay.

 

 

Turn the TRIP LEVEL slowly up (or down)  until the yellow 
TRIP indicator comes on.  Turn the adjustment back until the 
L E D just goes out (if the manual reset is used, press and hold 
the reset button during this step).

 

 

Reset the time delay to the previous setting. 
 

TROUBLESHOOTING

 

 

Should the Model 2732 Single Phase Current Monitor fail to 
operate, check all connections.  Verify that power is present, 
and check all fuses.  Should problems persist, contact the 
factory at 800-862-2875 for assistance. 
 

WARRANTY

 

 

The 

Model 2732 Single Phase Current Monitor 

is warranted 

to be free from defects in materials and workmanship for one 
year.  Should this device fail to operate, we will repair or 
replace it for one year from the date of purchase.  For 
complete warranty details, see the 

Terms and Conditions of 

Sales 

page in the front section of the Time Mark catalog. 

TYPICAL APPLICATION

 

Under-Current with Alarm; Manual Reset 

TYPICAL APPLICATION

 

Over-Current with Alarm; Remote Manual Reset 

MODEL 2732 

Single-Phase Current Monitor 

R e a d   A l l   I n s t r u c t i o n s   B e f o r e   I n s t a l l i n g ,   O p e r a t i n g   o r   S e r v i c i n g   T h i s

 

D e v i c e .

 

KEEP THIS DATA SHEET FOR FUTURE REFERENCE.

 

 

GENERAL SAFETY

 

 

POTENTIALLY HAZARDOUS VOLTAGES ARE PRESENT AT THE TERMINALS OF THE MODEL 2732.

 

ALL ELECTRICAL POWER SHOULD BE REMOVED WHEN CONNECTING OR DISCONNECTING WIRING. 

THIS DEVICE SHOULD BE INSTALLED AND SERVICED BY QUALIFIED PERSONNEL. 

 

Installation Instructions 

 

TIME MARK is a division of

Telephone:    Main -     (918) 438-1220 
                        Sales -    (800) 862-2875

 

Fax:                                 (918) 437-7584 
 
E-mail:            [email protected] 
Internet:         http://www.time-mark.com 

Doc No. 87A209   12/00 

© 2000   

TIME MARK CORPORATION

 

11440 East Pine Street  

Tulsa, Oklahoma  74116 

Shows No Power Applied 

Shows No Power Applied 