- 4 -
Definition of Measurement Categories
CAT I:
For measurements on circuits not directly connected to the AC
supply wall outlet such as protected secondaries, signal level,
and limited energy circuits.
CAT II:
For measurements performed on circuits directly connected to
the electrical distribution system. Examples are measurements
on household appliances or portable tools.
CAT III:
For measurements performed in the building installation at the
distribution level such as on hardwired equipment in fixed
installation and circuit breakers.
CAT IV:
For measurements performed at the primary electrical supply
(<1000V) such as on primary overcurrent protection devices,
ripple control units, or meters.
Receiving Your Shipment
Upon receiving your shipment, make sure that the contents are
consistent with the packing list. Notify your distributor of any missing
items. If the equipment appears to be damaged, file a claim immediately
with the carrier and notify your distributor at once, giving a detailed
description of any damage.
Packaging
The AC/DC Current Probe Model SL206 (Cat. #1201.45) is shipped with
one 9V battery (not installed) and this user manual.
Compatibility
The AC/DC Current Probe Model SL206 is compatible with any DMM,
voltmeter, or other voltage-measuring instrument that has the following
features:
Range and resolution capable of displaying 1mV of input.
Voltmeter accuracy (uncertainty) of 0.75% or better to take full
advantage of the accuracy of the probe.
Minimum input impedance of 100k
(1V/A range) or 10k
(10mV/A range).