ELECTRICAL SPECIFICATIONS

 

Nominal Range: 

2A, 150A

 

Measurement Range: 

2A:

 

0.01 to 2.4A 

 

150A:

 0.1 to 200A

 

Transformation Ratio: 

Voltage output

 

Output Signal:  

2A:

 

1000mV/A 

 

150A:

 10mV/A

 

Accuracy and Phase Shift*: 

2A Range - Accuracy 

0.01 to 0.1A: 

 5% Reading ± 2mV 

0.1 to 1A: 

 3% Reading ± 1mV 

1 to 2A: 

 1% Reading 

2 to 2.4A:  

 1% Reading 

Phase Shift: Not specified 

 

 

150A Range - Accuracy 

0.1 to 1A: 

 3% Reading ± 200µV 

1 to 20A: 

 2% Reading ± 200µV 

20 to 80A: 

 1% Reading 

80 to 150A: 

 3% Reading 

150 to 200A:  Not specified 

150A Range - Phase Shift 

0.1 to 1A: 

Not specified 

1 to 20A: 

 3° 

20 to 80A: 

 2° 

80 to 150A: 

 3° 

150 to 200A: 

 4° 

(*Reference  conditions: 18°C  to 28°C , 20 to 75% R

H, 

external  magnetic  field  <40  A/m, 48 to 65H z si ne w ave, 

distortion f actor l ess than 1%, no D

C  component,  no 

external current carrying conductor, test sample centered.) 

Load impedance > 1M

Overload: 

240A for 10 min ON, 30 min OFF

 

Frequency Range: 

40 to 10kHz

 

Limit Operating Conditions: 

200A permanently to 1kHz; Derating above 

3kHz: 200A x (1/0.333F), F in kHz 

Crest Factor: 

2A:

 3 @ 2A Peak w/ an error (due to CF) of 3% 

150A:

 3 @ 150A Peak w/ an error (due to CF) of 3% 

Working Voltage: 

600Vrms 

Common Mode Voltage: 

600Vrms

 

Influence of Adjacent Conductor: 

< 15mA/A at 50Hz 

Influence of DC on AC signal: 

2A Range:

 DC Current < 1A, < 3% 

150A Range:

 DC Current < 10A, < 10% 

Influence of Conductor Position in Jaw:  

0.5% of mV output @ 50/60Hz 

Influence of Frequency:  

2A Range:

 

40Hz to 1kHz: 10% of mV output 

1kHz to 10kHz: 10% of mV output 

150A Range:

 

40Hz to 1kHz: 5% of mV output 

1kHz to 10kHz: 15% of mV output 

Influence of Temperature: 

 200 ppm/°K, or 0.2% of mV output per 10°K 

Influence of Humidity (10 - 90% RH): 

 0.2% of mV output per 10°K @ 18° to 28°C 

MECHANICAL SPECIFICATIONS 

Operating Temperature: 

14° to 131°F (-10° to +55°C)  

Storage Temperature: 

-40° to 158°F  (-40° to +70°C) 

Operating Relative Humidity: 

10° to35°C 85% RH (without roll-off above 35°C) 

Maximum Cable Diameter: 

One Ø 0.78” (20mm), bus bar 20 x 5 mm 

Case Protection: 

IP 40 (IEC 529) 

Drop Test: 

Test per IEC 68-2-32: 

1.0 m drop on 38mm of Oak on concrete 

Mechanical Shock: 

Test per IEC 68-2-27 

Vibration: 

Test per IEC 68-2-6 

Dimensions: 

5.47 x 2.00 x 1.18" (139 x 51 x 30mm) 

Weight: 

180g (6.5oz) 

Polycarbonate Material: 

Jaws:  Polycarbonate with 10% fiberglass charge, 

 

Red UL 94 V0 

Case: Polycarbonate 920A Gray 

Opening Operations - Life:

 > 50,000

 

Output: 

Double/reinforced insulated 5 ft (1.5m) lead with 

safety 4mm banana plug  

SAFETY SPECIFICATIONS 

      

      

     

Electrical: 

Double insulation or reinforced insulation between 

the primary or secondary and the outer case of the 

handle conforms to IEC 1010-2-32. 

Common Mode Voltage: 

600V Category III, Pollution Degree 2 

Dielectric Strength: 

5550V, 50/60Hz between primary, secondary  

and the outer case of the handle 

Electromagnetic Compatibility: 

EN 50081-1 Class B 

EN 50082-2 Electrostatic discharge 

   IEC 1000-4-2 

Radiated field IEC 1000-4-3 

Fast transients IEC 1000-4-4 

Magnetic field at 50/60Hz IEC 1000-4-8 

ORDERING INFORMATION 

AC Current Probe MN373 ................. Cat #2116.28 

 

Accessories: 

Banana plug adapter 

(to non-recessed plug)  ....................... 

Cat #1017.45

 

E192383

2.56"

 (65 mm)

5.47"

 (139 mm)

.83"

 (21 mm)

Black

Red

.73"

2.00"

 (51 mm)

(18.5 mm)

.1.18"     

(30 mm)

Tactical

Barrier

(keep hands below

this barrier)

w

w

w

.

G

lo

ba

lTe

st

Su

pp

ly

.c

om

Fin

d Q

ua

lit

y P

ro

du

ct

s O

nli

ne

 a

t:

sa

le

s@

G

lo

ba

lTe

st

Su

pp

ly.c

om

Reviews: