background image

 

99-MAN 100138.v8 01/16 

 

OPERATION 

Please make sure that you have already read and fully understand the WARNING section on page 1. 

Making Measurements with the AC Current Probe Model MN213 

•   Connect the black lead of the current probe to “common” and the red lead to the AC current input on 

your  DMM  or  other  current  measuring  instrument.  Select  the  appropriate  current  range  (400mA

AC

 

range). Clamp the probe around the conductor to be tested with the arrow pointed toward the load. If the 
reading is less than 400mA, select the lower range until you obtain the best resolution. Read the value 
display on the DMM and multiply it by the probe ratio (1000/1). (If reading = 0.159A, the current flowing 
through the probe is 0.159A x 1000 = 159A

AC

•  For best accuracy, avoid if possible, the proximity of other conductors which may create noise. 

Tips for Making Precise Measurements 

•    When  using  a  current  probe  with  a  meter,  it  is  important  to  select  the  range  that  provides  the  best 

resolution. Failure to do this may result in measurement errors. 

•  Make sure that probe jaw mating surfaces are free of dust and contamination. Contaminants cause air 

gaps between the jaws, increasing the phase shift between primary and secondary. It is very critical for 
power measurement. 

MAINTENANCE: 
Warning

 

• For maintenance use only original factory replacement parts. 

• To avoid electrical shock, do not attempt to perform any servicing unless you are qualified to do so. 

• To avoid electrical shock and/or damage to the instrument, do not get water or other foreign agents 

into the probe 

Cleaning 

To ensure optimum performance, it is important to keep the probe jaw mating surfaces clean at all times. 
Failure to do so may result in error in readings. To clean the probe jaws, use very fine sand paper (fine 
600) to avoid scratching the jaw, then gently clean with a soft oiled cloth. 

REPAIR AND CALIBRATION 

You  must  contact  our  Service  Center  for  a  Customer  Service  Authorization  number  (CSA#).  This  will 
ensure that when your instrument arrives, it will be tracked and processed promptly. Please write the CSA# 
on the outside of the shipping container.  

Chauvin Arnoux

®

, Inc. d.b.a. AEMC

®

 Instruments 

 

15 Faraday Drive 

 Dover, NH 03820 USA 

(800) 945-2362 (Ext. 360) • (603) 749-6434 (Ext. 360) • [email protected] 

(Or contact your authorized distributor) 

NOTE: All customers must obtain a CSA# before returning any instrument. 

TECHNICAL AND SALES ASSISTANCE 

If  you  are  experiencing  any  technical  problems,  or  require  any  assistance  with  the  proper  use  or 
application of this instrument, please contact our technical hotline: 

(800) 343-1391 • (508) 698-2115 • [email protected] 

LIMITED WARRANTY 

The current probe is warranted to the owner for a period of one year from the date of original purchase 
against  defects  in  manufacture.  This  limited  warranty  is  given  by  AEMC

®

  Instruments,  not  by  the 

distributor from whom it was purchased. This warranty is void if the unit has been tampered with, abused 
or if the defect is related to service not performed by AEMC

®

 Instruments.  

Full warranty coverage and product registration is available on our website at: 
www.aemc.com/warranty.html. 

Please print the online Warranty Coverage Information for your records. 

 

AC Current Probe 
Model MN213 

User Manual

 

 

DESCRIPTION 

The  MN213  (Cat.  #2115.75)  is  the  latest  in  compact  AC  current  probes.  Designed  to  meet  the  most 
stringent demands in industry and electrical contracting, it also meets the latest safety and performance 
standards.  The  probe  has  a  measurement  range  up  to  240Arms  which  makes  it  a  perfect  tool  for 
measurement with DMMs, recorders, power and harmonic meters. The Model MN213 is compatible with 
any AC ammeter, multimeter, or other current measurement instrument with an input impedance lower 
than  1

.  To  achieve  the  stated  accuracy,  use  the  MN213  with  an  ammeter  having  an  accuracy  of 

0.75% or better. 

WARNING 

The  safety  warnings  are  provided  to  ensure  the  safety  of  personnel and proper operation of the 
instrument. Read the instruction completely. 

•  Use caution on any circuit: potentially high voltages and currents may be present and may pose 

a shock hazard. 

•  Do not use the probe if damaged. Always connect the current probe to the measuring device 

before it is connected around the conductor 

•  Do  not  use  on  non-insulated  conductor  with  a  potential  to  ground  greater  than  600V  CAT  III 

pollution 2. Use extreme caution when clamping around bare conductors or bus bars. 

•  Before each use, inspect the probe; look for cracks in housing or output cable insulation. 

•  Do not use clamp in wet environment or in locations that hazardous gases exist. 

•  Do not use the probe anywhere beyond the tactile barrier. 

INTERNATIONAL ELECTRICAL SYMBOLS 

This symbol signifies that the current probe is protected by double or reinforced insulation. Use 
only factory specified replacement parts when servicing the instrument. 

This symbol signifies CAUTION! and requests that the user refer to the user manual before 
using the instrument. 

This is a type A current sensor. This symbol signifies that application around and removal from 
HAZARDOUS LIVE conductors is permitted. 

DEFINITION OF MEASUREMENT CATEGORIES 
CAT II: 

For  measurements  performed  on  circuits  directly  connected  to  the  electrical  distribution  system. 
Examples are measurements on household appliances or portable tools. 

CAT III:

  For  measurements  performed  in  the  building  installation  at  the  distribution  level  such  as  on 

hardwired equipment in fixed installation and circuit breakers. 

CAT IV: 

For  measurements  performed  at  the  primary  electrical  supply  (<1000V)  such  as  on  primary 
overcurrent protection devices, ripple control units, or meters. 

RECEIVING YOUR SHIPMENT 

Upon receiving your shipment, make sure that the contents are consistent with the packing list. Notify 
your distributor of any missing items. If the equipment appears to be damaged, file a claim immediately 
with the carrier and notify your distributor at once, giving a detailed description of any damage. 
 

Reviews: