background image

 

99-MAN 100137.v7 09/16 

 

OPERATION 

Please make sure that you have already read and fully understand the WARNING section on page 1. 

Making Measurements with the AC Current Probe Models MN210/MN211 

•  Connect the black lead of the current probe to “common” and the red lead to the AC current input on your 

DMM  or  other  current  measuring  instrument.  Select  the  appropriate  current  range  (400  mA  AC  range). 
Clamp the probe around the conductor to be tested with the arrow pointed toward the load. If the reading 
is less than 400 mA, select the lower range until you obtain the best resolution. Read the value display on 
the DMM and multiply it by the probe ratio (1000/1). (If reading = 0.159 A, the current flowing through the 
probe is 0.159 A x 1000 = 159 A AC) 

•  For best accuracy, avoid if possible, the proximity of other conductors which may create noise. 

Tips for Making Precise Measurements 

•    When  using  a  current  probe  with  a  meter,  it  is  important  to  select  the  range  that  provides  the  best 

resolution. Failure to do this may result in measurement errors. 

•  Make sure that probe jaw mating surfaces are free of dust and contamination. Contaminants cause air 

gaps between the jaws, increasing the phase shift between primary and secondary. It is very critical for 
power measurement. 

MAINTENANCE: 

Warning

 

• For maintenance use only original factory replacement parts. 

• To avoid electrical shock, do not attempt to perform any servicing unless you are qualified to do so. 

• To avoid electrical shock and/or damage to the instrument, do not get water or other foreign agents into 

the probe 

Cleaning 

To ensure optimum performance, it is important to keep the probe jaw mating surfaces clean at all times. 
Failure  to do so may result in error in  readings. To clean the probe jaws, use very fine sand  paper (fine 
600) to avoid scratching the jaw, then gently clean with a soft oiled cloth. 

REPAIR AND CALIBRATION 

You  must  contact  our  Service  Center  for  a  Customer  Service  Authorization  number  (CSA#).  This  will 
ensure that when your instrument arrives, it will be tracked and processed promptly. Please write the CSA# 
on the outside of the shipping container.  

Chauvin Arnoux

®

, Inc. d.b.a. AEMC

®

 Instruments 

 

15 Faraday Drive 

 Dover, NH 03820 USA 

(800) 945-

2362  (Ext. 360) • (603) 749-6434  (Ext. 360) • [email protected] 

(Or contact your authorized distributor) 

NOTE: All customers must obtain a CSA# before returning any instrument. 

TECHNICAL AND SALES ASSISTANCE 

If  you  are  experiencing  any  technical  problems,  or  require  any  assistance  with  the  proper  use  or 
application of this instrument, please contact our technical hotline: 

(800) 343-

1391 • (508) 698-2115 • [email protected] 

LIMITED WARRANTY 

The current probe is  warranted to the  owner  for a period  of one  year from  the date of original purchase 
against  defects  in  manufacture.  This  limited  warranty  is  given  by  AEMC

®

  Instruments,  not  by  the 

distributor from whom it was purchased. This warranty is void if the unit has been tampered with, abused 
or if the defect is related to service not performed by AEMC

®

 Instruments.  

Full warranty coverage and product registration is available on our website at: 
www.aemc.com/warranty.html. 

Please print the online Warranty Coverage Information for your records. 

AC Current Probe 
Models MN210 and MN211 

User Manual

 

 

DESCRIPTION 

The  MN210/MN211  (Catalog  #2115.72  and  #2115.73)  are  the  latest  in  compact  AC  Current  probes. 
Designed to meet the most stringent demands in industry and electrical contracting, they also meet the 
latest safety and performance standards. The probes have a measurement range up to 240 Arms which 
makes  them  perfect  tools  for  measurement  with  DMMs,  recorders,  power  and  harmonic  meters.    The 
Models MN210/MN211 are compatible with any AC ammeter, multimeter, or other current measurement 
instrument  with  an  input  impedance  lower  than  1

.  To  achieve  the  stated  accuracy,  use  the 

MN210/MN211 with an ammeter having an accuracy of 0.75% or better. 

WARNING 

These safety warnings are provided to ensure the safety of personnel and proper operation of the 
instrument. 

•  Read the instruction manual completely and follow all the safety information before attempting 

to use or service this instrument. 

•  Use caution on any circuit: Potentially high voltages and currents may be present and may pose 

a shock hazard. 

•  Read  the  Safety  Specifications  section  prior  to  using  the  current  probe.  Never  exceed  the 

maximum voltage ratings given. 

•  Safety is the responsibility of the operator. 

•  ALWAYS connect the  current  probe to the display  device  before clamping the probe  onto the 

sample being tested. 

•  ALWAYS inspect the instrument, probe, probe cable, and output terminals prior to use. Replace 

any defective parts immediately. 

•  NEVER  use  the  current  probe  on  electrical  conductors  rated  above  600V  in  overvoltage 

category III (CAT III). Use extreme caution when clamping around bare conductors or bus bars. 

INTERNATIONAL ELECTRICAL SYMBOLS 

This symbol signifies that the current probe is protected by double or reinforced insulation. Use 
only factory specified replacement parts when servicing the instrument. 

This symbol signifies CAUTION! and requests that the user refer to the user manual before 
using the instrument. 

This is a type A current sensor. This symbol signifies that application around and removal from 
HAZARDOUS LIVE conductors is permitted. 

DEFINITION OF MEASUREMENT CATEGORIES 
Cat. II: 

For  measurements  performed  on  circuits  directly  connected  to  the  electrical  distribution  system. 
Examples are measurements on household appliances or portable tools. 

Cat. III:

  For  measurements  performed  in  the  building  installation  at  the  distribution  level  such  as  on 

hardwired equipment in fixed installation and circuit breakers. 

Cat. IV: 

For  measurements  performed  at  the  primary  electrical  supply  (<1000V)  such  as  on  primary 
overcurrent protection devices, ripple control units, or meters. 

RECEIVING YOUR SHIPMENT 

Upon  receiving  your  shipment,  make  sure  that  the  contents  are  consistent  with  the  packing  list.  Notify 
your distributor of any missing items. If the equipment appears to be damaged, file a claim immediately 
with the carrier and notify your distributor at once, giving a detailed description of any damage. 

 

Reviews: