Non-Contact, High Voltage Detector 275HVD
The following information provides typical detection distances when using
a lower setting than the line voltage.
Note that the distances may vary with each unit and will be affected based
on the actual environment. The values displayed were conducted in an
ideal lab environment and cannot represent each field environment.
SETTING
VOLTAGE
DISTANCE
240V
AC
500V
AC
12" - 32cm
240V
AC
1kV
AC
18" - 48cm
240V
AC
2kV
AC
29" - 75cm
240V
AC
6kV
AC
48" - 124cm
240V
AC
11kV
AC
57" - 146cm
240V
AC
22kV
AC
89" - 226cm
SETTING
VOLTAGE
DISTANCE
2kV
AC
6kV
AC
16" - 40cm
2kV
AC
11kV
AC
20" - 52cm
2kV
AC
22kV
AC
24" - 60cm
2kV
AC
33kV
AC
36" - 92cm
SETTING
VOLTAGE
DISTANCE
6kV
AC
11kV
AC
24" - 61cm
6kV
AC
22kV
AC
29" - 75cm
6kV
AC
33kV
AC
41" - 105cm
SETTING
VOLTAGE
DISTANCE
11kV
AC
22kV
AC
13" - 35cm
11kV
AC
33kV
AC
16" - 42cm
SETTING
VOLTAGE
DISTANCE
22kV
AC
33kV
AC
14" - 36cm