Rx Message 2 receives the PWM duty value for the output. The PWM control of the outputs is designed to
regulate the speed of devices like pumps and fans. If message 2 is present then all of the outputs will
become PWM duty cycle outputs with a base frequency of 100hz.The requested duty cycle can vary
between 0 –
100%. Any outputs that you do not want to have a PWM should have a value of 255. If this
message does not update within 500mS then the PDU-8 will treat all channels with simple ON/OFF control.
PDMDutyOut0#
is an unsigned 8 bit number with a scale of 0.392157 and an offset of 0 (0-100%).
PDU-8 Rx Message 2, 0x000A0630 (for unit 1) timeout if not updated within 500mS
6/9/2020 –
Document Number: 10-8300-EV
© 2020 AEM Performance Electronics