Layout type (inside wall, under ground, free air etc.)
-
UV resistance
Illustration 5.4: Overview of Inverter with Torque Indications
Parameter
Screwdriver
Tightening Torque
1
Front screws
TX 30
6-8 Nm
2
Locking screw
TX 30
5 Nm
3
Terminal blocks (small)
Straight slot 0.5x3.0 mm
0.5 Nm
4
Terminal blocks (large)
Straight slot 1.0x5.5 mm
Min. 1.2 Nm
5
PE
Straight slot 1.0x5.5 mm
2.2 Nm
6
M16
SW 19 mm
2-3 Nm
7
M25
SW 30 mm
2-3 Nm
Table 5.6: Nm Specifications
Protect PV 10 kW
Protect PV 12.5 kW
Protect PV 15 kW
Maximum inverter current
15 A
19 A
22 A
Recommended fuse type gL/gG
16 A
20 A
25 A
Table 5.7: Mains Circuit Specifications
5. Technical Data
8000038781_00_BAL_en / L00410564-01_02
27
5