1. Introduction

1.1. Introduction

This manual provides information on functionality and maintenance of the Protect PV solar in-
verter.

Illustration 1.1: Protect PV 10 kW, Protect PV 12.5 kW, Protect PV 15 kW

CE marking - This certifies the conformity of the equipment with the regula-
tions which apply in accordance with the directives 2004/108/EC and
2006/95/EC.

The Protect PV inverter series comprises:
Protect PV
Protect PV easy

1.2. Operation Mode Definition

Off grid (LEDs off)
When no power has been delivered to the AC grid for more than 10 minutes, the inverter dis-
connects from the grid and shuts down. This is the normal night mode. The user and communi-
cation interfaces are still powered for communication purposes.

Connecting (Green LED flashing)
The inverter starts up when the PV input voltage reaches 250 V. The inverter performs a series
of internal self-tests, including PV auto detection and measurement of the resistance between
the PV arrays and earth. Meanwhile, it also monitors the grid parameters. When the grid pa-
rameters  have  been  within  the  specifications  for  the  required  amount  of  time  (depends  on
country settings), the inverter starts to energise the grid.

1. Introduction

 

2

 

 8000038784_00_BAL_en / L00410565-01_02 

 

1

Summary of Contents for Protect PV

Page 1: ...Protect PV Solar Inverters User Manual AEG Power Solutions GmbH Revision 01 Date 2011 05 25 User Manual 8000038784_00_BAL_en ...

Page 2: ...k Guide 12 Introduction 12 Supported Characters 12 Access and Initial Setup 12 Setup Wizard 13 Operation 17 Web Server Structure 17 Plant Group and Inverter Views 19 Additional Information 20 4 Troubleshooting 21 Troubleshooting 21 5 Maintenance 22 Maintenance 22 Cleaning the Cabinet 22 Cleaning the Heatsink 22 Contents 8000038784_00_BAL_en L00410565 01_02 1 ...

Page 3: ...e AC grid for more than 10 minutes the inverter dis connects from the grid and shuts down This is the normal night mode The user and communi cation interfaces are still powered for communication purposes Connecting Green LED flashing The inverter starts up when the PV input voltage reaches 250 V The inverter performs a series of internal self tests including PV auto detection and measurement of th...

Page 4: ...n goes into connecting mode or off grid mode Fail Safe Red LED flashing If the inverter detects an error in its circuits during the self test in connecting mode or during operation the inverter goes into fail safe mode The inverter will remain in fail safe mode until PV power has been absent for a minimum of 10 minutes or the inverter has been shut down completely AC PV Refer to the section on Tro...

Page 5: ...w Screen OK Enter select Arrow up A step up increase value Arrow Down A step down decrease value Arrow Right Moves cursor right Arrow Left Moves cursor left Back Return de select On Green LED On flashing On grid Connecting Alarm Red LED Flashing Fail safe The inverter is configured as mas ter Icons can be found in the top right corner The inverter is connected to a mas ter Icons can be found in th...

Page 6: ... Table 2 1 View 2 1 2 View 2 Menu Structure View 2 Parameter Description Grid mgmt Indicates whether or not any grid management measures are in effect Hidden if no grid management measures are in effect Performance ratio 87 Performance ratio is shown if irradiation sensor is available local or master Total CO2 saved 123 T Lifetime CO2 emission saved calculated using configured value Total revenue ...

Page 7: ...input 1 The configuration is only shown when the in verter is in Connecting or On grid mode PV input 2 Individual PV input 3 Individual AC grid Present Values Phase 1 Voltage 250 V Voltage on phase 1 Current 11 5 A Current on phase 1 Frequency 50 Hz Frequency on phase 1 Power 4997 W Power on phase 1 Phase 2 Phase 3 Residual Current Monitor Current 350 mA Residual current in mA Grid management Only...

Page 8: ...d Part and serial number C0010000241 Aux board part number 002541H2204 Aux board serial number Communication board Part and serial number C0010000201 Communication board part number 032500H2504 Communication board serial number Software version Communication board software version Func Safety Processor Software version Functional Safety processor software version Display Software version Display s...

Page 9: ...on from this year shown in KWh Last year 10000 kWh m2 2 years ago 10000 kWh m2 3 years ago 10000 kWh m2 20 years ago 10000 kWh m2 Irradiation log Only visible if it contains non zero values This week Irradiation from this week Monday 37 kWh m2 Irradiation from one day shown in kWh m2 Tuesday 45 kWh m2 Wednesday 79 kWh m2 Thursday 65 kWh m2 Friday 88 kWh m2 Saturday 76 kWh m2 Sunday 77 kWh m2 Past ...

Page 10: ...Due to frequency support Reactive Power 0 h Due to reactive energy support Reactive Power Only visible if the current country setting is an MV country or custom and in Protect PV versions Reactive Energy underexcited 1000 000 VArh Reactive Energy overexcited 1000 000 VArh Event log Latest event 0 The latest event is displayed The number is for service purposes Zero indicates no error Last 20 event...

Page 11: ...current date Time hh mm ss 13 45 27 Set the current time Calibration Only applicable if sensors are connected PV array PV input 1 6000 W PV 1 area 123 m2 PV input 2 6000 W PV 2 area 123 m2 PV input 3 6000 W Not visible if inverter only has 2 PV inputs PV 3 area 123 m2 Not visible if inverter only has 2 PV inputs Irradiation sensor Scale mV 1000 W m2 75 Sensor calibration Temp coeff 0 06 oC Sensor ...

Page 12: ... Utest 234 V Only visible during voltage tests Fgrid 50 03 Hz Only visible during frequency tests Ftest 50 03 Hz Only visible during frequency tests Disconnection time 53 ms Not visible in Off and Completed OK states Logging Interval 10 min The interval between each logging Logging capacity 10 Days Web Server Reset password Resets the password of the Web Server to its default value Security Passwo...

Page 13: ...e allowed in inverter name 3 3 Access and Initial Setup 3 3 1 Access via PC Ethernet Interface Change the Web Server logon and password of the master inverter immediately for optimal security when connecting to the internet To change the password go to Setup Web Server Admin Setup Sequence 1 Select which inverter will be set up as master 2 Open the cover of this inverter Refer to the Protect PV In...

Page 14: ...r click on Set this inverter as master A scan runs to identify inverters in the network A pop up window shows the inverters successfully identified Click ok to confirm that the correct number of inverters has been found Illustration 3 2 Step 1 of 7 Master Setting To change this setting later refer to Setup Inverter Details Step 2 of 7 Display language Select display language This is not a country ...

Page 15: ... and time are used for logging purposes Adjustment for daylight savings is automatic Illustration 3 4 Step 3 of 7 Time and Date To change these settings later refer to Setup Inverter details Set Date and Time Step 4 of 7 Installed power For each PV input enter surface area installed power For more information refer to the Protect PV Reference Manual 3 Web Server Quick Guide 14 8000038784_00_BAL_en...

Page 16: ...country setting to match the installation To meet medium voltage grid requirements select a country option ending in MV The default setting is undefined Select the country setting again to confirm The setting is activated immediately Correct selection is essential to comply with local and national standards An incorrect setting can have serious consequences 3 Web Server Quick Guide 8000038784_00_B...

Page 17: ...e country setting later refer to Setup Setup Details Step 6 of 7 Replication To replicate the settings from steps 1 to 6 to other inverters in the same network Select inverters Click Replicate Note When the PV configuration installed PV power and PV array area of follower inverters in the network differ from that of the master do not replicate Set up the follower inverters individ ually 3 Web Serv...

Page 18: ...elf test takes a few minutes Illustration 3 8 Step 7 of 7 Inverter startup To change the setup later access the inverter via the integrated web interface or the display at inverter level To change the name of the inverter go to Setup Inverter details To enable master mode go to Setup Inverter details 3 4 Operation 3 4 1 Web Server Structure The Web Server overview is structured as follows 3 Web Se...

Page 19: ...rter view Change the name of the inverter via Setup Inverter details in the inverter view 4 Main menu This menu corresponds to the inverter display main menu 5 Sub menu The sub menu corresponds to the main menu item currently selected All sub menu items belonging to a particular main menu item are displayed here 6 Content area The Web Server main menu and sub menus are identical to the menus in th...

Page 20: ... content of the main menu changes depending on which view is currently selected the plant a group of inverters or an individual inverter The active view is indicated by text in red 3 4 2 Plant Group and Inverter Views The overview screens for plant view group view and inverter view display the same overall status information Illustration 3 10 Plant View 3 Web Server Quick Guide 8000038784_00_BAL_e...

Page 21: ...l Yield today kWh x x Cumulative yield for the day Total revenue Euro x x Cumulative revenue earned since initial startup Total CO2 saving kg x x Cumulative CO2 saved since initial startup Performance ratio x x Real time performance ratio Total yield kWh x x Cumulative yield since initial startup Power limit adjust ment x Maximum power limit as of nominal inverter AC output rating Note To calculat...

Page 22: ...ed LED will flash and the display will show an event Refer to the table for event descriptions and recommended actions Event text Description Remedy Grid Grid values are out of range Check the voltage and frequency values in the display If values are zero check the circuit breaker fuses and cables If values are outside the applied limits request technical service from in staller energy company PV ...

Page 23: ...e inverter cabinet using pressurised air a soft cloth or a brush 5 1 2 Cleaning the Heatsink Clean the heatsink using pressurised air a soft cloth or a brush For correct operation and long service life ensure free air circulation around the heatsink at the rear of the inverter to the fan at the inverter base Do not touch the heatsink during operation Temperature can exceed 70 C Note Do not cover t...

Page 24: ...ax 420 274 773 265 Email service cz aegps com Spain AEG Power Solutions SL Parque Tecnologico de Alava C Albert Einstein 31 01510 Minano Alava Tél 34 66 990 31 12 Fax 34 945 21 41 11 Email service es aegps com Netherlands AEG Power Solutions Weerenweg 29 1161 AH Zwanenburg Tel 31 20 40 77 818 821 Tel outside office hours 31 20 40 77 866 Fax 31 20 40 77 801 Email service nl aegps com Germany AEG Po...