background image

Protect alpha

DEALER STAMP/SIGNATURE

MODEL:
SERIAL NUMBER:
PURCHASE DATE: 

Emil-Siepmann-Str. 32 
59581 Warstein-Belecke – Germany 
Tel.: +49 180 523 4787 – Fax: +49 180 523 4789 
www.aegps.com

AEGPS - Pr

otect alpha

.

 450, 600, 800 - EN - 05/2013 V1 - T

echnical data in t

his document does not contain any bind

ing guarantees or warrant

ies. Content only serves for informat

ion purposes and 

can be mod

ified at any t

ime. W

e wil

l make bind

ing commitments only upon r

eceipt of concr

ete enquiries and customer not

ificat

ion of t

he r

elevant cond

itions. Due to t

he non-bind

ing natur

e of t

hese terms, we 

assume l

iabil

ity neit

her for t

he accuracy nor completeness of t

he data pr

ovided her

e. AEG is a r

egister

ed trademark used under l

icense fr

om AB Electr

olux.

Summary of Contents for Protect alpha 450

Page 1: ...USER MANUAL EN Protect alpha Uninterruptible Power Supply Protect alpha 450 Protect alpha 600 Protect alpha 800 ...

Page 2: ...n 3 2 Introduction 5 3 Trouble shooting 6 4 System description 7 4 1 Inspection 7 4 2 Charging 8 4 3 Placement 8 4 4 Connection 9 4 5 Turn On Off 9 4 6 DC start 9 4 7 Green Power Function 9 5 Specification 10 6 CE conformity 11 ...

Page 3: ... not plug the UPS input into its own output Do not attach a power strip or surge suppressor to the UPS Do not attach non computer related items such as medical equipment life support equipment microwave ovens or vacuum cleaners to the UPS To reduce the risk of overheating the UPS do not cover the UPS cooling vents and avoid exposing the unit to direct sunlight or installing the unit near heat emit...

Page 4: ... be operated by non technical users During the installation of this equipment it should be assured that the sum of the leakage currents of the UPS and the connected loads does not exceed 3 5 mA Attention electric shock hazard With disconnection of this unit from the mains hazardous voltage still may be accessible through the supply from the battery The battery supply should therefore be disconnect...

Page 5: ...input voltage range It is also built in with DC start function This function enables the UPS to be started up without AC power supplied Although it s a small UPS the main features of the Protect alpha UPS are listed below Microprocessor control guarantees high reliability Equipped with boost and buck AVR Green Power Function for energy saving DC start Function Auto restart while AC recovery Compac...

Page 6: ...again Alarm buzzer beeps continu ously when AC supply is normal Overload of the UPS Verify that the load matches the UPS capability specified in the specs In event of power failure back up time is shortened 1 Overload of the UPS 1 Remove some non critical load 2 Battery voltage is too low 2 Charge battery for 8 hours or more 3 Battery defective due to high temperature operation environment or impr...

Page 7: ...de Green flashing 3 Power switch Back panel 1 AC input 2 Output sockets 3 RJ11 communication 4 1 INSPECTION Remove the UPS from its packaging and inspect it for damage that may have occurred during shipping If any damage is discovered repack the unit and return it to the place of purchase ...

Page 8: ...leaving it plugged in for at least 6 hours with no load connected i e no electrical devices such as computers monitors etc 4 3 PLACEMENT Install the UPS unit in any protected environment that provides adequate airflow around the unit and is free from excessive dust corrosive fumes and conductive contaminants Do not operate your UPS in an environment where the ambient temperature or humidity is hig...

Page 9: ... power switch lightly To turn off the UPS unit press the power switch again 4 6 DC START All Protect alpha UPSs are equipped with DC start To start the UPS when AC utility power is not available simply press the power switch 4 7 GREEN POWER FUNCTION All Protect alpha UPSs are equipped with Green Power Function For saving power and protecting battery the method of deep discharging protection is ado...

Page 10: ... 7Ah 12 V 9Ah Recharge time 6 hours to 90 after complete discharge TRANSFER TIME Typical 2 6ms typical 10ms max INDICATOR AC mode Green LED Battery mode Green flashing LED AUDIBLE ALARM Backup mode Sounding every 10 seconds Low battery Sounding every 1 second Overload Sounding every 0 5 seconds Fault Continuously sounding PROTECTION Full protection Discharge overcharge and overload protection PHYS...

Page 11: ...11 6 CE CONFORMITY ...

Page 12: ...t contain any binding guarantees or warranties Content only serves for information purposes and can be modified at any time We will make binding commitments only upon receipt of concrete enquiries and customer notification of the relevant conditions Due to the non binding nature of these terms we assume liability neither for the accuracy nor completeness of the data provided here AEG is a register...

Reviews: