General Data
Classification
VFI SS 211 to IEC 62040–3
Double conversion technology
Overall efficiency (full load)
PROTECT C. 1000 R (S)
≥
85 %
PROTECT C. 2000 R (S)
≥
85 %
PROTECT C. 3000 R (S)
≥
88 %
PROTECT C. 6000 R
> 88 %
Noise level (1m distance)
PROTECT C. 1000 R (S)
< 45 dB (A)
PROTECT C. 2000 R (S)
< 50 dB (A)
PROTECT C. 3000 R (S)
< 50 dB (A)
PROTECT C. 6000 R
< 55 dB (A)
Type of cooling
Forced cooling
by variable speed fans
Operating temperature range 0°C to +40°C
Recommen15°C to
+25°C (due to battery
system)
Storage temperature range
0°C to +40°C
Relative humidity
< 95%, non-condensing
Max. site altitude
up to 1000 m at full load
If the UPS is installed or used
in a place where the altitude
is above than 1000m, the
output:
Altitude (m)
1000 1500 2000 2500 3000
Derating
Power
100% 95%
90%
85%
80%
19