UPS IST7 Series (60K-200K)
User Manual
5 Use and Operation
93
5.3.3 UPS Shutdown
When the system bypass is normal, after the UPS shutdown, system will turn to bypass power supply
mode; when system bypass is abnormal, after the UPS shutdown, system will be without output. Before
shutting down, please ensure that the load is closed and support the UPS power off at any time.
Step 1
Close the user load.
Step 2
Shut down the inverter.
Shutdown method 1: OFF combination button on the panel
Press the panel OFF combination button on the panel for 3s, the system will turn to the bypass
output from inverter output. View the system running status in the touch screen to check if the
system turns to the bypass power supply mode.
Shutdown method 2: Touch screen
In main page, click
icon, it will enter the ON/OFF page, as shown in Figure5-3, click
Confirm
button to perform the shutdown operation.
Figure5-3
Power off prompting
Step 3
Switch off the external battery switch
→
mains switch
→
bypass switch
→
output switch.
Step 4
After the touch screen and all LED indicators are off, the UPS is completely shut down.