2 Overview
UPS IST3-J (1-3kVA)
User Manual
24
2.4.1 Battery Box
Battery box for
IST3-J 1kVA
: 2 groups of 3*7AH12V battery
Battery box for
IST3-J 2kVA
: 2 groups of 4*9AH12V battery
Battery box for
IST3-J 3kVA
: 2 groups of 6*9AH12V battery
2.4.2 Programmable Outlets
There are two kinds of outputs: programmable outlets and general outlets. Please connect non-critical
devices to the programmable outlets and critical devices to the general outlets. During power failure,
you may extend the backup time to critical devices by setting shorter backup time for non-critical
devices.
2.4.3 Charging Module (7A)
AEC IST3-J
series (1K-3K) UPS can be equipped with a charging module with 7A to
enhance the charging capacity of UPS, which can match battery with different amperages to
ensure fast charging and prolong battery service life.