5
Install the unit by screwing three screws.
1-3KVA 24V, 1KVA/3KVA 48V model 2-3KVA 24V/48V Plus, 4-5KVA 48V model
Battery Connection
CAUTION:
For safety operation and regulation compliance, it’s requested to install a separate DC over-current
protector or disconnect device between battery and inverter. It may not be requested to have a disconnect
device in some applications, however, it’s still requested to have over-current protection installed. Please refer
to typical amperage in below table as required fuse or breaker size.
WARNING!
All wiring must be performed by a qualified personnel.
WARNING!
It's very important for system safety and efficient operation to use
appropriate cable for battery connection. To reduce risk of injury, please use the
proper recommended cable and terminal size as below.
Recommended battery cable and terminal size:
Model
Typical
Amperage
Battery
Capacity
Wire Size
Ring Terminal
Torque
Value
Cable
mm
2
Dimensions
D (mm) L (mm)
1KVA 48V
20A
100AH
1*14AWG
2
6.4
21.8
2~ 3 Nm
1KVA 24V, 2KVA 48V
33A
100AH
1*10AWG
5
6.4
22.5
2~ 3 Nm
3KVA 48V
50A
100AH
1*8AWG
8
6.4
23.8
2~ 3 Nm
2KVA 24V
66A
100AH
1*6AWG
14
6.4
29.2
2~ 3 Nm
200AH
2*10AWG
8
6.4
23.8
3KVA 24V
100A
100AH
1*4AWG
22
6.4
33.2
2~ 3 Nm
200AH
2*8AWG
14
6.4
29.2
4KVA
66A
200AH
1*4AWG
22
6.4
33.2
2~ 3 Nm
2*8AWG
14
6.4
29.2
5KVA
87A
200AH
1*4AWG
22
6.4
33.2
2~ 3 Nm
2*8AWG
14
6.4
29.2
Ring terminal: