25
MIC-1810 User Manual
C
ha
pte
r 3
In
itia
l S
etu
p
3.8.4
Measurement Type Selection
Measurement Type Selection
MIC-1816/MIC-1810 provides both current and voltage measurement for customers
to choose from. To configure this, you should follow below steps:
1.
Unscrew the bottom plate.
2.
Set the measurement type on SW2401 (Voltage: OFF, Current: ON).
3.
Set the channel to differential in software if current measurement mode is
selected.
4.
Set corresponded value range according to the switch setting.
SW2401
OFF, Voltage Measurement Mode (Default)
ON, Current Measurement Mode
Switch & Channel No.
Switch No. Channel
Switch No.
Channel
1
CH0 & CH1
5
CH8 & CH9
2
CH2 & CH3
6
CH10 & CH11
3
CH4 & CH57
7
CH12 & CH13
4
CH6 & CH7
8
CH14 & CH15