3. Setup and Connections
VlinxMESR9xx Modbus Gateway
Page 30
Manual Documentation Number MESR9xx-1016m
h.
Modbus Serial Retires – Select 0 through 5. This sets the maximum number of
times that the Modbus gateway will retry to send a Modbus message to a Modbus
client, before reporting a 0Bh exception if it is selected. Number of retries is
limited to 5.
i.
Milliseconds Modbus Message Timeout – This is the maximum amount of time to
wait for a response to the message. Valid value range is from 1 to 65535.
j.
Milliseconds TX Delay – This is the minimum amount of time after receiving a
response before the next message can be sent out. Valid value range is from 1 to
65535.
k.
Save settings by clicking the “Save” button.
12.
Port x ID Remap
a.
To access this screen, click the “Next” button or click the “Port x ID Remap” link
on the left side of the screen.
b.
This screen allows you to set Modbus Slave ID Remap settings.
Figure 38. Port ID Remap Screen
c.
The first box in line is the start of the remap range on the serial port you want to
remap. Valid value range is from 1 to 255.
d.
The second box in line is the last serial port of that range. Valid value range is
from 1 to 255.