Troubleshooting

Problem

Solution

The TX and RX connections are reversed.

Make sure the fiber connection is made so that the TX 

of one end is connected to the RX of the other.

Poor connection between the ADAM-4542+ and the 

communication port in computer.

Make sure the ADAM-4542+ is securely plugged into 

the communication port.

Attenuation on the fiber causes the signal level to drop 

below the accepted level.

Reduce attenuation by reducing connector loss, 

transmission distances, etc.

The connection between the communication ports is 

neither DTE to DTE nor DCE to DCE connection.

Add a converter to one of the optical modems, so that 

the pin assignments from the communication port to 

the modem are from pin 2 to pin3 and from pin 3 to 

pin 2.

Damage Test

If none of the above resolved your problem, your module may be damaged. To test for damage, use the hyper 

terminal program of MS Windows to perform a loop-back test of the optical modem. This will detect if the module 

is damaged.

Ring Operation System

Startup Manual 6

Summary of Contents for ADAM-4542+

Page 1: ...42 for a redundant architecture This special design offers higher reliability Features Direct plug and play Easily mounted on a DIN rail panel or piggybacked Transmission speeds of up to 921 6 kbps RS422 485 Optical fibers enable transmission of up to 15 km Half Full duplex bidirectional transmission mode Support for ring mode Avoid lightning strikes and EMI RFI Prevents damage from electrostatic ...

Page 2: ...hen you need to set SW2 Baud Rate SW2 1 2 3 4 5 6 7 8 9 1200 bps ON OFF OFF OFF OFF OFF OFF OFF OFF 2400 bps OFF ON OFF OFF OFF OFF OFF OFF OFF 4800 bps OFF OFF ON OFF OFF OFF OFF OFF OFF 9600 bps OFF OFF OFF ON OFF OFF OFF OFF OFF 19 2 kbps OFF OFF OFF OFF ON OFF OFF OFF OFF 38 4 kbps OFF OFF OFF OFF OFF ON OFF OFF OFF 57 6 kbps OFF OFF OFF OFF OFF OFF ON OFF OFF 115 2 kbps OFF OFF OFF OFF OFF OF...

Page 3: ...o save lots of cost caused from the number of modules and the length of optical fiber Following diagrams demonstrates the Ring application Ring Operation mode is set by DIP4 of SW3 Limitation While applying ring operation please notice the following limitations It only supports the half duplex Up to 100 ADAM 4542 can be connected over a distance of 1 500 km Under ring operation RS 232 422 485 all ...

Page 4: ...f module there are two sets of LED which are status LED and TX RX LED The meaning for LED display method is described as following table Description Status TX RX Green Red Red TransmittingData ON Receiving Data ON Power Fiber state Fiber Rx Redundant Working ON Power Fiber state Fiber Rx Redundant Failed ON If the module is set as a secondary module in the redundant structure no LED will be ON ...

Page 5: ...artup Manual 5 Wiring Diagrams Non Redundant System Redundant System Redundant systems can also support RS 422 In a redundant system the ground of the external power for modules must be connected together ...

Page 6: ... Reduce attenuation by reducing connector loss transmission distances etc The connection between the communication ports is neither DTE to DTE nor DCE to DCE connection Add a converter to one of the optical modems so that the pin assignments from the communication port to the modem are from pin 2 to pin3 and from pin 3 to pin 2 Damage Test If none of the above resolved your problem your module may...

Reviews: