background image

4    ADAM-4510/4510S/4520  Startup Manual

 

Power Supply

For easy use in industrial environments, the ADAM mod-
ules are designed to accept industry st24 V

DC

 

unregulated power. Operation is guaranteed when using 
any power supply b10 and +30 V

DC

. Power rip-

ples must be limited to 5 V peak to peak while the voltage 
in all cases must be maintained b10 and +30 
V

DC

. All power supply specifications are referenced at 

module connector.

The power cables should be selected according to the 
number of modules connected and the length of the 
power lines. When using a network with long cables, we 
advise the use of thicker wire to limit the line voltage drop. 
In addition to serious voltage drops, long voltage lines can 
also cause interference with communication wires.

We advise that the following standard colors (as

indicated on the modules) be used for power lines:

+Vs (R) Red

GND (B) Black

Communication Wiring

We recommend that shielded-twisted-pair cables that 
comply with the EIA RS-485 standard be used with the 
ADAM network to reduce interference. Only one set of 
twisted-pair cables is required to transmit both data and 
RTS signals. We advise that the following standard colors 
(as indicated on the modules) be used for the communica-
tion lines:

DATA + (Y) Yellow

DATA - (G) Green

Basic configuration hook-up.

Before placing a module in an existing network, the mod-
ule should be properly configured. The two following dia-
grams show typical layouts for both modules.

Application Wiring

Power Supply

+10~30 V

-

+

(G

) DAT

A-

(R

) +

V

s

(B

) GN

D

  1

0

ADAM Dimensions

DATA +

DATA -

Rx +

Rx -

Tx +

Tx -

DATA +

DATA -

Tx +

Tx -

Rx +

Rx -

RS-485 Device

RS-422 Device

TxD (2)

RxD (3)
RTS (7)

GND (5)

RxD (2)
TxD (3)
RTS (7)

GND (5)

Host

DB-9 female

connector

DATA +

DATA -

Tx +

Tx -

Rx +

Rx -

DATA0 +

DATA0 -

Rx 0+

Rx 0-

Tx 0+

Tx 0-

RS-485 Device

RS-422 Host

DATA +

DATA -

Rx +

Rx -

Tx +

Tx -

DATA1 +

DATA1 -

Tx 1+

Tx 1-

Rx 1+

Rx 1-

RS-485 Device

RS-422 Slave

Reviews: