4
B. RUN MENU
During normal operations the controller will be in the RUN mode where current values are displayed. If left
in the SET UP mode the display will revert to the RUN mode screen if no keys are touched for 3 minutes. If
an alarm is present, it will flash on the screen in the RUN mode.
While in the RUN mode, hit the down arrow to show the following items:
DAY-TIME
Current day or the week and time.
DATE
Current date.
CHEM (A-E)
If a chemical feed relay is on, how long it has been on.
GALLONS
If a water meter is being used, total number of gallons made up.
WATER METER
If a water meter is being used, number of contacts
VI. Troubleshooting
The Advantage Microtron controller is designed for many years of trouble free operation. Should a
problem occur, refer to the following chart to help identify the problem.
SYMPTOM
POSSIBLE CAUSE SOLUTION
No system power
Power source
Check power source
Cable from power supply
Secure cable
board to relay board
No output power
Check relay fuse
Replace as needed
Check ribbon cable from
Secure ribbon cable
logicboard to relays
& orientation
Not receiving water meter
Connection between unit and Check cable between water
contacts
water meter
meter and unit
Meter input set incorrectly
Check meter input in
System Set
If problem persists, contact our customer service department with the model number and serial
number and software version (found under diagnostics) of unit for free factory technical assistance
at 800-743-743.