15
Units with a biocide timer will have this SET UP menu
for setting biocide feed times. Biocide Set Menu
consists of two weekdays, week and start times, one
feed length time and an overall prebleed and lockout
setting for each biocide.
BIO __ (A1,A2,B1,B2...) WEEKDA
Y - Select from
Sunday through Saturday, or TuesThrSat, MonWedFri,
Every Other day, Every Day or No Day. A setting of No
Day disables timer.
BIO__(A1,A2,B1,B2 ...) WEEK
- Select week (1-4),
Even Weeks, Odd Weeks, or Every Week. A setting of
No Week disables timer.
BIO__(A1,A2,B1,B2 ...) MONTH
- Select month
(1-12), Even Month, Odd Month, or Every Month.
A setting of No Month disables timer.
BIO_(A,B,C...)TIME HH.MM
- Start time based on 24
hour clock, in hours and minutes.
BIO_(A,B,C...) LENGTH H.MM
- Feed time in hours
and minutes can be set up to 9 hours and 59 minutes,
0 (zero) disables both start times for that biocide.
BIO_ (A,B,C...) PREBLEED H.MM
- Prebleed and
lockout settings are in hours and minutes, with a
maximum of 9 hours and 59 minutes, 0 (zero) disables
timer. When the clock reaches a start time for any of
the four timers, the Prebleed is begun.
BIO_(A,B,C...) LOCKOUT H.MM
- The lockout timer
is a timer that starts after the biocide feed time is
finished. The timer can be set for a time up to 9 hours
and 59 minutes to lock out the bleed.
7.
CLOCK SET
-- BIOCIDE SET --
Shows BIO A timer 1 activation day
To change day of the week
To cycle through day options
SUN,MON,TUES,WED,THUR,FRI,SAT,
ALTERNATE ...
To select day
Shows BIO A timer 1 activation week
To change week
To cycle through week options
press ENTER to set week
Shows BIO A timer 1 activation month
To change month
To cycle through month options
press ENTER to set month
Shows BIO A Timer 1 start time of day
To change Time of Day
To enter time keyed in using
number keys
Menu repeats for BIO A Timer 2
BIO A LENGTH 0.00 (H.MM)
To change length
To accept value keyed in
using number keys.
BIO A PREBLEED 0.00 (H.MM)
To change length
To enter time keyed in
using number keys.
Continued..
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
CLEAR
ENTER
CLEAR
ENTER
CLEAR
BIO A LOCKOUT 0.00 (H.MM)
To change length
To enter time keyed in
using number keys.
Program repeats for addional biocide
timers if ordered (B, C, and D)
ENTER
CLEAR