26
5.2
Date and Time Set Up
DATE AND TIME
- For setting the date, time, day and
week on the controller.
5.3
Relays
CONFIGURE RELAYS
- This menu lets you choose a
Main Action
or function (timer 1, conductivity, alarms
etc...) to activates a relay.
A pop-up screen appears with a list of all available
activation functions to arrow through.
Additional relay logic is available with up to 3 additional
Activators
and up to 4
Disablers
allowing multiple
functions to activate the same relay and multiple functions to prevent the relay from coming on. There is
also a Daily Max amount of time that a relay can be on. If a relay is on for the max amount, it does not
let the relay come on anymore that day. (A 24 hour clock is used for the day with midnight being the start
of the day). The Delay setting is the amount of time a control function must come on before the relay will
UHDFWDQGDFWLYDWH7KLVLVWRSUHYHQWDUHOD\IURPFKDWWHULQJRQRႇLIDUHDGLQJLVERXQFLQJDURXQGWKHVHW
point or alarm.
5.4
History
7KLVPHQXLVXVHGWRVHWWKHKLVWRU\³WLPHVWDPS´LQWHUYDOWKHZDWHUPHWHUGDLO\KLVWRU\VWDUWLQJKRXUWKH
alarm delay period and the USB history save format.
INTERVAL
- The amount of time between each history
time stamp for probe readings.
W/M HOUR
- The time of day that the daily water
meter history cycle is to start.
ALARM DELAY
- The amount of time an alarm has to
be on before it is recognized as an alarm.
SAVE FORMAT
- The USB history save format.