MyDict - MyAir3 as Master with Panasonic A/C
2
2013
Panasonic Unit
1.
Install the Panasonic indoor and outdoor unit according to Panasonic’s instructions. Do not
connect any MyAir electronics.
2.
Connect up the Panasonic wall controller in the roof space, there is no need to run the
controller down the wall as it will be only be used to configure the system initially then it will be
disconnected & removed later.
3.
Test the Panasonic system completely using this Panasonic wall controller.
4.
Once testing is complete proceed to next step (Field Settings).
Panasonic Field Settings
Setup the Panasonic wall controller as follows for the CZ-
RTC2 Panasonic remote controller.
NOTE:
There are two separate field settings menus that you
need to access and change.
1.
Menu 1
a.
Press and hold the MODE (Top Right) & TIMER
SET buttons together on the remote controller
for more than 4 seconds.
b.
Select the code you would like to change with
the UP & DOWN
TEMPERATURE
buttons
c.
Change the codes value with UP & DOWN
TIMER
buttons
d.
Set the following
i.
01 = 0001
ii.
OA = 0001 (
Essential for MyZone
TM
feature when using MyAir temperature
sensors
).
e.
When you are done press the SET button
f.
Then press the SPANNER button
g.
Remote returns to main screen