1  Wiring Configuration 

The diagram below 

shows a ‘typical’ application for the 4A sounder booster. Note that a 10KΩ EOL resistor 

must be fitted to the end of the boosted sounder output circuit to maintain correct fault monitoring. 

 

Mxp-026 Wiring Configuration. 

 

Note. PSU ‘

Failsafe’

 Operation

 

The EN54 

PSU shall be fitted with a ‘Fault’ relay that is energised during normal operation and de-energised for 

any fault condition. The ‘FAULT I/P’ connections on the sounder booster card should be connected to the ‘COM’ 
and ‘N/O’ connections of the PSU as shown above. The table below indicates the state of the relay for all 
conditions.

 

 

PSU ‘ON’ without Fault 

(Energised) 

PSU ‘ON’ with Fault 

(De-energised) 

PSU ‘OFF’ 

(De-energised) 

Relay Contacts 

Com – N/O 

Closed 

Open 

Open 

Relay Contacts 

Com – N/C 

Open 

Closed 

Closed 

 

From the panel 
sounder output 
circuit. 

10K EOL resistor 
must be fitted to the 
end of the boosted 
output circuit for 
correct fault 
monitoring. 

V

– 

V

o +

 

B

A

T +

 

BAT

– 

N/

N/

O

 

CO

M

 

5A EN54 PSU 

(-BXP) 

4A Boosted O/P 